DOWNLOAD Panasonic CW-C180BG / CW-C241SG / CW-A180BG Service Manual ↓ Size: 553.6 KB | Pages: 18 in PDF or view online for FREE

Model
CW-C180BG CW-C241SG CW-A180BG
Pages
18
Size
553.6 KB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / WINDOW TYPE
File
cw-c180bg-cw-c241sg-cw-a180bg.pdf
Date

Panasonic CW-C180BG / CW-C241SG / CW-A180BG Service Manual ▷ View online

CW-C180BG
– 8 –
1
. Power Supply
Set the Main Control Knob to the OFF position;
confirm that the power supply cord is connected
to a proper AC outlet.
Recommended
Use the air conditioner under
the following conditions:
• Operating temperature range.
(unit in 
°
C)
Indoor unit
Outdoor unit
D.B.T. W.B.T. D.B.T. W.B.T.
Maximum
Temperature
Minimum
Temperature
D.B.T.: Dry Bulb Temperature
W.B.T.: Wet Bulb Temperature
• Humidity does not exceed 90%.
Continuous operation at over 90% humidity
may create condensation and waterdrops on
the intake and outlet vents.
32
23
43
26
21
15
21
15
2
. Open the
cover
3
. Main Control Knob
Set to either Low Cool or High Cool as required.
(FAN setting operates the fan only.)
* Caution: If the Main Control Knob is turned
off or changed to a fan setting from a cooling
operation setting, WAIT at least 3 minutes
before resetting to a cooling operation.
4
. Thermostat Control Knob
Set the Thermostat Control Knob at the
desired setting. (Usually “6 ~ 7” is a
recommended setting position.) If the room
temperature is unsatisfactory after a
reasonable amount of time, turn the control
knob clockwise to cool the room more, or
anticlockwise to cool the room less.
• When the Thermostat Control Knob is set to
10, moisture may freeze onto the coils and
prevent effective cooling. If this happens, turn
the Main Control knob to High Fan, and the
thermostat control knob anticlockwise. This will
quickly defrost the cooling coil so that normal
cooling can be resumed.
5
. Air Swing Switch
(Airflow direction adjustment
Side-to-Side)
For fixed side-to-side air direction, set the Air
Swing Switch to ON until the desired air direction
is obtained, then move it to OFF.
For continuous side-to-side air circulation, set
the Air Swing Switch to ON and leave it there.
HOW TO OPERATE
CW-C180BG, CW-C241SG (Cooling Only)
CW-C180BG
– 9 –
1
. Power Supply
Set the Main Control Knob to the OFF position;
confirm that the power supply cord is connected
to a proper AC outlet.
32
23
43
26
21
15
21
15
Recommended
Use the air conditioner under
the following conditions:
• Operating temperature range.
(unit in 
°
C)
Indoor unit
Outdoor unit
D.B.T. W.B.T. D.B.T. W.B.T.
Maximum
Temperature
Minimum
Temperature
Maximum
Temperature
Minimum
Temperature
D.B.T.: Dry Bulb Temperature
W.B.T.: Wet Bulb Temperature
• Humidity does not exceed 90%.
Continuous operation at over 90% humidity
may create condensation and waterdrops on
the intake and outlet vents.
  
HEATING
COOLING
27
21
15
20
-5
-6
2
. Open the
cover
3
. Main Control Knob
Set to either Low COOL, High COOL, Low
HEAT or High HEAT as required.
(FAN setting operates the fan only.)
* Caution: If the Main Control Knob is turned
off or changed to a fan setting from a cooling
or heating operation setting, WAIT at least 3
minutes before resetting to a cooling or
heating operation.
4
. Thermostat Control Knob
Set the Thermostat Control Knob to the desired
setting. (Usually “4 ~5” is a recommended
setting for heating and “6 ~ 7” for cooling.) If the
room temperature is unsatisfactory after a
reasonable amount of time, turn the control
knob clockwise or anticlockwise to make the
room cooler or warmer.
• When the Thermostat Control Knob is set to
10, moisture may freeze onto the coils and
prevent effective cooling. If this happens, turn
the Main Control knob to Fan, and the thermo-
stat control knob anticlockwise. This will quickly
defrost the cooling coil so that normal cooling
can be resumed.
5
. Air Swing Switch
(Airflow direction adjustment
Side-to-Side)
For fixed side-to-side air direction, set the Air
Swing Switch to ON until the desired air direction
is obtained, then move it to OFF.
For continuous side-to-side air circulation, set
the Air Swing Switch to ON and leave it there.
HOW TO OPERATE
CW-A180BG (Cooling & Heating)
CW-C180BG
– 10 –
TROUBLE
CHECK
RESULT
CAUSE
REMEDY
Fan Motor and
1. Supply Voltage.
Less than - 10% by Rated.
Customer Restarted unit
Consult ELECTRICIAN.
Compressor
2. Fuse Box or Circuit Breaker.
Open Contacts.
immediately without
Repair Open Circuit.
won’t run.
waiting 3 minutes
WAIT FOR 3 MINUTES.
3. Power cord or Wiring Harness.
Pulled loose or Shorted.
Repair or Replace it.
4. Thermostat Setting.
Higher than ROOM TEMP.
Set it LOWER.
Fan Motor
1. Objects around Fan.
Locked Fan.
Fan Hitting Cowling or
Adjust Fan Position set screw.
won’t run
Foreign Materials.
Remove Foreign Materials.
Frozen Bearings.
Replace Fan Motor.
2. RESISTANCE between Wires.
Shorted/Open circuit.
Shorted or Burned out.
Replace Fan Motor.
3. Capacitor Fan Motor.
OHM Meter doesn’t Deflect.
Capacitor Defect.
Replace Capacitor Fan.
4. Main Control Switch.
No contacts at Position Shown.
Main Control Switch defect.
Replace Main Control Switch.
Compressor
1. Thermostat Setting.
Higher than ROOM TEMP.
Set it lower.
won’t run
2. RESISTANCE between
Shorted.
Winding Coil touched to the
Replace Compressor.
(Fan runs)
Terminal and the
Body.
Compressor Body.
3. RESISTANCE between
Shorted.
Rear Shorted or Burnt out.
Replace Compressor.
Terminals.
4. Overload Protector.
Infinity between Terminals.
Overload protector defect.
Replace Overload Protector.
5. Capacitor Compressor.
OHM Meter doesn’t deflect.
Capacitor defect.
Replace Capacitor Comp.
6. Thermostat.
No CLICK around position.
Thermostat defect.
Replace Thermostat.
7. Main Control Switch.
No contacts at Position shown.
Main Control Switch defect.
Replace Main Control Switch.
Insufficient
1. Thermostat Setting.
Higher or lower than ROOM TEMP.
Set it lower or higher.
cooling or
2. Ventilation Door open.
Open.
Reduces capacity.
Close Vent door.
heating
3. Air Filter dirty.
Clogged or Dirty.
Restricted air circulation.
Clean or Replace Air Filter.
4. Location of installation.
Sunlight hitting outdoor side
Restricted Heat Exchanger
Consider building an AWNING.
at cooling.
Obstacles.
Restricted Heat Exchanger.
Remove obstacles or
reinstall unit.
5. Evaporator/Condenser
Clogged or Dirty.
Restricted air circulation.
Clean by steam cleaner.
Coil obstructed.
6. Unit capacity for the room too
Not Satisfied.
Replace the Unit with
small.
bigger one.
7. Temp difference and
REFER PERFORMANCE
Leakage of refrigerant or
Locate repair leak.
Running Current.
EVALUATION.
refrigeration system is blocked.
Flush refrigeration cycle.
Noise
1. Source of Noise.
Vibration.
Faulty installation.
Reinstall unit or Reinforce
the installation.
Intermittent Noise.
Fan hitting objects.
Adjust Fan position or
remove Foreign Materials.
Refrigerant tubing touching
About 1/2" Clearance.
each other.
Fan splashing Drain Water.
Consider Attaching the Drain
Pan and pull plug in bottom
pan. (REFER INSTALLATION
INSTRUCTIONS)
No heating
1. Reversing Valve Coil.
Infinity between Coil.
Replace Reversing Valve coil.
(Fan and
2. Reversing Valve.
Resistance between  Reversing
Replace Reversing Valve.
Compressor run.)
Valve Coil.
Water dripping
1. Unit Installation.
Tilted to inside room.
Restricted run off.
Tilt unit to outside slightly.
inside room
2. Drain Tray-STYROFOAM
Clogged.
Clogged or blocked.
Remove the foreign materials.
Pieces blocking Drain
(REFER OPERATING
Channel.
INSTRUCTIONS)
Frozen
1. Thermostat Setting
Set too low for ambient
Outdoor TEMP. Low
Set Main Control Switch to
Evaporator
conditions.
(Night time)
Fan to melt ICE and Set the Temp.
control to higher temperature
2. Air Filter/Evaporator.
Clogged or Dirty.
Restricted air circulation
Clean Air Filter/Evaporator.
3. Temp. difference and
REFER PERFORMANCE
Leakage of refrigerant or
Locate repair leak.
Running Current.
EVALUATION.
refrigeration system is blocked.
Flush refrigeration cycle.
Frozen
1. Outdoor ambient
Heating Operation at Low
Outdoor ambient temp.
Set Main Control Switch
Condenser
temp.
outdoor ambient temp.
is Low.
to Fan to melt ICE.
TROUBLESHOOTING GUIDE
WARNING: DISCONNECT UNIT FROM ELECTRICAL POWER SUPPLY BEFORE MAKING ANY ELECTRICAL
CHECKS.
DISCHARGE THE CAPACITOR BEFORE CHECKING IT.
CW-C180BG
– 11 –
Always turn off the air conditioner and main power supply before cleaning to ensure safety.
CARE AND MAINTENANCE
Air Filter
The air filter behind the intake grille should be
washed at least every two weeks or as often as it
needs cleaning.
HOW TO CLEAN THE AIR FILTER:
1. To remove the air filter, grasp the tab on the filter
and pull to the right.
2. Vacuum the filter on the dusty side to remove
light dust.
3. Wash the filter, cleaner side up under gently flowing
water to wash out accumulated dust and lint.
4. If the filter is very dirty, use a mild household
detergent in the wash water.
Let the filter dry thoroughly before reinstalling it.
When reinstalling the filter, be sure the word “FRONT”
is facing you as you slide the filter back into place.
Front Grille
Clean the front grille with a clean cloth lightly
dampened with mild liquid dish-washing detergent.
Caution
Wipe off dirt with a soft, dry cloth (use a vacuum
cleaner to remove dust from the air intake.)
Use a cloth and water less than 40
°
C to remove
stubborn dirt (the cloth should be well-wrung).
Do not use the following cleansers as they cause
the paint to peel and lead to malfunctions:
Benzene, thinner, scouring powder, chemical-
soaked cloths, etc.
lukewarm water +
mild detergent
Vacuum cleaner
BENZENE
THINNER
Cabinet
Clean the cabinet with mild soap or detergent and
lukewarm water.
Annual check
* After long-term usage of room air conditioners, dust
and dirt will accumulate inside, lowering the perform-
ance.  This may cause the generation of odour or may
impede the drainage of the dehumidifying water.
* Besides regular cleaning of the air conditioner, a
separate annual check is also recommended
(chargeable). Please request your dealer to carry out
these checks.
– 11 –
Page of 18
Display

Click on the first or last page to see other CW-C180BG / CW-C241SG / CW-A180BG service manuals if exist.