Panasonic S-F18DB4E5 / U-B18DBE5 / S-F24DB4E5 / U-B24DBE5 / S-F28DB4E5 / U-B28DBE5 / S-F28DB4E5 / U-B28DBE8 / S-F34DB4E5 / U-B34DBE5 / S-F34DB4E5 / U-B34DBE8 / S-F43DB4E5 / U-B43DBE8 / S-F50DB4E5 / U-B50DBE8 Service Manual ▷ View online

9
2.5.
Group Control Equipment
Wired
Remote
Control
Group control by one remote control
• All air conditioner units are controlled 
as a whole by remote control.
• All indoor units operate in the same 
mode.
[Remote side]
• Optional wired remote 
control CZ-RD513C
[Local side]
Not needed
Twin remote control separate control
• Each indoor unit can be operated by 
either one of the two remote control.
• Apart from timer setting time, displays 
for two remote control are identical.
• Last button pressed has priority (main 
or slave is set at remote control unit).
[Remote side]
• Optional wired remote 
control
[Local side]
• Optional wired remote 
control CZ-RD513C
Common
Control
Common control / group
• Operation is possible using either 
wired or wireless remote control unit.
• Last button pressed has priority.
• Optional wired remote 
control and wireless 
remote control
Wired CZ-RD513C
Wireless CZ-RL513B
10
3 Product Specification
3.1.
S-F18DB4E5  U-B18DBE5
1. Cooling capacities are based on indoor temperature of 27
qC D.B. (80.6qF D.B.), 19.0qC W.B. (66.2qF W.B.) and outdoor air
temperature of 35
qC D.B. (95qF D.B.), 24qC W.B. (75.2qF W.B.)
2. Heating capacities are based on indoor temperature of 20
qC D.B. (68qF D.B.) and outdoor air temperature of 7qC D.B. (44.6qF
D.B.), 6
qC W.B. (42.8qF W.B.)
ELECTRICAL DATA (50 Hz)
 
Indoor Unit
Outdoor Unit
Main Body
S-F18DB4E5
U-B18DBE5
ITEM / MODEL
Panel
CZ-BT03P
Remote
Control
CZ-RD513C (Wired)
CZ-RL513B (Wireless)
Cooling Capacity
kW
5.0
BTU/h
17,100
Heating Capacity
kW
5.60
BTU/h
19,100
Refrigerant Charge-less
m
20
Standard Air Volume for High, 
m
3
/min
20
57
cfm
706
2013
Outside Dimension (H x W x D)
mm
246 
u 840 u 840
795 
u 900 u 320
inch
9-11/16 
u 33-1/24 u 33-1/24
31-5/16 
u 35-7/16 u 12-19/32
Net Weight
kg (lbs)
26 (57)
57 (126)
Piping
Connection
Refrigerant
Gas
mm (inch)
O.D Ø 12.70 (1/2) Flared Type
Liquid
mm (inch)
O.D Ø 6.35 (1/4) Flared Type
Drain
O.D Ø 20
I.D Ø 20
Compressor
Type, Number of Set
 
-
Hermatic, 1
Starting Method
 
-
Permanent Split Capacitor
Motor
Type
 
-
2-pole 1 phase brushless motor
Rated Output
kW
-
1.50
Fan
Type, Number of Set
 
Turbo fan-1
Mix flow fan,1
Motor
Type
 
8-pole DC motor
6-pole single phase induction motor
Rated Output
kW
0.04
0.07
Air-heat Exchanger (Row x Stage x FPI)
 
Louver-fin type (2 
u 10 u 20)
Corrugate-fin type (2 
u 36 u 19)
Refrigerant Control
 
-
Expansion Valve
Refrigerant Oil (Charged)
cm
3
-
FV50S (1130)
Refrigerant (Charged) R410a
kg (oz)
-
1.35 (47.6)
Running
Adjustment
Control Switch
 
Wireless or Wired Remote Control
-
Room Temperature
 
Thermostat
-
Noise Level
 dB (A)
Cooling:       35/32
49/-
Heating:      34/31
50/-
Power Level 
dB
Cooling:       50/47
65/-
Heating:      49/46
66/-
Moisture Removal
 L/h (Pt/h)
2.80 (5.9)
EER
 W/W
2.96/2.91//2.86
COP
 W/W
3.52/3.46/3.39
 ITEM / MODEL
Condition by ISO5151
Volts
V
220
230
240
Phase
 Single
Single
Single
Power Consumption
kW
Cooling
1.69
1.72
1.75
Heating
1.59
1.62
1.65
Running Current
A
Cooling
7.76
7.70
7.65
Heating
7.3
7.2
7.1
Starting Current
A
26
27
28
Power Factor
%
Cooling
99
97
95
Heating
99
98
97
*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Panasonic
Power source
AC, 1~220V, 230V, 240V 50Hz
11
3.2.
S-F24DB4E5  U-B24DBE5
1. Cooling capacities are based on indoor temperature of 27
qC D.B. (80.6qF D.B.), 19.0qC W.B. (66.2qF W.B.) and outdoor air
temperature of 35
qC D.B. (95qF D.B.), 24qC W.B. (75.2qF W.B.)
2. Heating capacities are based on indoor temperature of 20
qC D.B. (68qF D.B.) and outdoor air temperature of 7qC D.B. (44.6qF
D.B.), 6
qC W.B. (42.8qF W.B.)
ELECTRICAL DATA (50 Hz)
 
Indoor Unit
Outdoor Unit
Main Body
S-F24DB4E5
U-B24DBE5
ITEM / MODEL
Panel
CZ-BT03P
Remote
Control
CZ-RD513C (Wired)
CZ-RL513B (Wireless)
Cooling Capacity
kW
6.6
BTU/h
22,500
Heating Capacity
kW
7.1
BTU/h
24,200
Refrigerant Charge-less
m
30
Standard Air Volume for High, 
m
3
/min
18
60
cfm
636
2120
Outside Dimension (H x W x D)
mm
246 
u 840 u 840
795 
u 900 u 320
inch
9-11/16 
u 33-1/24 u 33-1/24
31-5/16 
u 35-7/16 u 12-19/32
Net Weight
kg (lbs)
26 (58)
69 (152)
Piping
Connection
Refrigerant
Gas
mm (inch)
O.D Ø 15.88 (5/8) Flared Type
Liquid
mm (inch)
O.D Ø 9.52 (3/8) Flared Type
Drain
mm
O.D Ø 20
I.D Ø 20
Compressor
Type, Number of Set
 
-
Hermatic, 1
Starting Method
 
-
Permanent Split Capacitor
Motor
Type
 
-
2-pole 1 phase brushless motor
Rated Output
kW
-
1.8
Fan
Type, Number of Set
 
Turbo fan-1
Mix flow fan,1
Motor
Type
 
8-pole DC motor
6-pole single phase induction motor
Rated Output
kW
0.04
0.07
Air-heat Exchanger (Row x Stage x FPI)
 
Louver-fin type (2 
u 10 u 20)
Corrugate-fin type (2 
u 36 u 19)
Refrigerant Control
 
-
Expansion Valve
Refrigerant Oil (Charged)
cm
3
-
FV50S (1130)
Refrigerant (Charged) R410a
kg (oz)
-
1.70 (60)
Running
Adjustment
Control Switch
 
Wireless or Wired Remote Control
-
Room Temperature
 
Thermostat
-
Noise Level
 dB (A)
Cooling:       36/32
50/-
Heating:      36/32
51/-
Power Level 
dB
Cooling:       51/47
66/-
Heating:      51/47
67/-
Moisture Removal
 L/h (Pt/h)
3.8 (8.0)
EER
 W/W
2.68/2.63/2.57
COP
 W/W
3.07/3.01/2.95
 ITEM / MODEL
Condition by ISO5151
Volts
V
220
230
240
Phase
 Single
Single
Single
Power Consumption
kW
Cooling
2.46
2.51
2.57
Heating
2.31
2.36
2.41
Running Current
A
Cooling
12.3
12.4
12.6
Heating
10.9
11.2
11.7
Starting Current
A
59
62
65
Power Factor
%
Cooling
91
88
85
Heating
96
92
86
*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Panasonic
Power source
AC, 1~220V, 230V, 240V 50Hz
12
3.3.
S-F28DB4E5  U-B28DBE5
1. Cooling capacities are based on indoor temperature of 27
qC D.B. (80.6qF D.B.), 19.0qC W.B. (66.2qF W.B.) and outdoor air
temperature of 35
qC D.B. (95qF D.B.), 24qC W.B. (75.2qF W.B.)
2. Heating capacities are based on indoor temperature of 20
qC D.B. (68qF D.B.) and outdoor air temperature of 7qC D.B. (44.6qF
D.B.), 6
qC W.B. (42.8qF W.B.)
ELECTRICAL DATA (50 Hz)
 
Indoor Unit
Outdoor Unit
Main Body
S-F28DB4E5
U-B28DBE5
ITEM / MODEL
Panel
CZ-BT03P
Remote
Control
CZ-RD513C (Wired)
CZ-RL513B (Wireless)
Cooling Capacity
kW
7.3
BTU/h
24,900
Heating Capacity
kW
8.00
BTU/h
27,300
Refrigerant Charge-less
m
30
Standard Air Volume for High, 
m
3
/min
20
63
cfm
706
2226
Outside Dimension (H x W x D)
mm
246 
u 840 u 840
795 
u 900 u 320
inch
9-11/16 
u 33-1/24 u 33-1/24
31-5/16 
u 35-7/16 u 12-19/32
Net Weight
kg (lbs)
26 (58)
69 (152)
Piping
Connection
Refrigerant
Gas
mm (inch)
O.D Ø 15.88 (5/8) Flared Type
Liquid
mm (inch)
O.D Ø 9.52 (3/8) Flared Type
Drain
O.D Ø 20
I.D Ø 20
Compressor
Type, Number of Set
 
-
Hermatic, 1
Starting Method
 
-
Permanent Split Capacitor
Motor
Type
 
-
2-pole 1 phase brushless motor
Rated Output
kW
-
2.20
Fan
Type, Number of Set
 
Turbo fan-1
Mix flow fan,1
Motor
Type
 
8-pole DC motor
6-pole single phase induction motor
Rated Output
kW
0.04
0.07
Air-heat Exchanger (Row x Stage x FPI)
 
Louver-fin type (2 
u 10 u 20)
Corrugate-fin type (2 
u 36 u 19)
Refrigerant Control
 
-
Expansion Valve
Refrigerant Oil (Charged)
cm
3
-
FV50S (1130)
Refrigerant (Charged) R410a
kg (oz)
-
2.05 (72)
Running
Adjustment
Control Switch
 
Wireless or Wired Remote Control
-
Room Temperature
 
Thermostat
-
Noise Level
 dB (A)
Cooling:       38/33
52/-
Heating:      38/33
53/-
Power Level 
dB
Cooling:       53/48
67/-
Heating:      53/48
68/-
Moisture Removal
 L/h (Pt/h)
4.3 (9.0)
EER
 W/W
2.66/2.61//2.56
COP
 W/W
3.14/3.08/3.02
 ITEM / MODEL
Condition by ISO5151
Volts
V
220
230
240
Phase
 Single
Single
Single
Power Consumption
kW
Cooling
2.74
2.8
2.85
Heating
2.55
2.6
2.65
Running Current
A
Cooling
12.7
12.8
12.9
Heating
11.7
11.8
11.9
Starting Current
A
62
65
68
Power  Factor
%
Cooling
98
95
92
Heating
99
96
93
*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Panasonic
Power source
AC, 1~220V, 230V, 240V 50Hz
Page of 127
Display