Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ▷ View online
Mini VRF SYSTEM
Address Settings
1
Contents
1-1
1. Test Run ............................................................................................................................... 1-2
2. Settings of Outdoor Unit Control PCB .............................................................................. 1-3
3. Auto Address Setting .......................................................................................................... 1-5
3-1. Auto Address Setting ...................................................................................................... 1-5
3-2. Automatic Address Setting from the Remote Controller ............................................... 1-10
3-3. Display during automatic address setting ..................................................................... 1-11
3-4. Request concerning recording the indoor/outdoor unit combination Nos. .................... 1-12
3-5. Checking the indoor unit addresses ............................................................................. 1-12
1. Address Settings
(Outdoor Units)
SM830196-03_Mini_VRF SYS.indb 1
SM830196-03_Mini_VRF SYS.indb 1
2014/09/08 10:46:23
2014/09/08 10:46:23
Mini VRF SYSTEM
Address Settings
1
1. Test Run
1-2
Test Run Procedure
Items to Check Before the Test Run
1.
2.
2.
Turn the remote power switch on at least 5 hours before the test, in order to energize the crankcase heater.
Turn the outdoor service valves (2 locations) to the full-open positions.
Turn the outdoor service valves (2 locations) to the full-open positions.
Use caution when making the settings.
If there are duplicated system addresses, or if the settings for the Nos. of the indoor units are not consistent, an alarm will occur
and the system will not start.
These settings are not made on the indoor unit PCB.
If there are duplicated system addresses, or if the settings for the Nos. of the indoor units are not consistent, an alarm will occur
and the system will not start.
These settings are not made on the indoor unit PCB.
Recheck the items to check before the test run.
Set the No. of indoor units.
Are the inter-unit control wires
connected to more than 1 refrigerant
system?
Set the system address.
When multiple outdoor units exist, disconnect the terminals extended
from the shorted plugs (CN-TERMINAL) at all outdoor main unit PCBs
except for 1. Alternatively, move the sockets to the OPEN side.
from the shorted plugs (CN-TERMINAL) at all outdoor main unit PCBs
except for 1. Alternatively, move the sockets to the OPEN side.
<Outdoor unit control PCB>
No. of I/U setting switch
(S004)
(Check the link wiring.)
<Outdoor unit control PCB>
R. C. ADD setting switch
(S002 and S003)
NO
YES
YES
NO
NO
YES
CASE 1
CASE 2
Refer to
page 1-3.
page 1-3.
Is it possible to turn ON the
power only for the 1 refrigerant system where the
test run will be performed?
Will automatic address setting be
performed in Heating mode?
CASE 3B
CASE 3A
Turn ON the indoor and
outdoor unit power for that
refrigerant system only.
Short-circuit the automatic address pin
(CN-A.ADD) on the outdoor unit PCB
for 1 second or longer, then release it.
(CN-A.ADD) on the outdoor unit PCB
for 1 second or longer, then release it.
LED 1 and 2 blink alternately
(about 2 or 3 minutes).
(about 2 or 3 minutes).
Are LEDs 1 and 2 on the
outdoor unit PCB OFF?
Refer to “Table of
Self-Diagnostic Functions and
Description of Alarm Displays.”
Self-Diagnostic Functions and
Description of Alarm Displays.”
YES
NO
Turn OFF the indoor and
outdoor unit power.
Make necessary
corrections.
Check the alarm contents.
Make necessary
corrections
corrections
Turn OFF the
indoor and
outdoor unit
indoor and
outdoor unit
Check the alarm
contents.
Is it OK to start the compressors?
Turn ON the indoor and
outdoor unit power.
Short-circuit the cooling side of the
mode change 3P pin (CN-MODE)
on the outdoor main unit PCB.
At the same time, short-circuit the
automatic address pin (CN-A.ADD)
for 1 second or longer, then pull it
out.
mode change 3P pin (CN-MODE)
on the outdoor main unit PCB.
At the same time, short-circuit the
automatic address pin (CN-A.ADD)
for 1 second or longer, then pull it
out.
Start indoor and outdoor unit
cooling operation.
LED 1 and 2 blink alternately.
cooling operation.
LED 1 and 2 blink alternately.
Start indoor and outdoor unit
heating operation.
LED 1 and 2 blink alternately.
heating operation.
LED 1 and 2 blink alternately.
Short-circuit the automatic
address pin (CN-A.ADD) on the
outdoor unit PCB for 1 second
or longer, then release it.
address pin (CN-A.ADD) on the
outdoor unit PCB for 1 second
or longer, then release it.
Turn ON the indoor and
outdoor unit power.
Is it OK to start the
compressors?
*2
*2
3
*
3
*
Are LEDs 1 and 2 on the
outdoor unit PCB OFF?
YES
NO
Check that test run preparation is OK.
(Do not allow the short-circuited pins to remain short-circuited.)
(Do not allow the short-circuited pins to remain short-circuited.)
NO
YES
Set the wired remote controller for test run.
Refer to the remote
controller test-run
settings.
controller test-run
settings.
Return remote control to normal mode
Check and make corrections according to “Table of Self-Diagnostic Functions.”
Does system operate?
End test run.
*1 Use a flathead screwdriver to short-circuit the pin on the PC board.
*2 A minimum of 5 hours must have passed after the power was turned ON
to the outdoor unit.
Refer to Section 2 “1. Remote Controller Test Run Settings”.
Refer to Section 5. Self-Diagnostics Function Table.
*3 All indoor units operate in all refrigerant systems where the power is ON.
*1
*1
*1
*5
*5
*4
*4
*4
SM830196-03_Mini_VRF SYS.indb 2
SM830196-03_Mini_VRF SYS.indb 2
2014/09/08 10:46:52
2014/09/08 10:46:52
Mini VRF SYSTEM
Address Settings
1
2. Settings of Outdoor Unit Control PCB
1-3
For single-phase outdoor unit PCB
For 3-phase outdoor unit PCB
D303 (LED2)
D302 (LED1)
TERMINAL
TERMINAL
D303 (LED2)
D302 (LED1)
A.ADD
MODE
A.ADD
MODE
S003
JP001
S002
S004
CN-OPT1
CN-OPT2
EMG plug (CN-EMG)
SILENT
(CN-SILENT)
(CN-SILENT)
TEST
AP
RUN
STOP
LED for EEPROM
memory IC (D330)
POWER LED
(D514)
High-pressure
sensor (CN-HPS)
Outdoor air
temp (CN-TO)
Comp discharge
temp (CN-TD)
RC plug
(CN-RC)
(CN-RC)
Liquid temp
(CN-C1)
Suction temp (CN-TS)
High-pressure switch
plug (CN-63PH)
plug (CN-63PH)
OC plug (CN-OC)
MOV plug (CN-MOV1)
EEPROM memory
IC (IC18)
CHK
S003
JP001
CN-PRY2
CN-PRY1
S002
S004
TEST
AP
RUN
STOP
CHK
CN-OPT1
CN-OPT2
EMG plug
(CN-EMG)
(CN-EMG)
SILENT
(CN-SILENT)
(CN-SILENT)
LED for EEPROM
memory IC (D330)
memory IC (D330)
POWER LED (D514)
High-pressure
sensor (CN-HPS)
Outdoor air
temp (CN-TO)
Comp discharge
temp (CN-TD)
RC plug (CN-RC)
Liquid temp (CN-C1)
Suction temp (CN-TS)
High-pressure switch
plug (CN-63PH)
plug (CN-63PH)
OC plug (CN-OC)
MOV plug (CN-MOV1)
EEPROM memory IC
(IC18)
(IC18)
SM830196-03_Mini_VRF SYS.indb 3
SM830196-03_Mini_VRF SYS.indb 3
2014/09/08 10:46:52
2014/09/08 10:46:52
Mini VRF SYSTEM
Address Settings
1
2. Settings of Outdoor Unit Control PCB
1-4
<General Explanation of the Switches on the Outdoor Unit Control PCB>
MODE (3P)
Changes the operating mode (heating/cooling). (Can be used only at the main unit.)
During normal operation: Short-circuiting these pins once will change all indoor units in that
system to either cooling mode or heating mode.
During automatic address setting: When the pins are not connected, the mode is heating mode.
During normal operation: Short-circuiting these pins once will change all indoor units in that
system to either cooling mode or heating mode.
During automatic address setting: When the pins are not connected, the mode is heating mode.
A. ADD (2P)
Short-circuited for 1 second or longer → Automatic address setting begins when the pins are
released. Short-circuiting these pins for 1 second or longer while automatic address setting is in
progress interrupts automatic address setting.
released. Short-circuiting these pins for 1 second or longer while automatic address setting is in
progress interrupts automatic address setting.
CHK (2P)
When these pins are short-circuited, the mode is test run mode. (Test run mode is automatically
canceled after 1 hour.) When the pins are released, test run mode is canceled.
canceled after 1 hour.) When the pins are released, test run mode is canceled.
RC (3P, blue)
(CN-RC)
(CN-RC)
The outdoor unit maintenance remote controller can be connected here to check the alarm
details.
details.
RUN (2P)
Short-circuit these pins and apply a pulse signal to start all indoor units in that system.
STOP (2P)
Short-circuit these pins and apply a pulse signal to stop all indoor units in that system.
(If the pins are left short-circuited, it will not be possible to start operation from the indoor unit
remote controllers.)
(If the pins are left short-circuited, it will not be possible to start operation from the indoor unit
remote controllers.)
AP (2P)
Socket for silent
mode
2P plug (White)
(CN-SILENT)
mode
2P plug (White)
(CN-SILENT)
These pins are used when applying vacuum to the outdoor unit.
Examples of the No. of indoor units settings
No. of indoor units
Indoor unit setting (S004)
(Rotary switch, gray)
1 unit (factory setting)
set to 1
2 units
set to 2
9 units
set to 9
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used)
System address
No.
System address
(S003)
(2P DIP switch, black)
System address
(S002)
(Rotary switch, yellow)
System 1 (factory setting)
Both OFF
ON
1
2
ON
OFF
set to 1
System 11
1 ON
ON
1
2
ON
OFF
set to 1
System 21
2 ON
ON
1
2
ON
OFF
set to 1
System 30
1 & 2 ON
ON
1
2
ON
OFF
set to 0
Used for installing the external timer for the silent mode.
(Refer to Section 1-14. Servicing and Maintenance Functions in Service Manual.)
(Refer to Section 1-14. Servicing and Maintenance Functions in Service Manual.)
SM830196-03_Mini_VRF SYS.indb 4
SM830196-03_Mini_VRF SYS.indb 4
2014/09/08 10:46:54
2014/09/08 10:46:54