CAUTION 
10. 
Power supply connection to Indoor Unit. 
 
Power supply point should be in easily accessible place for power disconnection in case of emergency. 
 
Must follow local national wiring standard, regulation and this installation instruction. 
 
Strongly recommended to make permanent connection to a circuit breaker. 
Power supply 1: Use approved 30A 2-poles circuit breaker with a minimum contact gap of 3.0 mm. 
Power supply 2: Use approved 30A 2-poles circuit breaker with a minimum contact gap of 3.0 mm. 
 
11.  Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fire. 
 
12. 
After installation, check the water leakage condition in connection area during test run. If leakage occurs, it will cause damage to other 
properties. 
 
13. 
Installation work. 
It may need two or more people to carry out the installation work. The weight of Indoor Unit / Outdoor Unit might cause injury if carried 
by one person. 
 
2. Specifications 
2.1 WH-SXC09H3E5 
WH-UX09HE5 
 
Item 
Unit 
Outdoor Unit 
Performance Test Condition 
EN 14511 
Condition 
(Ambient/Water) 
A35W7 
kW 7.00 
BTU/h 23900 
Cooling Capacity 
kcal/h 6020 
W/W 3.17 
Cooling EER 
kcal/hW 2.72 
Condition 
(Ambient/Water) 
A7W35 A2W35 
kW 9.00 
9.00 
BTU/h 30700 
30700 
Heating Capacity 
kcal/h 7740 
7740 
W/W 4.84 
3.59 
Heating COP 
kcal/hW 4.16 
3.08 
Low Temperature Application (W35) 
Application Climate 
Warmer Average  Colder 
Pdesign kW 
9.0 
9.0 
11.0 
Tbivalent / TOL 
°C 
2 / 2 
-10 / -10 
-15 / -22 
SCOP / ns 
(W/W) / % 
5.95 / 235 
4.59 / 181 
4.08 / 160 
Annual Consumption 
kWh 
2020 
4049 
6651 
Class 
 
A++ A++ A++ 
Medium Temperature Application (W55) 
Application Climate 
Warmer Average  Colder 
Pdesign kW 
9.0 
9.0 
11.0 
Tbivalent / TOL 
°C 
2 / 2 
-10 / -10 
-15 / -22 
SCOP / ns 
(W/W) / % 
4.02 / 158 
3.32 / 130 
3.20 / 125 
Annual Consumption 
kWh 
2991 
5596 
8468 
Heating ErP 
Class 
 
A++ A++ A++ 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
dB (A) 
Cooling: 49 
Heating: 51 
— 
Noise Level 
Power Level dB 
Cooling: 67 
Heating: 68 
— 
Air Flow 
m
3
/min (ft
3
/min) 
Cooling: 89.5 (3160) 
Heating: 76.8 (2710) 
Refrigeration Control Device 
 
Expansion Valve 
Refrigeration Oil 
cm
3
 FV50S 
(1200) 
Refrigerant (R410A) 
kg (oz) 
2.85 (100.6) 
GWP 2088 
F-GAS 
CO2eq (ton) (Precharged / Maximum) 
5.951 / 8.039 
Height 
mm (inch) 
1340 (52-3/4) 
Width 
mm (inch) 
900 (35-7/16) 
Dimension 
Depth 
mm (inch) 
320 (12-19/32) 
Net Weight 
kg (lbs) 
101 (223) 
Liquid 
mm (inch) 
9.52 (3/8) 
Pipe Diameter 
Gas 
mm (inch) 
15.88 (5/8) 
Standard Length 
m (ft) 
7 (23.0) 
Pipe Length Range 
m (ft) 
3 (9.8) ~ 30 (98.4) 
I/D & O/D Height Difference 
m (ft) 
20 (65.6) 
Item 
Unit 
Outdoor Unit 
Additional Gas Amount 
g/m (oz/ft) 
50 (0.5) 
Refrigeration Charge Less 
m (ft) 
10 (32.8) 
Type  
Hermetic 
Motor 
Motor Type 
 
Brushless (4-poles) 
Compressor 
Rated Output 
kW 
3.00 
Type  
Propeller 
Fan 
Material  
PP 
Motor Type 
 
DC (8-poles) 
Input Power 
— 
Output Power 
60 
Fan 
Fan Speed 
rpm 
Cooling: 550 (Top), 590 (Bottom) 
Heating: 490 (Top), 530 (Bottom) 
Fin material 
 
Aluminium (Pre Coat) 
Fin Type 
 
Corrugated Fin 
Row × Stage × FPI 
 
2 × 51 × 18 
Heat Exchanger 
Size (W × H × L) 
mm 
903.7 × 1295.4 × 38.1 
ø Single 
V 230 
Power Source (Phase, Voltage, Cycle) 
Hz 50 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
Input Power 
kW 
Cooling: 2.21 
Heating: 1.86 
Heating: 2.51 
Maximum Input Power For Heatpump System 
kW 
6.27 
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
1Ø / 29.0 / 6.27k 
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
1Ø / 13.0 / 3.00k 
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
— / — / — 
Starting Current 
10.2 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
Running Current 
Cooling: 10.4 
Heating: 8.8 
Heating: 11.8 
Maximum Current For Heatpump System 
29.0 
Power Factor 
Power factor means total figure of compressor and 
outdoor fan motor. 
Cooling: 92 
Heating: 92 
Number of core 
 
— 
Power Cord 
Length m 
(ft) 
— 
Thermostat  
Electronic 
Control 
Protection Device 
 
Electronic Control 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Item 
Unit 
Indoor Unit 
Performance Test Condition 
EN 14511 
Outdoor Ambient 
°C 
Cooling: 16 ~ 43 
Heating: -28 ~ 35 
Operation Range 
Water Outlet 
°C 
Cooling: 5 ~ 20 
Heating: 20 ~ 55 (Below Ambient -15°C) 
               20 ~ 60 (Below Ambient -10°C) 
Internal Pressure Differential 
kPa 
Cooling: 20 
Heating: 30 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
dB (A) 
Cooling: 33 
Heating: 33 
— 
Noise Level 
Power Level dB 
Cooling: 46 
Heating: 46 
— 
Height 
mm (inch) 
892 (35-1/8) 
Width 
mm (inch) 
500 (19-11/16) 
Dimension 
Depth 
mm (inch) 
340 (13-13/32) 
Net Weight 
kg (lbs) 
43 (95) 
Liquid 
mm (inch) 
9.52 (3/8) 
Refrigerant Pipe Diameter 
Gas 
mm (inch) 
15.88 (5/8) 
Inlet 
mm (inch) 
28 (1-3/32) 
Water Pipe Diameter 
Outlet 
mm (inch) 
28 (1-3/32) 
Water Drain Hose Inner Diameter 
mm (inch) 
15 (19/32) 
Motor Type 
 
DC Motor 
No. of Speed 
 
7 (Software Selection) 
Pump 
Input Power 
58 
Type  
Brazed 
Plate 
No. of Plates 
 
36 
Size (W × H × L) 
mm 
65 × 119 × 376 
Hot Water Coil 
Water Flow Rate 
l/min (m
3
/h) 
Cooling: 20.1 (1.2) 
Heating: 25.8 (1.5) 
Pressure Relief Valve Water Circuit 
kPa 
Open: 300, Close: 266 and below 
Flow Switch 
 
Electronic Sensor 
Protection Device 
Residual Current Circuit Breaker (40) 
Volume I 
10 
Expansion Vessel 
MWP bar 
Capacity of Integrated Electric Heater 
kW 
3.00 
Note: 
  Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled indoor water inlet 
temperature of 12°C and water outlet temperature of 7°C. 
  Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb 
(42.8°F Wet Bulb) with controlled indoor water inlet temperature of 30°C and water outlet temperature of 35°C. 
  Specification are subjected to change without prior notice for further improvement. 