DOWNLOAD Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ↓ Size: 15.68 MB | Pages: 127 in PDF or view online for FREE

Model
WH-SXC09H3E5 WH-SXC12H6E5 WH-UX09HE5 WH-UX12HE5
Pages
127
Size
15.68 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR-TO-WATER HEATPUMP
File
wh-sxc09h3e5-wh-sxc12h6e5-wh-ux09he5-wh-ux12he5.pdf
Date

Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ▷ View online

18.
 
Technical Data................................................213
 
18.1
 
Operation Characteristics ..........................213
 
18.2
 
Heating Capacity Table .............................225
 
18.3
 
Cooling Capacity Table .............................225
 
19.
 
Exploded View and Replacement Parts List .....
 .........................................................................226
 
19.1
 
Indoor Unit .................................................226
 
19.2
 
Outdoor Unit ..............................................229
 
1. Safety Precautions 
  Read the following “SAFETY PRECAUTIONS” carefully before installation. 
  Electrical work must be installed by a licensed electrician. Be sure to use the correct rating and main circuit for 
the model to be installed. 
  The caution items stated here must be followed because these important contents are related to safety. The 
meaning of each indication used is as below. Incorrect installation due to ignoring of the instruction will cause 
harm or damage, and the seriousness is classified by the following indications. 
  Please leave this installation manual with the unit after installation. 
 
 
WARNING 
This indication shows the possibility of causing death or serious injury. 
 
CAUTION 
This indication shows the possibility of causing injury or damage to properties only. 
 
 
The items to be followed are classified by the symbols: 
 
 
Symbol with white background denotes item that is PROHIBITED from doing. 
 
Symbol with dark background denotes item that must be carried out. 
 
 
Carry out test run to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and 
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference. 
 
 
WARNING 
1. 
Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with 
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire. 
 
2.  Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen. 
 
3.  Keep plastic bag (packaging material) away from small children, it may cause suffocation. 
 
4.  Do not use pipe wrench to install refrigerant piping. It might deform the piping and cause the unit to malfunction. 
 
5.  Do not purchase unauthorized electrical parts for installation, service, maintenance and etc. They might cause electrical shock or fire. 
 
6. 
Do not modify the wiring of Indoor Unit for installation of other components (i.e. heater, etc). Overloaded wiring or wire connection 
points may cause electrical shock or fire. 
 
7.  Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc. 
 
8. 
Do not use joint cable for Indoor / Outdoor Unit connection cable. Use specified Indoor / Outdoor Unit connection cable, refer to 
instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for Indoor / Outdoor Unit connection. Clamp the cable 
so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat up or fire at the 
connection. 
 
9. 
Do not install outdoor unit near handrail of veranda. When installing outdoor unit at veranda of high rise building, child may climb up to 
outdoor unit and cross over the handrail and causing accident. 
 
10.  Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury. 
 
 
11.  Do not sit or step on the unit, you may fall down accidentally. 
 
 
12. 
For electrical work, follow local wiring standard, regulation and this installation instruction. An independent circuit and single outlet 
must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire. 
 
13. 
For water circuit installation work, follow to relevant European and national regulations (including EN61770) and local plumbing and 
building regulation codes. 
 
14. 
Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or 
fire. 
 
15. 
 
This is a R410A model, when connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may 
cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only R410A 
refrigerant. 
 
Thickness or copper pipes used with R410A must be 0.8 mm or more. Never use copper pipes thinner than 0.8 mm. 
 
It is desirable that the amount of residual oil is less than 40mg/10m. 
 
16. 
When install or relocate Indoor Unit / Outdoor Unit, do not let any substance other than the specified refrigerant, e.g. air etc. mix into 
refrigerant cycle (piping). Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.. 
 
17.  Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 
 
 
WARNING 
18. 
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not 
properly done, the set will drop and cause injury. 
 
19. 
This equipment is strongly recommended to be installed with Residual Current Device (RCD) on-site according to the respective 
national wiring rules or country–specific safety measures in terms of residual current. 
 
20. 
During installation, install the refrigerant piping properly before run the compressor. Operation of compressor without fixing 
refrigeration piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in 
explosion, injury etc. 
 
21. 
During pump down operation, stop the compressor before remove the refrigeration piping. Removal of refrigerant piping while 
compressor is operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigerant cycle and result in 
explosion, injury etc. 
 
22. 
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over tightened, after a long period, the flare 
may break and cause refrigerant gas leakage. 
 
23. 
After completion of installation, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts 
with fire. 
 
24. 
Ventilate the room if there is refrigerant gas leakage during operation. Extinguish all fire sources if present. It may cause toxic gas 
when the refrigerant contacts with fire. 
 
25.  Only use the supplied or specified installation parts, else, it may cause unit vibrate loose, water leakage, electrical shock or fire. 
 
26. 
The unit is only for use in closed water system. Utilization in an open water circuit may lead to excessive corrosion of water piping and 
risk of incubating bacteria colonies, particularly Legionella, in water. 
 
27.  If there is any doubt about the installation procedure or operation, always contact the authorized dealer for advice and information. 
 
28.  Select a location where in case of water leakage, the leakage will not cause damage to other properties. 
 
29. 
When installing electrical equipment at wooden building of metal lath or wire lath, in accordance with electrical facility standard, no 
electrical contact between equipment and building is allowed. Insulator must be installed in between. 
 
30. 
Any work carried out on the Indoor Unit / Outdoor Unit after removing any panels which is secured by screws, must be carried out 
under the supervision of authorized dealer and licensed installation contractor. 
 
31. 
This unit must be properly earthed. The electrical earth must not be connected to a gas pipe, water pipe, the earth of lightening rod or 
a telephone. Otherwise there is a danger of electrical shock in the event of an insulation breakdown or electrical earth fault in the 
outdoor unit. 
 
32. 
Do not use joint cable for outdoor connection cable. Use specified outdoor connection cable, refer to instruction CONNECT THE 
CABLE TO THE OUTDOOR UNIT 
and connect tightly for outdoor connection. Clamp the cable so that no external force will be acted 
on the terminal. If connection or fixing is not perfect, it will cause heat up or fire at the connection. 
 
 
 
CAUTION 
1. 
Do not install the Indoor Unit / Outdoor Unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates 
at surrounding of the unit, it may cause fire. 
 
2. 
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the 
liquid refrigerant, it may cause frostbite. 
 
3.  Do not install this appliance in a laundry room or other high humidity location. This condition will cause rust and damage to the unit. 
 
4.  Make sure the insulation of power supply cord does not contact hot part (i.e. refrigerant piping) to prevent from insulation failure (melt).
 
5. 
Do not apply excessive force to water pipes that may damage the pipes. If water leakage occurs, it will cause flooding and damage to 
other properties. 
 
6.  Do not touch the sharp aluminium fin, sharp parts may cause injury. 
 
 
7. 
Do not release refrigerant into the atmosphere. The product contains fluorinated greenhouse gases and that its functioning relies upon 
such gases. 
 
8.  Select an installation location which is easy for maintenance. 
 
9. 
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage 
the furniture. 
 
 
 
 
 
 
 
 
CAUTION 
10. 
Power supply connection to Indoor Unit. 
 
Power supply point should be in easily accessible place for power disconnection in case of emergency. 
 
Must follow local national wiring standard, regulation and this installation instruction. 
 
Strongly recommended to make permanent connection to a circuit breaker. 
Power supply 1: Use approved 30A 2-poles circuit breaker with a minimum contact gap of 3.0 mm. 
Power supply 2: Use approved 30A 2-poles circuit breaker with a minimum contact gap of 3.0 mm. 
 
11.  Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fire. 
 
12. 
After installation, check the water leakage condition in connection area during test run. If leakage occurs, it will cause damage to other 
properties. 
 
13. 
Installation work. 
It may need two or more people to carry out the installation work. The weight of Indoor Unit / Outdoor Unit might cause injury if carried 
by one person. 
 
Page of 127
Display

Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ▷ Download

  • DOWNLOAD Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ↓ Size: 15.68 MB | Pages: 127 in PDF or view online for FREE
  • Here you can View online or download the Service Manual for the Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 in PDF for free, which will help you to disassemble, recover, fix and repair Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Air Conditioner. Information contained in Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual (repair manual) includes:
  • Disassembly, troubleshooting, maintenance, adjustment, installation and setup instructions.
  • Schematics, Circuit, Wiring and Block diagrams.
  • Printed wiring boards (PWB) and printed circuit boards (PCB).
  • Exploded View and Parts List.