Panasonic CS-UE9JKE / CS-UE12JKE / CU-UE9JKE / CU-UE12JKE Service Manual ▷ View online
29
2. Manual vertical airflow direction can be set using remote control. The angels of the vane are as stated above. When the air
conditioner is stopped using remote control, the vane will shift to close position.
* Above angle data is for reference only.
conditioner is stopped using remote control, the vane will shift to close position.
* Above angle data is for reference only.
11.3.2 Horizontal
Airflow
The horizontal airflow direction louvers can be adjusted manually by hand.
11.3.3 Quiet operation
● To provide quiet operation comparing to normal operation. The Quiet operation can be active or stop by pressing
QUIET/POWERFUL button on remote control.
● Once Quiet mode is active, the unit will continuously operate in QUIET Mode until cancel the mode by pressing
QUIET/POWERFUL button on remote control.
11.3.4 Powerful
operation
● To cooling or heating the room faster comparing to normal operation. The POWERFUL operation can be active or
stop by pressing QUIET/POWERFUL button on remote control.
● When powerful operation is active, the unit will continuously operate in POWERFUL mode until cancel the mode
by pressing QUIET/POWERFUL button on remote control. Operation details are as the fig. below.
1. For cooling, soft Dry mode
Power Button pressed
PIPING
TEMP.
(COOLING)
TEMP.
(COOLING)
FAN SPEED
( rpm)
( rpm)
ON
OFF
AUTO
45 seconds
20 ‘
Shi
20 ‘
Fast Cooling
Cooling, Soft Dry
Min.5’
Correction
Factor(
Factor(
)
℃
-0.25
+0.25
-1.67
-1.00
A
B
C
D
20 ‘
20 ‘
1130 (Max)
730 (Min.)
2. For
Heating
mode:
Power Button pressed
ON
OFF
AUTO
45 seconds
20 ‘
Shi
20 ‘
Fast Heating1
Heating
Min.5’
+0.25
+0.25
+2
+1.00
A
B
C
D
20 ‘
20 ‘
1270 (Max)
940 (Min.)
PIPING
TEMP.
(COOLING)
TEMP.
(COOLING)
FAN SPEED
( rpm)
( rpm)
Correction
Factor(
Factor(
)
℃
Note: The value of A, B, C, D will change according to the indoor temperature.
30
11.3.5 Automatic Restart Control
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to
four minutes after power supply resumes.
four minutes after power supply resumes.
11.3.6 Indication
Panel
LED POWER
TIMER
Color Green
Orange
Light ON
Operation ON
Timer setting ON
Light OFF
Operation OFF
Timer setting OFF
Note:
● If POWER LED blinks, the possible operation of the unit is operation mode judgment, or ON timer
sampling.
● If Timer LED blinks, there is an abnormal operation occurs.
11.3.7 Timer
control
Delay ON Timer can be set using remote controller, the unit with timer set will start operate earlier than the setting
time. This is to provide a comfortable environment when reaching the set ON time. Seventy minutes before the set
time for ON Timer or ON-OFF Timer setting, indoor ( at fan speed of Lo-) and outdoor fan motor start operate for 30
seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation
mode. From the above judgment, the decided operation will start operate earlier than the set time as shown below.
Timer Signal Receiving sound During Operation.
time. This is to provide a comfortable environment when reaching the set ON time. Seventy minutes before the set
time for ON Timer or ON-OFF Timer setting, indoor ( at fan speed of Lo-) and outdoor fan motor start operate for 30
seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation
mode. From the above judgment, the decided operation will start operate earlier than the set time as shown below.
Timer Signal Receiving sound During Operation.
Timer Signal Receiving Sound When the Air Conditioner Stops.
35
31
12. Protection
control
12.1 Protection Control for All Operations
12.1.1 Time Delay Safety Control
● The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
● This control is not applicable if the power supply is cut off and on again.
● This phenomenon is to balance the pressure inside the refrigerant cycle.
● This phenomenon is to balance the pressure inside the refrigerant cycle.
12.1.2 30 Seconds Forced Control
● Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
● The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
12.1.3 Total running current control
1. If the outdoor unit total running current is detected exceeding I
1
(A), the frequency instructed for compressor
operation will be decreased.
2. If the running current does not exceed I
1
(A) for 5 seconds, the frequency instructed will be increased.
UE9JKE UE12JKE
Operation mode
I
1
(A) I
1
(A)
Cooling/ Soft Dry /Fan A*
5.8
7.4
Cooling/ Soft Dry /Fan B
5.6
7.3
Heating
7.01
8.05
*The first 30 minutes of cooling operation, A will be applied.
12.1.4 IPM (Power transistor) Protection Control.
1. DC Peak Current Control
● When electric current to IPM exceeds set value of DC17.3 1A, the compressor will stop. It will restart after
three minutes.
● If the set value is exceeded again within 30 seconds, the operation will restart after one minute.
● If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
● Error code [F99] will be displayed.
● If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
● Error code [F99] will be displayed.
2. Overheating protection control
When the IPM temperature rises to 90 ℃ , compressor will stop immediately.
Compressor restarts after three minutes if the temperature decreases to 97℃
Compressor restarts after three minutes if the temperature decreases to 97℃
12.1.5 Compressor
Overheating Prevention Control
Instructed frequency for compressor operation will be regulated compressor discharge temperature. The change of
frequency is as below.
frequency is as below.
Outdoor temperature
112 ℃
110 ℃
100 ℃
32
12.1.6 Low pressure Prevention control (Gas Leakage Detection)
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
Comp Frequency
45 Hz or above
64 Hz or above
58 Hz or above
73 Hz or above
Total Outdoor Current
1b≤1<3 1b≤1<1.6 1b≤1<1.3 1b≤1<1.6
Indoor Piping Temp
20 ℃ or above
25 ℃ or less
20 ℃ or above
25 ℃ or less
Operation Mode
Cool/Dry
Heat
Cool/Dry
Heat
Model UE9JKE
UE12JKE
12.1.7 Low Operation Frequency Protection Control
If all following conditions exists, the compressor will run with the frequency of 40 Hz (UE9JKE, UE12JKE) or 30Hz
(RE15JKE)
(RE15JKE)
Models UE9JKE,
UE12JKE
Intake Air Temp.
≥30 ℃ or <15 ℃
-------------------
Outdoor Temp.
≥38 ℃ or <16 ℃
≥24 ℃ or <4 ℃
Indoor Piping Temp.
<30 ℃
≥0 ℃
Operation Mode
Cool / Dry
Heat
12.1.8 Compressor Tank Temperature Rise Protection Control
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4℃.
Indoor temperature and outdoor temperature is 30±5℃.
Remote Control setting 16℃ and Hi Fan Speed.
Indoor temperature and outdoor temperature is 30±5℃.
Remote Control setting 16℃ and Hi Fan Speed.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5℃.
Indoor temperature and outdoor temperature is 20 ± 2℃.
Remote control setting 30℃ and Hi Fan Speed.
Indoor temperature and outdoor temperature is 20 ± 2℃.
Remote control setting 30℃ and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
12.2 Protection Control for Cooling and Soft Dry Operation
12.2.1 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air temperature.
• Compressor frequency will adjust base on outdoor air temperature.
Outdoor air temp.( ℃.)
38
25
18
11
free
Free
38
26
16
37
22
15
8
Outdoor air temp.( ℃.)