12.19 Boiler Bivalent Control
- Boiler is an additional or alternative heat source to heat up the room when necessary.
- Purpose of this control is to turn ON and turn OFF the Boiler output signal when boiler heating capacity
- Purpose of this control is to turn ON and turn OFF the Boiler output signal when boiler heating capacity
needed in the system.
- Boiler is possible to connect to DHW Tank and Buffer Tank depends on the installer.
- Boiler operation parameter need to be set on Boiler itself, indoor do not control the boiler operation direction
- Boiler operation parameter need to be set on Boiler itself, indoor do not control the boiler operation direction
and operation.
- There are Alternative mode, Parallel mode, & Advance Parallel mode available to select by installer to fit to
the total system.
Bivalent control selection by remote controller
Remote control setting value:
1) Outdoor Ambient Set = (Range: -15°C ~ 15°C)
a) Alternative
Mode
- Only one heat source operates at one time, either heat pump or boiler depends on condition.
Control detail:
During Operation ON at Heat mode or Tank mode or Heat + Tank Mode
- Boiler signal turn ON and heat pump and water pump turn OFF when:
During Operation ON at Heat mode or Tank mode or Heat + Tank Mode
- Boiler signal turn ON and heat pump and water pump turn OFF when:
a. Outdoor ambient < Outdoor Ambient Set AND
b. Boiler prohibit flag = 0
b. Boiler prohibit flag = 0
** However indoor water pump can operate when Anti-freeze control condition fulfilled.
- Boiler signal turn OFF and heat pump and water pump turn ON when:
a. Outdoor ambient > Outdoor Ambient Set + [2°C] OR
b. Boiler prohibit flag = 1
b. Boiler prohibit flag = 1
b) Parallel
Mode
- Parallel mode allows heat pump and boiler ON at the same time. Boiler operates as an additional heating
capacity when low heat pump capacity at low ambient condition.
Control detail:
During operation ON at Heat mode or Tank mode or Heat + Tank mode
- Boiler signal turns ON when:
During operation ON at Heat mode or Tank mode or Heat + Tank mode
- Boiler signal turns ON when:
a. Outdoor ambient < Outdoor Ambient Set AND
b. Boiler prohibit flag = 0
b. Boiler prohibit flag = 0
- Boiler signal turns OFF when:
a. Outdoor ambient > Outdoor Ambient Set + [2°C] OR
b. Boiler prohibit flag = 1
b. Boiler prohibit flag = 1
c) Advance Parallel Mode
- Advance parallel mode allow heat pump to operate and turn ON boiler only when ambient and temperature
condition is fulfilled.
Remote control setting value:
1) Outdoor Ambient Set = (Range : -15°C ~ 15°C)
2) Selection of boiler connection direction. (Heat only, DHW only, Heat & DHW)
3) Setting data under Heat Direction
1) Outdoor Ambient Set = (Range : -15°C ~ 15°C)
2) Selection of boiler connection direction. (Heat only, DHW only, Heat & DHW)
3) Setting data under Heat Direction
a. Start Temperature
| START_TEMP |
b. Start Delay Timer
| START_TIMER |
c. Stop Temperature
| STOP_TEMP |
d. Stop Delay Timer
| STOP_TIMER |
4) Setting data under DHW Direction
a. Delay Timer
| DELAY_TIMER |
127
Control detail:
During operation ON at Heat Mode
During operation ON at Heat Mode
- Boiler signal turns ON when
a. Outdoor ambient < Outdoor Ambient Set AND
b. Buffer tank temperature < Target Buffer Tank Temperature + [START_TEMP] for [START_TIMER]
b. Buffer tank temperature < Target Buffer Tank Temperature + [START_TEMP] for [START_TIMER]
AND
c. Heat pump operate at room side AND
d. Connection of Boiler to Heating Select "YES" From installer menu AND
e. Buffer Tank connection select "YES" AND
f. Boiler prohibit flag = 0
d. Connection of Boiler to Heating Select "YES" From installer menu AND
e. Buffer Tank connection select "YES" AND
f. Boiler prohibit flag = 0
- Boiler signal turns OFF when
a. Outdoor ambient > Outdoor Ambient Set + [-2°C] OR
b. Buffer Tank temperature > Target Buffer Tank temperature + [STOP_TEMP] for [STOP_TIMER] OR
c. Heat pump not at room side. OR
d. Boiler prohibit flag = 1
b. Buffer Tank temperature > Target Buffer Tank temperature + [STOP_TEMP] for [STOP_TIMER] OR
c. Heat pump not at room side. OR
d. Boiler prohibit flag = 1
During operation ON at Tank Mode
- Boiler signal turns ON when
a. Outdoor ambient < Outdoor Ambient Set AND
b. Heat pump operate at tank side for continuous | DELAY_TIMER | AND
c. Connection of Boiler to DWH Tank select "YES" from installer menu. AND
d. Boiler prohibit flag = 0
b. Heat pump operate at tank side for continuous | DELAY_TIMER | AND
c. Connection of Boiler to DWH Tank select "YES" from installer menu. AND
d. Boiler prohibit flag = 0
- Boiler signal turns OFF when
a. Outdoor ambient > Outdoor Ambient Set + [2°C] OR
b. Heat pump not operates at tank side. OR
c. Boiler prohibit flag = 1
b. Heat pump not operates at tank side. OR
c. Boiler prohibit flag = 1
Boiler prohibit flag control
Purpose:
Purpose:
- For product safety. Boiler signal is OFF when water temperature is too high.
Start condition:
a. Water
outlet
≥ 85°C continues for 5 minutes.
b. Water
inlet
≥ 85°C continues for 5 minutes.
c. Zone1
water
temp
≥ 75°C continues for 5 minutes.
d. Zone2
water
temp
≥ 75°C continues for 5 minutes.
Contents:
After start condition fulfilled, set boiler prohibit flag = 1
Cancel condition:
- After 30 minutes from start condition fulfilled.
Contents:
Set boiler prohibit flag = 0
128
12.20 External Room Thermostat Control (Optional)
Purpose:
1 Better room temperature control to fulfill different temperature request by external room thermostat.
Recommended external room thermostat:
Maker Characteristic
Siemen (REV200)
Touch panel
Siemen (RAA20)
Analog
Connection of external room thermostat:
Wire Connection and thermo characteristic of Siemen REV200:
Wire Connection and thermo characteristic of Siemen REV200:
Setting
L/L1 (H)
Heat Thermo
L/L2 (C)
Cool Thermo
Set Temp < Actual Temp
Open Circuit OFF Short
Circuit ON
Set Temp > Actual Temp
Short Circuit
ON
Open Circuit
OFF
Cooling
Heating
Siemen REV200
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
heating and cooling line for heat + cool model.
Indoor Unit
9
L (label)
10
11
12
L1 (label)
L2 (label)
9 : Terminal Bord No.
Wire Connection and thermo characteristic of Siemen RAA20:
Setting
L/Y1
(H) Heat
Thermo L/Y2
(C) Cool
Thermo
Set Temp < Actual Temp
Open Circuit OFF Short
Circuit ON
Set Temp > Actual Temp
Short Circuit
ON
Open Circuit
OFF
Cooling
Heating
Siemen RAA20
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
heating and cooling line for heat + cool model.
Indoor Unit
9
L (label)
10
11
12
Y1 (label)
Y2 (label)
9 : Terminal Bord No.
Control Content:
External room thermostat control activate only when remote thermostat connection select YES by Indoor
control panel.
When indoor running heat mode, refer thermo On/Off from heating line feedback. And when indoor running
cool mode, refer thermo On/Off from cooling line feedback.
Heat pump Off immediately when receive thermo off feedback.
129
12.21 Three Ways Valve Control
Purpose:
- 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side.
Control contents:
1 3 ways valve switch Off:
o
During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
2 3 ways valve switch On:
o
During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
3 Stop
condition:
o
During stop mode, 3 ways valve will be in switch off position.
L
N2
Indoor Unit
N1
Spring Return 2 point
SPDT 3 wire
M
L
N1
N2
COM
Open
Close
M
L
NC
N1
N2
M
L
NO
N1
N2
AC230V
* During pump down and force mode, fix 3 ways valve in close condition.
* Recommended Parts : SFA 21/18 (Siemens)
12.22 Two Ways Valve Control
Functionality of 2 ways valve:
Use to allow hot water to floor heating panel or block cold water to floor heating panel.
Control contents:
1 When indoor running in heat mode, OPEN the 2 ways valve.
2 When indoor running in cool mode, CLOSE the 2 ways valve.
3 Stop
2 When indoor running in cool mode, CLOSE the 2 ways valve.
3 Stop
condition:
a.
During stop mode, fix 2 ways valve in close condition.
L
N2
Indoor Unit
N1
Spring Return 2 point
SPDT 3 wire
M
L
N1
N2
COM
Open
Close
M
L
NC
N1
N2
M
L
NO
N1
N2
AC230V
* During pump down mode, fix 2 ways valve in close condition.
* During force mode, open 2 ways valve.
* During force mode, open 2 ways valve.
* Recommended Parts : SFA 21/18 (Siemens)