12.17  Anti Freeze Control 
  Anti freeze protection control menu can be set YES or NO by control panel. 
  In heatpump system, there are 3 types of anti freeze control: 
1.  Expansion tank anti-freeze control 
  Expansion tank anti freeze heater ON condition: 
o  Outdoor ambient temp. < 3°C 
  Expansion tank anti freeze heater OFF condition: 
o  Outdoor ambient temp. > 4°C 
 
2.  Water pump circulation anti freeze control 
  Water pump turns ON when ALL below conditions are fulfilled: 
o  Heatpump OFF (stand by) OR error occurs. 
o  Water flowing flag is ON. 
o  Water flow switch is not abnormal. 
o  Outdoor ambient temp. < 3°C OR outdoor ambient temp. sensor is abnormal. 
o  Water inlet/outlet temp. < 6°C. 
o  After 5 minutes from previous water pump OFF. 
  Water pump turn OFF when ANY of below conditions is fulfilled: 
o  Outdoor ambient temperature ≥ 4°C. 
o  During -5°C < outdoor ambient temp. < 4°C 
  After water pump ON for 4 minutes, and water inlet temp. ≥ 8°C. 
  Else, shift to back up heater anti freeze control. 
o  During outdoor ambient temp. < -5°C 
  After water pump ON for 4 minutes, and water inlet/outlet ≥ 20°C. 
  Else, shift to back up heater anti freeze control. 
  However, if flow switch is abnormal (H62), then water pump circulation anti freeze control will not activate. 
 
3.  Back up heater anti freeze control: 
  Back up heater turn ON when ALL below conditions is fulfilled: 
o  Water inlet/outlet temp. < 6°C. 
o  Water pump circulation anti freeze control activated and water pump ON for 4 minutes. 
  Back up heater turns OFF when ANY of below conditions is fulfilled: 
o  Water inlet/outlet temp. > 28°C. 
o  Water pump circulation anti freeze control deactivated/water pump OFF. 
  However, if back up heater is abnormal (H70) then back up heater anti freeze control will not activate. 
12.17.1 Zone Anti-Freeze Control 
  If buffer tank selection is “NO” and Anti- Freeze function select “NO” from remote control, this control cannot 
activate. 
 
Start condition: 
a)  After [5] min from previous Zone pump off. AND 
b)  Outdoor air temp < [3] °C OR Outdoor sensor is abnormal. AND 
c)  Zone water temperature < [6]°C OR Zone Sensor Short or Open 
 
Cancel condition: 
a)  After water Zone pump ON [4] min AND 
b)  Outdoor air temp ≥ [4]°C OR 
c)  During -5 °C ≤ Outdoor air temp < [4] °C OR 
Zone water temperature sensor > [8] °C 
d)  During Outdoor air temp < [-5] °C 
Zone water temperature sensor > [20] °C 
*However, Zone water temperature sensor is Open or Short, Condition C and D is ignored. 
 
124 
12.18  Solar Operation (Optional) 
12.18.1 Solar Operation: 
Solar function: 
-  This function allow user to control the solar pump to operate depend on the solar sensor reading compare to 
the tank installed. Solar pump will circulate the hot water energy store at solar panel to heat up the DHW 
Tank or Buffer Tank. 
Solar Connection Diagram: 
 
 
 
a)  Solar function can only enable when the Optional PCB is connected. 
b)  Few part as below need to install to control the solar operation: 
- Solar 
Panel 
- Solar 
Pump 
-  Solar Panel Sensor 
-  Tank Sensor (Buffer tank sensor OR DHW Tank sensor depend on the connection direction) 
* During Solar Connection to the system, installer need to alert on the high water temperature may flow to the 
zone circuit or DHW piping circuit. Therefore pipe which withstand higher water temperature need to be 
installed. 
125 
Solar remote control setting 
1)  Solar Setting can only be set when the optional PCB connection is select "YES" 
2)  By remote controller, Setting as below list can be set for solar function operation (Installer Menu) 
-  Solar Function ("YES" or "NO) 
-  Tank Connection Direction ("DHW TANK" or "BUFFER TANK") 
-  Delta T turns ON: Difference temperature setting between solar panel sensor and Tank to turn on solar 
pump. (Range :5 ~ 15°C) 
-  Delta T turns OFF: Difference temperature setting between solar panel thermistor and Tank to turn off 
solar pump. (Range :2 ~ 10°C) 
-  Outdoor temp for Anti-Freeze : Outdoor temp to start Anti-Freeze control for solar circuit. (Range : -20 ~ 
10°C) 
-  Tank Temperature HI Limit Set (Range : 70 ~ 90°C)
 
 
12.18.2 Solar Operation Control 
-  Solar function can only be activate if the solar function selection “YES” from remote control. To achieve hot 
water from solar panel, indoor need to control the solar pump and circulate hot water from solar panel. 
 
Under normal case: 
Solar pump start condition: 
a)  Solar panel temperature > Delta T turn on setting temp (R/C) + Tank temperature (depend on 
selection, DHW or Buffer) AND 
b)  Tank temperature (DHW or Buffer) < Solar HI Limit Temp (R/C) AND 
c)  Operation ON with heat mode (apply to solar connect to "Buffer Tank" case) 
* Condition c) ignore if the solar system is connect to DHW tank (control active under operation OFF 
time for Tank connection case) 
Solar pump stop condition: 
a)  Solar panel temperature < Delta T turn OFF setting temp (R/C) + Tank temperature (depend on 
selection, DHW or Buffer) OR 
b)  Tank hot water temp >= Solar HI Limit Temp (R/C) + [2]°C 
Under solar Anti-freeze protection control: 
Solar pump start condition: 
a)  Outdoor temp < Outdoor temp setting for Anti-Freeze (R/C) 
Solar pump stop condition: 
a)  Outdoor temp > Outdoor temp setting for Anti-Freeze + [2]°C 
**However, During Cool mode this function cannot activate if Tank selection is “Buffer Tank". 
**Solar pump can operate even if Heat pump is under error stop. 
 
  Solar operation during error: 
-  During Tank sensor (DHW or Buffer depend on selection) abnormal, Solar operation will not able to function. 
-  During Solar Panel sensor detect OPEN (not include SHORT), Solar operation will not able to function too. 
126 
12.19  Boiler Bivalent Control 
-  Boiler is an additional or alternative heat source to heat up the room when necessary. 
-  Purpose of this control is to turn ON and turn OFF the Boiler output signal when boiler heating capacity 
needed in the system. 
-  Boiler is possible to connect to DHW Tank and Buffer Tank depends on the installer. 
-  Boiler operation parameter need to be set on Boiler itself, indoor do not control the boiler operation direction 
and operation. 
-  There are Alternative mode, Parallel mode, & Advance Parallel mode available to select by installer to fit to 
the total system. 
Bivalent control selection by remote controller 
 
Remote control setting value: 
1)  Outdoor Ambient Set = (Range: -15°C ~ 15°C) 
 
a) Alternative 
Mode 
-  Only one heat source operates at one time, either heat pump or boiler depends on condition. 
Control detail: 
During Operation ON at Heat mode or Tank mode or Heat + Tank Mode 
-  Boiler signal turn ON and heat pump and water pump turn OFF when: 
a.  Outdoor ambient < Outdoor Ambient Set AND 
b.  Boiler prohibit flag = 0 
** However indoor water pump can operate when Anti-freeze control condition fulfilled. 
 
-  Boiler signal turn OFF and heat pump and water pump turn ON when: 
a.  Outdoor ambient > Outdoor Ambient Set + [2°C] OR 
b.  Boiler prohibit flag = 1 
 
b) Parallel 
Mode 
-  Parallel mode allows heat pump and boiler ON at the same time. Boiler operates as an additional heating 
capacity when low heat pump capacity at low ambient condition. 
Control detail: 
During operation ON at Heat mode or Tank mode or Heat + Tank mode 
-  Boiler signal turns ON when: 
a.  Outdoor ambient < Outdoor Ambient Set AND 
b.  Boiler prohibit flag = 0 
-  Boiler signal turns OFF when: 
a.  Outdoor ambient > Outdoor Ambient Set + [2°C] OR 
b.  Boiler prohibit flag = 1 
 
c)  Advance Parallel Mode 
-  Advance parallel mode allow heat pump to operate and turn ON boiler only when ambient and temperature 
condition is fulfilled. 
Remote control setting value: 
1)  Outdoor Ambient Set = (Range : -15°C ~ 15°C)  
2)  Selection of boiler connection direction. (Heat only, DHW only, Heat & DHW) 
3)  Setting data under Heat Direction 
a.  Start Temperature 
| START_TEMP | 
b.  Start Delay Timer 
| START_TIMER | 
c.  Stop Temperature 
| STOP_TEMP | 
d.  Stop Delay Timer 
| STOP_TIMER | 
4)  Setting data under DHW Direction 
a.  Delay Timer 
| DELAY_TIMER | 
 