33 
seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation 
mode. From the above judgment, the decided operation will start operate earlier than the set time as shown below. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Timer Signal Receiving sound During Operation. 
 
 
Timer Signal Receiving Sound When the Air Conditioner Stops. 
 
 
13. Protection 
control 
13.1  Protection Control For All Operations 
13.1.1  Time Delay Safety Control 
● The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on 
again by pressing OFF/ON button at remote control within this period. 
● This control is not applicable if the power supply is cut off and on again. 
● This phenomenon is to balance the pressure inside the refrigerant cycle.
 
13.1.2  30 Seconds Forced Control 
● Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation 
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the 
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit. 
●  The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a full 
cycle and return back to the outdoor unit. 
13.1.3  Total running current control 
1.  If the outdoor unit total running current is detected exceeding I
1
(A), the frequency instructed for compressor 
operation will be decreased. 
2.  If the running current does not exceed I
1
(A) for 5 seconds, the frequency instructed will be increased. 
YE9MKE YE12MKE  YE18MKE 
Operation mode 
I
1
(A) I
1
(A) I
1
(A) 
Cooling/ Soft Dry /Fan A* 
5.03 
6.35 
8.98 
Cooling/ Soft Dry /Fan B 
4.89 
6.22 
8.00 
Heating  
4.75 
6.22 
9.31 
 
*The first 30 minutes of cooling operation, A will be applied. 
35 
34 
 
(For RE9MKE,RE12MKE)                                                  (RE18MKE) 
13.1.4  IPM (Power transistor) Protection Control. 
1.  DC Peak Current Control 
●  When electric current to IPM exceeds set value of DC17.3 1A, the compressor will stop. It will restart after 
three minutes. 
●  If the set value is exceeded again within 30 seconds, the operation will restart after one minute. 
●  If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off. 
●  Error code [F99] will be displayed. 
2.    Overheating protection control 
When the IPM temperature rises to 112 ℃ , compressor will stop immediately. 
Compressor restarts after three minutes if the temperature decreases to 97℃ 
13.1.5 Compressor 
Overheating Prevention Control 
 
 
Instructed frequency for compressor operation will be regulated compressor discharge temperature. The change of 
frequency is as below. 
 
 
 
 
 
 
 
 
 
 
 
13.1.6  Low pressure Prevention control (Gas Leakage Detection) 
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes. 
2.  If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off. 
3. This control is not applicable for deice operation. 
 
Comp Frequency 
45 Hz or above
64 Hz or above 
58 Hz or above 
73 Hz or above 
Total Outdoor Current 
1b≤1<3 1b≤1<1.6 1b≤1<1.3 1b≤1<1.6 
Indoor Piping Temp 
20 ℃ or above 
25 ℃ or less 
20 ℃ or above 
25 ℃ or less 
Operation Mode 
Cool/Dry 
Heat 
Cool/Dry 
Heat 
Model YE9MKE 
YE12MKE 
13.1.7  Low Operation Frequency Protection Control 
If all following conditions exists, the compressor will run with the frequency of 40 Hz (YE9MKE,YE12MKE) or 30Hz 
(YE18MKE) 
Models YE9MKE, 
YE12MKE 
YE18MKE 
Intake Air Temp. 
≥30 ℃ or <15 ℃ 
------------------- 
≥30 ℃ or <14 ℃ 
≥28 ℃ or <14 ℃ 
Outdoor Temp. 
≥38 ℃ or <16 ℃ 
≥24 ℃ or <4 ℃ 
≥38 ℃ or <13 ℃ 
≥24 ℃ or <4 ℃ 
Indoor Piping Temp. 
<30 ℃ 
≥0 ℃ 
<30 ℃ 
≥0 ℃ 
Operation Mode 
Cool / Dry 
Heat 
Cool/ Dry 
Heat 
13.1.8  Compressor Tank Temperature Rise Protection Control 
a. Control start conditions 
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A. 
• During Cooling and Soft Dry operations: 
39 ℃ 
39 ℃ 
39 ℃ 
38 ℃ 
Outdoor temperature 
RE9/12MKE 
112 ℃
112 ℃ 
110 ℃ 
100 ℃ 
RE18MKE 
35 
Indoor suction temperature - indoor piping temperature is below 4℃. 
Indoor temperature and outdoor temperature is 30±5℃. 
Remote Control setting 16℃ and Hi Fan Speed. 
• During Heating operations: 
Indoor piping temperature - indoor suction is under 5℃. 
Indoor temperature and outdoor temperature is 20 ± 2℃. 
Remote control setting 30℃ and Hi Fan Speed. 
b. Control contents 
• Compressor stops (and restart after 3 minutes) 
• If the conditions above happen 2 times within 20 minutes, the unit will: 
- Stop operation 
- Timer LED blinks and “F91” indicated 
13.2  Protection Control For Cooling and Soft Dry Operation 
13.2.1  Outdoor Air Temperature Control 
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the 
diagram below. 
• This control will begin 1 minute after the compressor starts. 
• Compressor frequency will adjust base on outdoor air temperature. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                      RE9MKE, RE12MKE                                                                          RE18MKE 
13.2.2  Freeze Prevention Control 
1 .Frequency of the compressor 
For prevention of freezing of the indoor evaporator, the frequency of the compressor will be changed according to 
the indoor piping temperature. 
 
 
 
 
 
 
 
 
 
2 .Indoor Fan Control 
Indoor fan speed changes according to the indoor piping temperature. 
 
 
 
 
 
 
 
 
13.2.3  Dew Prevention Control 
• To prevent dew formation at indoor unit discharge area. 
Outdoor air temp.( ℃.) 
38 
25 
18 
11 
free 
Free    
38    
26  
16  
37
22
15
8
Outdoor air temp.( ℃.)
38
25
18
11
free 
16    
26    
37   
47   
37
22
15
8
9℃. 
8℃. 
6℃. 
0℃. 
36 
• This control starts if all conditions continue for 20 minutes: 
- Operated with Cooling or Soft Dry Mode. 
- Indoor intake temperature is between 25℃ and 29℃. 
- Outdoor air temperature is less than 30℃. 
• This control stopped then receive air swing change signal from Remote Control. 
13.2.4 Overload 
Protection For Cooling Operation 
The frequency for the compressor will change according to the outdoor piping temperature. 
 
 
 
 
 
 
 
 
 
 
 
 
 
13.3  Indoor Piping Air Temperature Control (Heating) 
13.3.1  Indoor Fan Control 
1. Indoor fan is controlled by the indoor piping temperature. 
●  Manual Fan Speed 
 
Piping Temperature(℃) 
K0 K1 K2 K3 K4 K5 K6 K7 K8 K9 K10
K11
16 19 24 32 32 36 36 39 54 54 57  60 
 
●   Auto Fan Speed 
 
 
 
2. During heating operation, the indoor fan will run at the following speed when the compressor stops.
 
 
3. Hot Start 
When the heating operation starts, the indoor fan stops and the compressor runs with a certain frequency. 
This is to prevent the cold airflow from blowing. 
If the piping temperature rises to 19 ℃, and the indoor fan speed and airflow direction varies with the indoor piping 
temperature, the hot start control is completed.
 
13.3.2  Overload Protection Control 
The frequency for the compressor is determined by indoor piping temperature. 
 
K7 
Fixed 
+15rpm/s 
Free 
63℃
.
Outdoor pipe Temp.
61℃
60℃
56℃
RE9MKE, RE12MKE
RE18MKE
58℃
Max:40 Hz   Min 30Hz 
K8 
460
Page of 47
Display