Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ▷ View online
6
CAUTION
10.
Power supply connection to Indoor Unit.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
Must follow local national wiring standard, regulation and this installation instruction.
Strongly recommended to make permanent connection to a circuit breaker.
-
-
Power supply 1: Use approved 30A 2-poles circuit breaker with a minimum contact gap of 3.0 mm.
-
Power supply 2: Use approved 30A 2-poles circuit breaker with a minimum contact gap of 3.0 mm.
11. Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fire.
12.
After installation, check the water leakage condition in connection area during test run. If leakage occurs, it will cause damage to other
properties.
properties.
13.
Installation work.
It may need two or more people to carry out the installation work. The weight of Indoor Unit / Outdoor Unit might cause injury if carried
by one person.
It may need two or more people to carry out the installation work. The weight of Indoor Unit / Outdoor Unit might cause injury if carried
by one person.
7
2. Specifications
2.1 WH-SXC09H3E5
WH-UX09HE5
Item
Unit
Outdoor Unit
Performance Test Condition
EN 14511
Condition
(Ambient/Water)
A35W7
kW 7.00
BTU/h 23900
Cooling Capacity
kcal/h 6020
W/W 3.17
Cooling EER
kcal/hW 2.72
Condition
(Ambient/Water)
A7W35 A2W35
kW 9.00
9.00
BTU/h 30700
30700
Heating Capacity
kcal/h 7740
7740
W/W 4.84
3.59
Heating COP
kcal/hW 4.16
3.08
Low Temperature Application (W35)
Application Climate
Warmer Average Colder
Pdesign kW
9.0
9.0
11.0
Tbivalent / TOL
°C
2 / 2
-10 / -10
-15 / -22
SCOP / ns
(W/W) / %
5.95 / 235
4.59 / 181
4.08 / 160
Annual Consumption
kWh
2020
4049
6651
Class
A++ A++ A++
Medium Temperature Application (W55)
Application Climate
Warmer Average Colder
Pdesign kW
9.0
9.0
11.0
Tbivalent / TOL
°C
2 / 2
-10 / -10
-15 / -22
SCOP / ns
(W/W) / %
4.02 / 158
3.32 / 130
3.20 / 125
Annual Consumption
kWh
2991
5596
8468
Heating ErP
Class
A++ A++ A++
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
dB (A)
Cooling: 49
Heating: 51
—
Noise Level
Power Level dB
Cooling: 67
Heating: 68
—
Air Flow
m
3
/min (ft
3
/min)
Cooling: 89.5 (3160)
Heating: 76.8 (2710)
Heating: 76.8 (2710)
Refrigeration Control Device
Expansion Valve
Refrigeration Oil
cm
3
FV50S
(1200)
Refrigerant (R410A)
kg (oz)
2.85 (100.6)
GWP 2088
F-GAS
CO2eq (ton) (Precharged / Maximum)
5.951 / 8.039
Height
mm (inch)
1340 (52-3/4)
Width
mm (inch)
900 (35-7/16)
Dimension
Depth
mm (inch)
320 (12-19/32)
Net Weight
kg (lbs)
101 (223)
Liquid
mm (inch)
9.52 (3/8)
Pipe Diameter
Gas
mm (inch)
15.88 (5/8)
Standard Length
m (ft)
7 (23.0)
Pipe Length Range
m (ft)
3 (9.8) ~ 30 (98.4)
I/D & O/D Height Difference
m (ft)
20 (65.6)
8
Item
Unit
Outdoor Unit
Additional Gas Amount
g/m (oz/ft)
50 (0.5)
Refrigeration Charge Less
m (ft)
10 (32.8)
Type
Hermetic
Motor
Motor Type
Brushless (4-poles)
Compressor
Rated Output
kW
3.00
Type
Propeller
Fan
Material
PP
Motor Type
DC (8-poles)
Input Power
W
—
Output Power
W
60
Fan
Fan Speed
rpm
Cooling: 550 (Top), 590 (Bottom)
Heating: 490 (Top), 530 (Bottom)
Heating: 490 (Top), 530 (Bottom)
Fin material
Aluminium (Pre Coat)
Fin Type
Corrugated Fin
Row × Stage × FPI
2 × 51 × 18
Heat Exchanger
Size (W × H × L)
mm
903.7 × 1295.4 × 38.1
ø Single
V 230
Power Source (Phase, Voltage, Cycle)
Hz 50
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
Input Power
kW
Cooling: 2.21
Heating: 1.86
Heating: 2.51
Maximum Input Power For Heatpump System
kW
6.27
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
1Ø / 29.0 / 6.27k
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
1Ø / 13.0 / 3.00k
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
— / — / —
Starting Current
A
10.2
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
Running Current
A
Cooling: 10.4
Heating: 8.8
Heating: 11.8
Maximum Current For Heatpump System
A
29.0
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
Power factor means total figure of compressor and
outdoor fan motor.
%
Cooling: 92
Heating: 92
Heating: 92
Number of core
—
Power Cord
Length m
(ft)
—
Thermostat
Electronic
Control
Protection Device
Electronic Control
9
Item
Unit
Indoor Unit
Performance Test Condition
EN 14511
Outdoor Ambient
°C
Cooling: 16 ~ 43
Heating: -28 ~ 35
Operation Range
Water Outlet
°C
Cooling: 5 ~ 20
Heating: 20 ~ 55 (Below Ambient -15°C)
20 ~ 60 (Below Ambient -10°C)
Internal Pressure Differential
kPa
Cooling: 20
Heating: 30
Heating: 30
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
dB (A)
Cooling: 33
Heating: 33
—
Noise Level
Power Level dB
Cooling: 46
Heating: 46
—
Height
mm (inch)
892 (35-1/8)
Width
mm (inch)
500 (19-11/16)
Dimension
Depth
mm (inch)
340 (13-13/32)
Net Weight
kg (lbs)
43 (95)
Liquid
mm (inch)
9.52 (3/8)
Refrigerant Pipe Diameter
Gas
mm (inch)
15.88 (5/8)
Inlet
mm (inch)
28 (1-3/32)
Water Pipe Diameter
Outlet
mm (inch)
28 (1-3/32)
Water Drain Hose Inner Diameter
mm (inch)
15 (19/32)
Motor Type
DC Motor
No. of Speed
7 (Software Selection)
Pump
Input Power
W
58
Type
Brazed
Plate
No. of Plates
36
Size (W × H × L)
mm
65 × 119 × 376
Hot Water Coil
Water Flow Rate
l/min (m
3
/h)
Cooling: 20.1 (1.2)
Heating: 25.8 (1.5)
Heating: 25.8 (1.5)
Pressure Relief Valve Water Circuit
kPa
Open: 300, Close: 266 and below
Flow Switch
Electronic Sensor
Protection Device
A
Residual Current Circuit Breaker (40)
Volume I
10
Expansion Vessel
MWP bar
3
Capacity of Integrated Electric Heater
kW
3.00
Note:
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled indoor water inlet
temperature of 12°C and water outlet temperature of 7°C.
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb
(42.8°F Wet Bulb) with controlled indoor water inlet temperature of 30°C and water outlet temperature of 35°C.
Specification are subjected to change without prior notice for further improvement.
Flow rate indicated are based on nominal capacity adjustment of leaving water temperature (LWT) 35°C and
Flow rate indicated are based on nominal capacity adjustment of leaving water temperature (LWT) 35°C and
∆
T
= 5°C.