2. Specifications
2.1 WH-SDC07F3E5
WH-UD07FE5
Item
Unit
Outdoor Unit
Performance Test Condition
EN 14511
Cooling Capacity
Condition
(Ambient/Water)
A35W7
kW
6.00
BTU/h
20500
kcal/h
5160
Cooling EER
W/W
2.63
kcal/hW
2.26
Heating Capacity
Condition
(Ambient/Water)
A7W35
A2W35
kW
7.00
6.55
BTU/h
23900
22300
kcal/h
6020
5630
Heating COP
W/W
4.46
3.34
kcal/hW
3.84
2.87
Noise Level
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
dB (A)
Cooling: 48
Heating: 48
—
Power Level dB
Cooling: 66
Heating: 66
—
Air Flow
m
3
/min (ft
3
/min)
Cooling: 56.3 (1987)
Heating: 46.0 (1624)
Heating: 46.0 (1624)
Refrigeration Control Device
Expansion Valve
Refrigeration Oil
cm
3
FV50S (900)
Refrigerant (R410A)
kg (oz)
1.45 (51.2)
Dimension
Height
mm (inch)
795 (31-5/16)
Width
mm (inch)
900 (35-7/16)
Depth
mm (inch)
320 (12-19/32)
Net Weight
kg (lbs)
66 (146)
Pipe Diameter
Liquid
mm (inch)
6.35 (1/4)
Gas
mm (inch)
15.88 (5/8)
Standard Length
m (ft)
7 (23.0)
Pipe Length Range
m (ft)
3 (9.8) ~ 30 (98.4)
I/D & O/D Height Difference
m (ft)
20 (65.6)
Additional Gas Amount
g/m (oz/ft)
30 (0.3)
Refrigeration Charge Less
m (ft)
10 (32.8)
Compressor
Type
Hermetic Motor
Motor Type
Brushless (4-poles)
Rated Output
kW
1.70
Fan
Type
Propeller Fan
Material
PP
Motor Type
DC (8-poles)
Input Power
W
—
Output Power
W
60
Fan Speed
rpm
Cooling: 670
Heating: 580
Heating: 580
Heat Exchanger
Fin material
Aluminium (Pre Coat)
Fin Type
Corrugated Fin
Row × Stage × FPI
2 × 30 × 17
Size (W × H × L)
mm
38.1 × 762.0 × 873.8:903.8
6
Item
Unit
Outdoor Unit
Power Source (Phase, Voltage, Cycle)
ø
Single
V
230
Hz
50
Input Power
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
kW
Cooling: 2.28
Heating: 1.57
Heating: 1.96
Maximum Input Power For Heatpump System
kW
4.59
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
1Ø / 21.0 / 4.59k
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
1Ø / 13.0 / 3.00k
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
— / — / —
Starting Current
A
7.2
Running Current
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
A
Cooling: 10.3
Heating: 7.2
Heating: 9.0
Maximum Current For Heatpump System
A
21.0
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
Power factor means total figure of compressor and
outdoor fan motor.
%
Cooling: 96
Heating: 95
Heating: 95
Power Cord
Number of core
—
Length
m (ft)
—
Thermostat
Electronic Control
Protection Device
Electronic Control
Item
Unit
Indoor Unit
Performance Test Condition
EN 14511
Operation Range
Outdoor Ambient
°C
Cooling: 16 ~ 43
Heating: -20 ~ 35
Water Outlet
°C
Cooling: 5 ~ 20
Heating: 25 ~ 55
Internal Pressure Differential
kPa
Cooling: 26.5
Heating: 35.4
Heating: 35.4
Noise Level
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
dB (A)
Cooling: 33
Cooling: 33
—
Power Level dB
Cooling: 46
Cooling: 46
—
Dimension
Height
mm (inch)
892 (35-1/8)
Width
mm (inch)
502 (19-3/4)
Depth
mm (inch)
353 (13-29/32)
Net Weight
kg (lbs)
43 (95)
Refrigerant Pipe Diameter
Liquid
mm (inch)
6.35 (1/4)
Gas
mm (inch)
15.88 (5/8)
Water Pipe Diameter
Inlet
mm (inch)
28 (1-3/32)
Outlet
mm (inch)
28 (1-3/32)
Water Drain Hose Inner Diameter
mm (inch)
15 (19/32)
Pump
Motor Type
DC Motor
No. of Speed
7 (Software Selection)
Input Power
W
63
Hot Water Coil
Type
Brazed Plate
No. of Plates
48
Size (H × W × L)
mm
82 × 93 × 325
Water Flow Rate
l/min (m
3
/h)
Cooling: 17.6 (1.1)
Heating: 20.1 (1.2)
Heating: 20.1 (1.2)
Pressure Relief Valve Water Circuit
kPa
Open: 300, Close: 265 and below
Flow Switch
Magnetic Lead Switch
Protection Device
A
Residual Current Circuit Breaker (30)
7
Item
Unit
Indoor Unit
Expansion Vessel
Volume
I
10
MWP
bar
3
Capacity of Integrated Electric Heater
kW
3.00
Note:
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled indoor water inlet
temperature of 12°C and water outlet temperature of 7°C.
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb
(42.8°F Wet Bulb) with controlled indoor water inlet temperature of 30°C and water outlet temperature of 35°C.
Specification are subjected to change without prior notice for further improvement.
Flow rate indicated are based on nominal capacity adjustment of leaving water temperature (LWT) 35°C and
Flow rate indicated are based on nominal capacity adjustment of leaving water temperature (LWT) 35°C and
∆
T
= 5°C.
8
2.2 WH-SDC09F3E5
WH-UD09FE5
Item
Unit
Outdoor Unit
Performance Test Condition
EN 14511
Cooling Capacity
Condition
(Ambient/Water)
A35W7
kW
7.00
BTU/h
23900
kcal/h
6020
Cooling EER
W/W
2.43
kcal/hW
2.09
Heating Capacity
Condition
(Ambient/Water)
A7W35
A2W35
kW
9.00
6.70
BTU/h
30700
22800
kcal/h
7740
5760
Heating COP
W/W
4.13
3.13
kcal/hW
3.55
2.69
Noise Level
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
dB (A)
Cooling: 50
Heating: 49
—
Power Level dB
Cooling: 68
Heating: 67
—
Air Flow
m
3
/min (ft
3
/min)
Cooling: 56.3 (1987)
Heating: 51.0 (1800)
Heating: 51.0 (1800)
Refrigeration Control Device
Expansion Valve
Refrigeration Oil
cm
3
FV50S (900)
Refrigerant (R410A)
kg (oz)
1.45 (51.2)
Dimension
Height
mm (inch)
795 (31-5/16)
Width
mm (inch)
900 (35-7/16)
Depth
mm (inch)
320 (12-19/32)
Net Weight
kg (lbs)
66 (146)
Pipe Diameter
Liquid
mm (inch)
6.35 (1/4)
Gas
mm (inch)
15.88 (5/8)
Standard Length
m (ft)
7 (23.0)
Pipe Length Range
m (ft)
3 (9.8) ~ 30 (98.4)
I/D & O/D Height Difference
m (ft)
20 (65.6)
Additional Gas Amount
g/m (oz/ft)
30 (0.3)
Refrigeration Charge Less
m (ft)
10 (32.8)
Compressor
Type
Hermetic Motor
Motor Type
Brushless (4-poles)
Rated Output
kW
1.70
Fan
Type
Propeller Fan
Material
PP
Motor Type
DC (8-poles)
Input Power
W
—
Output Power
W
60
Fan Speed
rpm
Cooling: 700
Heating: 640
Heating: 640
Heat Exchanger
Fin material
Aluminium (Pre Coat)
Fin Type
Corrugated Fin
Row × Stage × FPI
2 × 30 × 17
Size (W × H × L)
mm
38.1 × 762.0 × 873.8:903.8