 2. When operate together with ON/OF timer.
 a. ON timer is set during operation stop.
Previous operation is Oxygen only,
→ Previous mode (Auto, Heat, Cool, Dry, Fan) only will operate.
 b. ON timer is set during Oxygen only operation.
→ Previous mode (Auto, Heat, Cool, Dry, Fan) + Oxygen will operate.
 c. OFF timer during Oxygen only operation.
→ Oxygen operation stop.
 d. There is no preliminary operation for Oxygen enrich operation.
 3. Remote control setting during Oxygen only operation.
     • 
• 
• 
• Remote control setting is acceptable during oxygen only operation.
D. Oxygen monitor indication
During oxygen enrich operation, oxygen monitor LED lights ON.
     • 
• 
• 
• Oxygen LED lights is ON or OFF when Oxygen operation is set to ON or OFF regardless of outdoor oxygen supply level.
In case of indoor unit is totally stop and vacuum pump is still running (during delay stop operation) oxygen LED is blinking
(ON 1s - OFF 1s).
8.3.3. Oxygen Enrich Control -2
A. Oxygen enrich system
 1. Indoor intake air temp sensor
 2. Indoor oxygen discharge hole
 3. Remote control
 4. Oxygen LED
 5. Connecting hose
 6. Vacuum pump
 7. Pump discharge hole
 8. Pump suction hole
 9. Pump motor cooling fan A
 10. Pump motor cooling fan B
 11. Pump motor OLP
 12. 2 way valve
 13. Pressure reduction device
 14. Odor filter
 15. Oxygen enrich membrance
 16. Outdoor air temp sensor
 17. Outdoor oxygen discharge hole
 18. Outdoor fan motor
41
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE
B. Oxygen enrich control overview
Upon receiving ON signal from indoor unit, the outdoor vacuum pump, fan & 2 way valve will operate according to the various
protection control setting.
C. Oxygen enrich protection control (O
2
supply level judgement)
 1. Vacuum pump protection
     • 
• 
• 
• Base on outdoor air temp., Comp. top temp., the oxygen supply level is decided.
     • 
• 
• 
• Priority is given to the lower level.
     • 
• 
• 
• Vacuum pump operation cycle time = EOPMPS01.
     • 
• 
• 
• O
2
supply level change only after vacuum pump ON/OFF operation completed 1 cycle time if the new level is higher than
the present level.
     • 
• 
• 
• O
2
supply level change immediately if the new level is lower than the present level (avoid O
2
supply level hunting).
     • 
• 
• 
• Vacuum pump operate with ON/OFF timing according to O
2
supply level except during continuous running required by
freeze-up prevention control (F-2).
E.g. Oxygen supply level change timing (vacuum pump continuous running control, (C-2) not yet activated).
42
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE
Outdoor air temp. status
O
2
supply level
Comp. top temp. status
O
2
supply level
5
0
2
1
4
1
1
2
3
2
0
3
2
3
1
Continuous running ( )
(freeze-up prevention control)
0
0
43
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE
O
2
Enrich
Operation
Protection Control
O
2
supply level
Vacuum Pump Operation Time
Remark
OFF time (min)
ON time (min)
OFF
0
EOPMPS01 - EOPMPS04
EOPMPS04
Continuous OFF
ON
1
EOPMPS01 - EOPMPS02
EOPMPS03
3 min ON 7 min OFF
2
EOPMPS01 - EOPMPS03
EOPMPS02
7 min ON 3 min OFF
3
0
EOPMPS01
Continuous ON
In this condition, when Oxygen operation is ON, vacuum pump run continuously regardless of O
2
supply level (vacuum pump
continuous running control (C-2) is deactivated).
For detail, refer to freeze-up prevention, vacuum pump continuous running control (F-2).
Detail Explanation for Specification
Data Name
Item
Data
EOPMPS01
Vacuum pump operation cycle time
10 min
EOPMPS02
O
2
supply level 2, vacuum pump ON time
7 min
EOPMPS03
O
2
supply level 1, vacuum pump ON time
3 min
EOPMPS04
O
2
supply level 0, vacuum pump ON time
0 min
     • 
• 
• 
• Base on outdoor air temp. & comp. top temp., vacuum pump ambient temp. is projected to prevent vacuum pump temp.
rise.
     • 
• 
• 
• To prevent ice formation in connecting tube during low outdoor air temperature, continuous running protection control is
implemented.
(During low outdoor temp., stagnant water in tube may freeze-up if ON/OFF operation is implemented).
     • 
• 
• 
• If outdoor temp. sensor abnormal, open or short circuit, temperature reading become below -10°C or above 40°C where
the O
2
supply level will become 0 (operation stop).
     • 
• 
• 
• Outdoor air temp. update/renew every 30 min during soft dry mode (instant renewal for other mode).
Data Name
Description
Data
EOPMPT01
Outdoor air temp. control temp.
-12°C
EOPMPT02
Outdoor air temp. control temp.
-10°C
EOPMPT03
Outdoor air temp. control temp.
-10°C
EOPMPT04
Outdoor air temp. control temp.
-8°C
EOPMPT05
Outdoor air temp. control temp.
3°C
EOPMPT06
Outdoor air temp. control temp.
5°C
EOPMPT07
Outdoor air temp. control temp.
26°C
EOPMPT08
Outdoor air temp. control temp.
27°C
EOPMPT09
Outdoor air temp. control temp.
32°C
EOPMPT10
Outdoor air temp. control temp.
33°C
EOPMPT11
Outdoor air temp. control temp.
44°C
EOPMPT12
Outdoor air temp. control temp.
45°C
EOPMPT13
Outdoor air temp. correction value, Heat
0 deg
EOPMPT14
Comp. top temp. control
44°C
EOPMPT15
Comp. top temp. control
45°C
EOPMPT16
Comp. top temp. control
69°C
EOPMPT17
Comp. top temp. control
70°C
 2. Vacuum pump continuous running control
     • 
• 
• 
• Vacuum pump continuous running control
(Life span counter measure)
Direction
: O
2
supply level, continuous running instruction time
Control
: O
2
supply level
i. Action explaination
: O
2
supply level when continue for EOPMPS05 min, the proceeding level 3 will limited to maximum level
MOPMPL01.
ii. Exceptional condition : a. Outdoor air temp. status 1 (ice prevention control activated).
b. O
2
supply level detection is lower than 3.
44
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE