36
11.10.
Ventilation Control
• To circulate the indoor air.
• The ventilation operation is enable by pressing the VENTILATION Button. (As a default setting, ventilation will be turned on auto-
matically once the air conditioner operation starts).
11.10.1. Simultaneous Operation
• Operates simultaneously with Auto/Cooling/Drying operation.
• Press VENTILATION button at remote control repeatedly to select your desired ventilation setting. Auto/Cooling/Drying opera-
tion remains as normal regardless of ventilation setting.
• When OFF/ON button at remote control is pressed, all of the air conditioner operations are turned off.
11.10.2. Independent Operation
• Ventilation operates independently.
• Ventilation can be turned on when the air conditioner is in non-operation mode.
• Fan speed in this setting remains as AUTO.
• Press OFF/ON button at remote control to turn off the ventilation operation.
37
12 Protection Control
12.1.
Time Delay Safety Control
• Compressor will not start for three minutes after stop of the operation.
12.2.
30 Seconds Forced Operation
• Once compressor starts the operation, it will not stop its operation for 30 seconds. However, it can be stopped with the remote
controller or the Auto button on the indoor unit.
12.3.
Total Running Current Control
1. When the total running current exceeds l1, compressor operation frequency is reduced. If it reaches below l1, the operation
frequency is increased. (But, up to programmed frequency.)
2. If total running current exceeds l2, compressor is stopped immediately.
3. If it happens three (3) times within 20 minutes, operation will be stopped and Timer LED blinks. (“F98” is activating.)
12.4.
IPM (Power transistor) Protection Control (DC Peak detection
Abnormal Current Control
• If inverter load current (DC peak) exceeds a rated value, compressor will be stopped immediately. When the excess occurs
within 30 seconds after operation, it restarts in 1 minute and when after 30 seconds, restarts in 2 minutes.
• If the excess continuously occurs 7 times within 30 minutes after compressor starts, the unit will be stopped and timer LED on
the indoor unit will be blinking. (“F99” is to be confirmed.)
IPM Overheating Prevention Control
• If temperature of IPM exceeds 103
qC, compressor will be stopped. It will restart in 2 minutes. Temperature for restarting: 90qC.
• If the excess occurs 7 times within 30 minutes after compressor starts, the compressor will be stopped and timer LED on the
indoor unit will be blinking. (“F96” is to be confirmed.)
12.5.
Compressor Overheating Prevention Control
1. If discharge pipe temperature exceeds 100
qC, compressor power will be limited.
2. If discharge pipe temperature exceeds 112
qC, compressor will be stopped.
3. If the above excess occurs 4 times per 10 minutes, timer LED will be blinking. (“F97” is to be confirmed.)
12.6.
Outdoor High Pressure Prevention Control (Cooling and Dry operations)
1. If outdoor heat exchanger temperature exceeds 63
qC in cooling or dry operation, compressor will be stopped.
2. Timer LED is not blinking. (“F95” is memorized, then.)
12.7.
Compressor Protection Control (Refrigeration Cycle Abnormality)
In cooling and Dry operations
1. When compressor is operated continuously for 5 minutes in the maximum cooling power: a running current of 0.7 - 1.4A and
“[Indoor intake air temperature] - [Indoor heat exchanger temperature]” < 4
qC, compressor will be stopped.
2. If the above excess occurs twice for 20 minutes, timer LED is to be blinking. (“F91” is to be confirmed.)
In Heating operation
1. When compressor is operated continuously for 5 minutes in the rated heating power: a running current of 0.7 - 1.4A and
“[Indoor heat exchanger temperature] - [Indoor intake air temperature]” < 5
qC, compressor will be stopped.
2. If the above excess occurs twice for 20 minutes, timer LED is to be blinking. (“F91” is to be confirmed.)
Running current
CS-XE9EKE
CS-XE12EKE
Cooling
I1
3.7A
5.8A
I2
25.0A
25.0A
Heating
I1
5.9A
8.2A
I2
25.0A
25.0A
38
12.8.
Four-way Valve Operation Detection Control (Switching Abnormality between Cool-
ing and Heating)
In Cooling operation
1. When indoor heat exchanger temperature exceeds 45
qC in 4 minutes after compressor starts, compressor will be stopped.
2. If the above excess occurs 4 times per 30 minutes, timer LED is to be blinking. (“F11” is to be confirmed.)
In Heating operation
1. When indoor heat exchanger temperature is below 0
qC in 4 minutes after compressor starts, compressor will be stopped.
2. If the above excess occurs 4 times per 30 minutes, timer LED is to be blinking. (“F11” is to be confirmed.)
12.9.
Anti-Freezing Control (Cooling and Dry operations)
Limit of Cooling power
1. When temperature of indoor heat exchanger is below 5
qC, operating frequency will be decreased.
2. When temperature of indoor heat exchanger exceeds 7
qC, operating frequency will be increased. (But, up to programmed fre-
quency.)
3. When temperature of indoor heat exchanger is below 0
qC continuously for 6 minutes, compressor will be stopped.
4. Timer LED is not blinking. (“H99” is memorized, then.)
Limit of Indoor fan speed
• When temperature of indoor heat exchanger is below 6
qC (2qC at Dry) continuously for 6 minutes, indoor fan speed will be
increased by 50 rpm.
12.10.
Outdoor Air Temperature Control
In Cooling and Dry operations
1. When outdoor air temperature is below 25
qC, the maximum power will be limited up to about 80 - 100% of the rated power.
2. When outdoor air temperature is below 18
qC, the maximum power will be limited up to about 50 - 100% of the rated power.
3. When outdoor air temperature is below 11
qC, the maximum power will be limited up to about 26 - 81% of the rated power.
12.11.
Indoor Intake Air Temperature Control (Heating operation)
1. When indoor air temperature is 35
qC or more, the maximum power will be limited up to the rated power.
2. When fan speed is set at “Lo” and intake air temperature is below 21
qC, the maximum power will be limited up to the rated
power.
39
13 Servicing Mode
13.1. Auto OFF/ON Button
This button is used to pump down the air conditioner during servicing or transferring of outdoor unit.
1. It can be used to operate the air conditioner in limited function if remote control is misplaced or malfunction.
• Auto operation will start when Auto OFF/ON Button is pressed and released within 5 seconds.
• Within 5 minutes of each operation, if the Auto OFF/ON Button is pressed again for more than 5 seconds the air conditioner
will switch to another operation after “Beep” sound.
2. The Auto OFF/ON Button may be used together with remote control to set / change the advanced setting of air conditioner
operation.
• Press and hold AUTO OFF/ON Button for more than 5 seconds, the air conditioner always operate force cooling operation.
• Press and hold AUTO OFF/ON Button until 2 Beep sounds are heard, the forced heating operation is at standby condition.
• Press and hold AUTO OFF/ON Button until 3 Beep sounds are heard, the various setting mode is at standby condition.
• Press and hold AUTO OFF/ON Button until 4 Beep sounds are heard, the individual correspondence mode is at standby con-
dition.
• During standby condition, when the indoor unit receives “AC RESET” signal (Beep sound is heard) from remote control, the
corresponding mode will be activated.
Page of 79