seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation
mode. From the above judgment, the decided operation will start operate earlier than the set time as shown below.
Timer Signal Receiving sound During Operation.
mode. From the above judgment, the decided operation will start operate earlier than the set time as shown below.
Timer Signal Receiving sound During Operation.
Timer Signal Receiving Sound When the Air Conditioner Stops.
13. Protection
control
13.1 Protection Control For All Operations
13.1.1 Time Delay Safety Control
● The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
● This control is not applicable if the power supply is cut off and on again.
● This phenomenon is to balance the pressure inside the refrigerant cycle.
● This phenomenon is to balance the pressure inside the refrigerant cycle.
13.1.2 30 Seconds Forced Control
● Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
● The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a full
cycle and return back to the outdoor unit.
13.1.3 Total running current control
1. If the outdoor unit total running current is detected exceeding I
1
(A), the frequency instructed for compressor
operation will be decreased.
2. If the running current does not exceed I
1
(A) for 5 seconds, the frequency instructed will be increased.
YE9MKE YE12MKE YE18MKE
Operation mode
I
1
(A) I
1
(A) I
1
(A)
Cooling/ Soft Dry /Fan A*
5.03
6.35
8.98
Cooling/ Soft Dry /Fan B
4.89
6.22
8.00
Heating
4.75
6.22
9.31
*The first 30 minutes of cooling operation, A will be applied.
35
34
(For RE9MKE,RE12MKE) (RE18MKE)
13.1.4 IPM (Power transistor) Protection Control.
1. DC Peak Current Control
● When electric current to IPM exceeds set value of DC17.3 1A, the compressor will stop. It will restart after
three minutes.
● If the set value is exceeded again within 30 seconds, the operation will restart after one minute.
● If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
● Error code [F99] will be displayed.
● If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
● Error code [F99] will be displayed.
2. Overheating protection control
When the IPM temperature rises to 112 ℃ , compressor will stop immediately.
Compressor restarts after three minutes if the temperature decreases to 97℃
Compressor restarts after three minutes if the temperature decreases to 97℃
13.1.5 Compressor
Overheating Prevention Control
Instructed frequency for compressor operation will be regulated compressor discharge temperature. The change of
frequency is as below.
13.1.6 Low pressure Prevention control (Gas Leakage Detection)
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
Comp Frequency
45 Hz or above
64 Hz or above
58 Hz or above
73 Hz or above
Total Outdoor Current
1b≤1<3 1b≤1<1.6 1b≤1<1.3 1b≤1<1.6
Indoor Piping Temp
20 ℃ or above
25 ℃ or less
20 ℃ or above
25 ℃ or less
Operation Mode
Cool/Dry
Heat
Cool/Dry
Heat
Model YE9MKE
YE12MKE
13.1.7 Low Operation Frequency Protection Control
If all following conditions exists, the compressor will run with the frequency of 40 Hz (YE9MKE,YE12MKE) or 30Hz
(YE18MKE)
(YE18MKE)
Models YE9MKE,
YE12MKE
YE18MKE
Intake Air Temp.
≥30 ℃ or <15 ℃
-------------------
≥30 ℃ or <14 ℃
≥28 ℃ or <14 ℃
Outdoor Temp.
≥38 ℃ or <16 ℃
≥24 ℃ or <4 ℃
≥38 ℃ or <13 ℃
≥24 ℃ or <4 ℃
Indoor Piping Temp.
<30 ℃
≥0 ℃
<30 ℃
≥0 ℃
Operation Mode
Cool / Dry
Heat
Cool/ Dry
Heat
13.1.8 Compressor Tank Temperature Rise Protection Control
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
• During Cooling and Soft Dry operations:
39 ℃
39 ℃
39 ℃
38 ℃
Outdoor temperature
RE9/12MKE
112 ℃
112 ℃
110 ℃
100 ℃
RE18MKE
35
Indoor suction temperature - indoor piping temperature is below 4℃.
Indoor temperature and outdoor temperature is 30±5℃.
Remote Control setting 16℃ and Hi Fan Speed.
Indoor temperature and outdoor temperature is 30±5℃.
Remote Control setting 16℃ and Hi Fan Speed.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5℃.
Indoor temperature and outdoor temperature is 20 ± 2℃.
Remote control setting 30℃ and Hi Fan Speed.
Indoor temperature and outdoor temperature is 20 ± 2℃.
Remote control setting 30℃ and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
13.2 Protection Control For Cooling and Soft Dry Operation
13.2.1 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air temperature.
• Compressor frequency will adjust base on outdoor air temperature.
RE9MKE, RE12MKE RE18MKE
13.2.2 Freeze Prevention Control
1 .Frequency of the compressor
For prevention of freezing of the indoor evaporator, the frequency of the compressor will be changed according to
the indoor piping temperature.
2 .Indoor Fan Control
2 .Indoor Fan Control
Indoor fan speed changes according to the indoor piping temperature.
13.2.3 Dew Prevention Control
• To prevent dew formation at indoor unit discharge area.
Outdoor air temp.( ℃.)
38
25
18
11
free
Free
38
26
16
37
22
15
8
Outdoor air temp.( ℃.)
38
25
18
11
free
16
26
37
47
37
22
15
8
9℃.
8℃.
6℃.
0℃.
8℃.
6℃.
0℃.
36
• This control starts if all conditions continue for 20 minutes:
- Operated with Cooling or Soft Dry Mode.
- Indoor intake temperature is between 25℃ and 29℃.
- Outdoor air temperature is less than 30℃.
- Indoor intake temperature is between 25℃ and 29℃.
- Outdoor air temperature is less than 30℃.
• This control stopped then receive air swing change signal from Remote Control.
13.2.4 Overload
Protection For Cooling Operation
The frequency for the compressor will change according to the outdoor piping temperature.
13.3 Indoor Piping Air Temperature Control (Heating)
13.3.1 Indoor Fan Control
1. Indoor fan is controlled by the indoor piping temperature.
● Manual Fan Speed
Piping Temperature(℃)
K0 K1 K2 K3 K4 K5 K6 K7 K8 K9 K10
K11
16 19 24 32 32 36 36 39 54 54 57 60
● Auto Fan Speed
2. During heating operation, the indoor fan will run at the following speed when the compressor stops.
3. Hot Start
When the heating operation starts, the indoor fan stops and the compressor runs with a certain frequency.
This is to prevent the cold airflow from blowing.
If the piping temperature rises to 19 ℃, and the indoor fan speed and airflow direction varies with the indoor piping
temperature, the hot start control is completed.
When the heating operation starts, the indoor fan stops and the compressor runs with a certain frequency.
This is to prevent the cold airflow from blowing.
If the piping temperature rises to 19 ℃, and the indoor fan speed and airflow direction varies with the indoor piping
temperature, the hot start control is completed.
13.3.2 Overload Protection Control
The frequency for the compressor is determined by indoor piping temperature.
K7
Fixed
+15rpm/s
Free
63℃
.
Outdoor pipe Temp.
61℃
60℃
56℃
RE9MKE, RE12MKE
RE18MKE
58℃
Max:40 Hz Min 30Hz
K8
460