DOWNLOAD Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ↓ Size: 7.25 MB | Pages: 127 in PDF or view online for FREE

Model
U-4LE1E5 U-4LE1E8 U-5LE1E5 U-5LE1E8 U-6LE1E5 U-6LE1E8
Pages
127
Size
7.25 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / MINI VRF SYSTEM
File
u-4le1e5-u-4le1e8-u-5le1e5-u-5le1e8-u-6le1e5-u-6le.pdf
Date

Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ▷ View online

Mini VRF SYSTEM
Address Settings
1
Contents
1-1
1. Test Run ............................................................................................................................... 1-2
2.  Settings of Outdoor Unit Control PCB .............................................................................. 1-3
3.  Auto Address Setting .......................................................................................................... 1-5
3-1. Auto Address Setting ...................................................................................................... 1-5
3-2. Automatic Address Setting from the Remote Controller ............................................... 1-10
3-3. Display during automatic address setting ..................................................................... 1-11
3-4. Request concerning recording the indoor/outdoor unit combination Nos. .................... 1-12
3-5. Checking the indoor unit addresses ............................................................................. 1-12
1. Address Settings
(Outdoor Units)
SM830196-03_Mini_VRF SYS.indb   1
SM830196-03_Mini_VRF SYS.indb   1
2014/09/08   10:46:23
2014/09/08   10:46:23
Mini VRF SYSTEM
Address Settings
1
1. Test Run
1-2
Test Run Procedure
Items to Check Before the Test Run
1.
2.
Turn the remote power switch on at least 5 hours before the test, in order to energize the crankcase heater.
Turn the outdoor service valves (2 locations) to the full-open positions.
Use caution when making the settings. 
If there are duplicated system addresses, or if the settings for the Nos. of the indoor units are not consistent, an alarm will occur 
and the system will not start. 
These settings are not made on the indoor unit PCB.
Recheck the items to check before the test run.
Set the No. of indoor units.
Are the inter-unit control wires 
connected to more than 1 refrigerant 
system?
Set the system address.
When multiple outdoor units exist, disconnect the terminals extended 
from the shorted plugs (CN-TERMINAL) at all outdoor main unit PCBs 
except for 1. Alternatively, move the sockets to the OPEN side. 
<Outdoor unit control PCB> 
No. of  I/U setting switch
(S004)
(Check the link wiring.)
<Outdoor unit control PCB> 
R. C. ADD setting switch
(S002 and S003)
NO
YES
YES
NO
NO
YES
CASE 1
CASE 2
Refer to 
page 1-3.
Is it possible to turn ON the 
power only for the 1 refrigerant system where the 
test run will be performed?
Will automatic address setting be 
performed in Heating mode?
CASE 3B
CASE 3A
Turn ON the indoor and 
outdoor unit power for that 
refrigerant system only.
Short-circuit the automatic address pin 
(CN-A.ADD) on the outdoor unit PCB 
for 1 second or longer, then release it.
LED 1 and 2 blink alternately 
(about 2 or 3 minutes).
Are LEDs 1 and 2 on the 
outdoor unit PCB OFF?
Refer to “Table of 
Self-Diagnostic Functions and 
Description of Alarm Displays.”
YES
NO
Turn OFF the indoor and 
outdoor unit power.
Make necessary 
corrections.
Check the alarm contents.
Make necessary 
corrections
Turn OFF the 
indoor and 
outdoor unit 
Check the alarm
contents.
Is it OK to start the compressors?
Turn ON the indoor and 
outdoor unit power.
Short-circuit the cooling side of the 
mode change 3P pin (CN-MODE) 
on the outdoor main unit PCB. 
At the same time, short-circuit the 
automatic address pin (CN-A.ADD) 
for 1 second or longer, then pull it 
out. 
Start indoor and outdoor unit 
cooling operation. 
LED 1 and 2 blink alternately.
Start indoor and outdoor unit 
heating operation. 
LED 1 and 2 blink alternately.
Short-circuit the automatic 
address pin (CN-A.ADD) on the 
outdoor unit PCB for 1 second 
or longer, then release it.
Turn ON the indoor and 
outdoor unit power.
Is it OK to start the 
compressors?
*2
*2
3
*
3
*
Are LEDs 1 and 2 on the 
outdoor unit PCB OFF?
YES
NO
Check that test run preparation is OK. 
(Do not allow the short-circuited pins to remain short-circuited.)
NO
YES
Set the wired remote controller for test run.
Refer to the remote 
controller test-run 
settings.
Return remote control to normal mode
Check and make corrections according to “Table of Self-Diagnostic Functions.”
Does system operate?
End test run.
*1  Use a flathead screwdriver to short-circuit the pin on the PC board.
*2  A minimum of 5 hours must have passed after the power was turned ON 
to the outdoor unit.
Refer to Section 2 “1. Remote Controller Test Run Settings”.
Refer to Section 5. Self-Diagnostics Function Table.
*3  All indoor units operate in all refrigerant systems where the power is ON.
*1
*1
*1
*5
*5
*4
*4
*4
SM830196-03_Mini_VRF SYS.indb   2
SM830196-03_Mini_VRF SYS.indb   2
2014/09/08   10:46:52
2014/09/08   10:46:52
Mini VRF SYSTEM
Address Settings
1
2. Settings of Outdoor Unit Control PCB
1-3
For single-phase outdoor unit PCB
For 3-phase outdoor unit PCB
D303 (LED2)
D302 (LED1)
TERMINAL
TERMINAL
D303 (LED2)
D302 (LED1)
A.ADD
MODE
A.ADD
MODE
S003
JP001
S002
S004
CN-OPT1
CN-OPT2
EMG plug (CN-EMG)
SILENT 
(CN-SILENT)
TEST
AP
RUN
STOP
LED for EEPROM 
memory IC (D330)
POWER LED 
(D514)
High-pressure 
sensor (CN-HPS)
Outdoor air 
temp (CN-TO)
Comp discharge
temp (CN-TD)
RC plug 
(CN-RC)
Liquid temp
(CN-C1)
Suction temp (CN-TS)
High-pressure switch 
plug (CN-63PH)
OC plug (CN-OC)
MOV plug (CN-MOV1)
EEPROM memory 
IC (IC18)
CHK
S003
JP001
CN-PRY2
CN-PRY1
S002
S004
TEST
AP
RUN
STOP
CHK
CN-OPT1
CN-OPT2
EMG plug 
(CN-EMG)
SILENT 
(CN-SILENT)
LED for EEPROM 
memory IC (D330)
POWER LED (D514)
High-pressure 
sensor (CN-HPS)
Outdoor air 
temp (CN-TO)
Comp discharge
temp (CN-TD)
RC plug (CN-RC)
Liquid temp (CN-C1)
Suction temp (CN-TS)
High-pressure switch 
plug (CN-63PH)
OC plug (CN-OC)
MOV plug (CN-MOV1)
EEPROM memory IC 
(IC18)
SM830196-03_Mini_VRF SYS.indb   3
SM830196-03_Mini_VRF SYS.indb   3
2014/09/08   10:46:52
2014/09/08   10:46:52
Mini VRF SYSTEM
Address Settings
1
2. Settings of Outdoor Unit Control PCB
1-4
<General Explanation of the Switches on the Outdoor Unit Control PCB>
MODE (3P) 
Changes the operating mode (heating/cooling). (Can be used only at the main unit.)
During normal operation: Short-circuiting these pins once will change all indoor units in that 
system to either cooling mode or heating mode.
During automatic address setting: When the pins are not connected, the mode is heating mode.
A. ADD (2P) 
Short-circuited for 1 second or longer  → Automatic address setting begins when the pins are  
released. Short-circuiting these pins for 1 second or longer while automatic address setting is in 
progress interrupts automatic address setting.
CHK (2P) 
When these pins are short-circuited, the mode is test run mode. (Test run mode is automatically 
canceled after 1 hour.) When the pins are released, test run mode is canceled.
RC (3P, blue) 
(CN-RC)
The outdoor unit maintenance remote controller can be connected here to check the alarm 
details.
RUN (2P) 
Short-circuit these pins and apply a pulse signal to start all indoor units in that system.
STOP (2P) 
Short-circuit these pins and apply a pulse signal to stop all indoor units in that system.
(If the pins are left short-circuited, it will not be possible to start operation from the indoor unit 
remote controllers.)
AP (2P) 
Socket for silent 
mode 
2P plug (White) 
(CN-SILENT)
These pins are used when applying vacuum to the outdoor unit.
Examples of the No. of indoor units settings
No. of indoor units
Indoor unit setting (S004)
(Rotary switch, gray)
1 unit (factory setting)
 set to 1
2 units
 set to 2
9 units
 set to 9
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used)
System address
No.
System address 
(S003)
(2P DIP switch, black)
System address 
(S002)
(Rotary switch, yellow)
System 1 (factory setting)
Both OFF
ON
1
2
ON
OFF
 set to 1
System 11
1 ON
ON
1
2
ON
OFF
 set to 1
System 21
2 ON
ON
1
2
ON
OFF
 set to 1
System 30
1 & 2 ON
ON
1
2
ON
OFF
 set to 0
Used for installing the external timer for the silent mode.
(Refer to Section 1-14. Servicing and Maintenance Functions in Service Manual.)
SM830196-03_Mini_VRF SYS.indb   4
SM830196-03_Mini_VRF SYS.indb   4
2014/09/08   10:46:54
2014/09/08   10:46:54
Page of 127
Display

Click on the first or last page to see other U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 service manuals if exist.