DOWNLOAD Panasonic CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE Service Manual ↓ Size: 33.93 MB | Pages: 127 in PDF or view online for FREE

Model
CS-Z20TKEW CS-Z25TKEW CS-Z35TKEW CS-Z42TKEW CS-Z50TKEW CS-Z71TKEW CS-XZ20TKEW CS-XZ25TKEW CS-XZ35TKEW CS-XZ50TKEW CU-Z20TKE CU-Z25TKE CU- 35TKE CU-Z42TKE CU-Z50TKE CU-Z71TKE CU-Z20TKE CU-Z25TKE CU-Z35TKE CU-Z50TKE
Pages
127
Size
33.93 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-z20tkew-cs-z25tkew-cs-z35tkew-cs-z42tkew-cs-z50.pdf
Date

Panasonic CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE Service Manual ▷ View online

53 
 
How to pull the piping and drain hose out, in case of the 
embedded piping.
 
In case of left piping how to insert the 
connection cable and drain hose.
Rear view for left piping installation
Drain cap
Drain hose
Adjust the piping slightly 
downwards.
Drain hose
Connection cable
 
PVC tube 
for drain 
hose
Indoor unit
Piping
Cable
Apply putty or 
caulking material 
to seal the wall 
opening.
Connection cable
Piping
More than 
470 mm
PVC tube (VP-65) for piping 
and connection cable
PVC tube for drain hose (VP-30)
PVC tube for drain 
hose (VP-20)
More than 700 mm
Drain hose 
from main unit
Cable
45°
Drain 
hose
Piping
Sleeve for piping hole
Drain hose
Piping
Connection cable
More than 950 mm
(For the right piping, follow the same procedure)
Exchange the drain hose and 
the cap
(3/4 ~ 1.75HP) or 
1150 mm (2.0 ~ 2.5HP)
More than 950 mm 
(3/4 ~ 1.75HP) or 
1150 mm (2.0 ~ 2.5HP)
70 mm (3/4 ~ 1.75HP) or 
80 mm (2.0 ~ 2.5HP)
12.2.4  Connect the Cable to the Indoor Unit 
The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille. 
1  Install the indoor unit on the installing holder that mounted on the wall. 
2  Open the front panel and grille door by loosening the screw. 
3  Cable connection to the power supply through Isolating Devices (Disconnecting means). 
Connect the approved polychloroprene sheathed power supply cord 3 × 1.5 mm
2
 (3/4 ~ 1.75HP) or  
3 × 2.5 mm
2
 (2.0 ~ 2.5HP), type designation 60245 IEC 57 or heavier cord to the terminal board, and 
connect the other end of the cable to Isolating Devices (Disconnecting means). 
Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or 
otherwise) is too short. 
In unavoidable case, joining of power supply cord between isolating devices and terminal board of air 
conditioner shall be done by using approved socket and plug rated 15/16A (3/4 ~ 1.75HP) or 16A 
(2.0HP) or 20A (2.5HP). Wiring work to both socket and plug must follow to national wiring standard. 
4  Bind all the power supply cord lead wire with tape and route the power supply cord via the left escapement. 
5  Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed  
4 × 1.5 mm
2
 (3/4 ~ 1.75HP) or 4 × 2.5 mm
2
 (2.0 ~ 2.5HP) flexible cord, type designation 60245 IEC 57 or 
heavier cord. 
6  Bind all the indoor and outdoor connection cable with tape and route the connection cable via the right 
escapement. 
 
 
 
 
 
 
54 
7  Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor 
unit according to the diagram below. 
 
Terminals on the outdoor unit
S1
2
3
1
2
3
Colour of wires (connection cable)
Terminals on the indoor unit
L
1
N
S1
2
3
OR
L
1
N
S1
2
3
(Power supply cord)
Connection for multi inverter 
model (Outdoor power 
supply)
Terminals on the isolating devices 
(Disconnecting means)
(L) (N)
 
 
8  Secure the power supply cord and connection cable onto the control board with the holder. 
9  Close grille door by tighten with screw and close the front panel. 
 
Connection cable
Power supply cord
Terminal Board
Control 
Board
Recommended 
length (mm)
Earth Wire 
longer than 
others 
AC wires 
for safety 
reason
Holder
Holder
Indoor & outdoor 
connection cable
Power supply 
cord
Outdoor unit
Isolating Devices
Tape
Tape
Recommended 
length (mm)
a
b
c
d
e
f
g
55 35 35 50 40 35 60
 
 
 WARNING
 
 This equipment must be properly earthed. 
 
Note: 
  Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap. 
  Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively. 
  Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires as shown in the figure for the 
electrical safety in case of the slipping out of the cord from the anchorage. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
55 
12.2.4.1  Wire Stripping Connecting and Requirement 
 
WARNING
RISK OF FIRE
JOINING OF 
WIRES MAY 
CAUSE 
OVERHEATING 
AND FIRE.
  Do not joint wires
OR
OR
  Use complete wire without joining.
  Use approved socket and plug with earth pin.
   Wire connection in this area must follow to national 
wiring rules.
Wire stripping
No loose strand 
when inserted
10 ± 1 mm
5 mm or more
Indoor/outdoor 
connection 
terminal board
(gap between wires)
Conductor 
fully inserted
Conductor over 
inserted
Conductor not 
fully inserted
ACCEPT
PROHIBITED
PROHIBITED
 
 
12.2.4.2 Cutting 
and 
Flaring the Piping 
1  Please cut using pipe cutter and then remove the burrs. 
2  Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end 
down to avoid the metal powder entering the pipe. 
3  Please make flare after inserting the flare nut onto the copper pipes. 
 
When properly fl ared, the internal surface of the 
fl are will evenly shine and be of even thickness. 
Since the fl are part comes into contact with the 
connections, carefully check the fl are fi nish.
 Improper  fl aring 
Inclined Surface 
damaged
Cracked Uneven 
thickness
1.  To cut
2.  To remove burrs
3.  To fl are
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle
Bar
0 – 0.5 mm
Copper pipe
Reamer
Point down
Pipe
 
 
12.2.5  Connect the Piping  
12.2.5.1 Connecting 
the Piping to Indoor 
For connection joint of all model (except R32 model) 
Please make flare after inserting flare nut (locate at 
joint portion of tube assembly) onto the copper pipe. 
(In case of using long piping) 
 
Connect the piping 
  Align the center of piping and sufficiently tighten 
the flare nut with fingers. 
  Further tighten the flare nut with torque wrench in 
specified torque as stated in the table. 
 
Torque 
wrench
Spanner or 
Wrench
 
 
For connection joint location at inside building for R32 
model only 
  Decide the length. 
  Cut and remove the tube connectors at indoor 
copper pipings (both gas and liquid piping) by 
using pipe cutter. Remove burrs from cut edge. 
  Use pipe expander to expand the end of long 
piping. 
  Align the center of piping and braze the piping 
joints. 
 
Indoor 
copper pipe
Tube connector
(40~50mm)
Brazing point
1. Cut and Remove
2.  Expand long pipe
3.  Braze both pipe
 
56 
12.2.5.2 Connecting 
the 
Piping to Outdoor 
Decide piping length and then cut by using pipe cutter. 
Remove burrs from cut edge. 
Make flare after inserting the flare nut (locate at valve) 
onto the copper pipe. Align center of piping to valve 
and then tighten with torque wrench to the specified 
torque as stated in the table. 
 
 
 
 
Do not overtighten, overtightening may cause gas leakage. 
 
 
Piping size 
Torque 
6.35 mm (1/4") 
[18 N•m (1.8 kgf•m)] 
9.52 mm (3/8") 
[42 N•m (4.3 kgf•m)] 
12.7 mm (1/2") 
[55 N•m (5.6 kgf•m)] 
15.88 mm (5/8") 
[65 N•m (6.6 kgf•m)] 
19.05 mm (3/4") 
[100 N•m (10.2 kgf•m)] 
 
12.2.5.3  Connecting the Piping to Outdoor Multi  
Decide piping length and then cut by using pipe cutter. 
Remove burrs from cut edge. Make flare after 
inserting the flare nut (locate at valve) onto the copper 
pipe. Align center of piping to valve and then tighten 
with torque wrench to the specified torque as stated in 
the table. 
 
Connection pipe
(female side)
Auxiliary pipe
(male side)
Flare Nut
Hall Union
Liquid side
 
 
 
 
* For Gas side piping please refer table and diagram below 
Outdoor Multi Combination Model 
Pipe size 
(refer to 
diagram)
R32 Model
R410A Model
CS-Z20***,
CS-XZ20***,
CS-Z25***,
CS-XZ25***,
CS-Z35***,
CS-XZ35***
CU-2Z35***,
CU-2Z41***,
CU-2Z50***,
CU-3Z52***,
CU-3Z68***,
CU-4Z68***,
CU-4Z80***,
CU-5Z90***
CU-2E12***,
CU-2E15***,
CU-2E18***,
CU-3E18***,
CU-3E23***,
CU-4E23***,
CU-4E27***,
CU-5E34***
CS-Z42***,
CS-Z50***,
CS-XZ50***
CU-2Z50***,
CU-3Z52***,
CU-3Z68***,
CU-4Z68***,
CU-4Z80***,
CU-5Z90***
CU-2E18***,
CU-3E18***,
CU-3E23***,
CU-4E23***,
CU-4E27***,
CU-5E34***
(CZ-MA1P)
CS-Z71***
CU-4Z80***,
CU-5Z90***
CU-4E27***,
CU-5E34***
(CZ-MA2P) & 
(CZ-MA3P)
Hall Union
Connection pipe 
(female side)
Auxiliary pipe
 (male side)
Flare Nut
Hall Union
Packing
Connection pipe 
(female side)
Auxiliary pipe
 (male side)
Pipe size reducer (CZ-MA1P)
Flare Nut
Auxiliary pipe
 (male side)
 (Outdoor)
Auxiliary pipe
 (male side)
 (Indoor)
Hall Union
Hall Union
Packing
Packing
Connection pipe 
(female side)
Pipe size expander 
(CZ-MA2P)
Flare Nut
Pipe size reducer 
(CZ-MA3P)
Gas side
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other CS-Z20TKEW / CS-Z25TKEW / CS-Z35TKEW / CS-Z42TKEW / CS-Z50TKEW / CS-Z71TKEW / CS-XZ20TKEW / CS-XZ25TKEW / CS-XZ35TKEW / CS-XZ50TKEW / CU-Z20TKE / CU-Z25TKE / CU- / 35TKE / CU-Z42TKE / CU-Z50TKE / CU-Z71TKE / CU-Z20TKE / CU-Z25TKE / CU-Z35TKE / CU-Z50TKE service manuals if exist.