12.4 Automatic Operation  
•  Automatic operation can be set using remote control. 
•  This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature. 
•  After judged the temperature, the operation mode is determined by referring to the below standard. 
 
 
 
•  Then, the unit starts to operate at determined operation mode, until it is switched off using remote control, with 
the setting temperature as shown in table below. 
 
 
Setting Temperature (Standard) 
Cooling Operation 
25°C 
Soft Dry Operation 
22°C 
Heating Operation 
21°C 
 
•  Operation mode will be determine again for judgement after 1 hour of operation, if the room temperature reaches 
to set temperature and compressor off time is over 7 minutes 30 seconds continuously. 
* The present operation mode will be continued, if the room temperature does not reach to set temperature 
(Compressor keeps running) eventhough after 1 hour from automatic operation mode started. 
 
 
 
Standard for Determining Operation Mode 
2nd Judgement onwards 
 
 
 
 
Next Mode 
Present Mode 
Judgement 
Cooling Soft 
Dry Heating 
 
 
 
Cooling  
23°C 
Heating  
Cooling 
 
 
 
(Judgement: 
23°C & Above) 
Not Applicable 
(Judgement: 
Below 23°C) 
 
 
 
Soft Dry 
 
20°C 
Heating  
Soft Dry 
 
 
 
Not Applicable 
(Judgement: 
20°C & Above) 
(Judgement: 
Below 20°C) 
 
 
 
Cooling  
25°C 
Heating  
Heating 
 
 
 
(Judgement: 
25°C & Above) 
Not Applicable 
(Judgement: 
Below 25°C) 
 
•  Automatic Set Temperature 
For each operation, set temperature will automatically set as shown below. 
•  The setting temperature for all the operations can be changed one level up or one level down from the standard 
temperature as shown in below table by pressing on the temperature up or temperature down button at remote 
control. 
Hi (Standard) Lo 
Operation 
(+2°C) (±0°C)  (-2°C) 
Cooling 27°C 
25°C 
23°C 
Soft Dry 
24°C 
22°C 
20°C 
Heating 23°C 
21°C 
19°C 
 
 
 
 
 
Cooling Operation 
Soft Dry Operation 
↑ 
Intake Air 
Temperature 
23°C  
 
20°C 
Heating Operation 
34 
•  The operation mode judging temperature and standard setting temperature can be increased by 2°C 
permanently, by open the circuit of JX03 at indoor unit’s printed circuit board. 
 
 
12.5  Indoor Fan Speed Control 
•  Indoor fan speed can be set using remote control. 
 
12.5.1  Fan Speed Rotation Chart 
 
Speed 
Cool, Dry 
Heat 
CS-PW18MKD CS-PW24MKD 
SHi Hi 1310 
1530 
Hi  
1280 
1390 
Me Me 1200 
1270 
Lo+ Lo 1180 
1230 
Lo  
1120 
1150 
Lo- Lo- 910 940 
SLo SLo 700  720 
 SSLo 
300 300 
 
 
12.5.2  Automatic Fan Speed Control 
•  When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the 
table. 
o
  Fan speed rotates in the range of Hi, Me and Lo-. 
o
  Deodorizing Control will be activated. 
 
 Speed Mode 
SHi 
Hi 
Me 
Lo+ 
Lo 
Lo- 
SLo 
SSLo 
Stop 
Hi 
  
  
  
  
  
  
  
  
Me 
  
  
  
  
  
  
  
  
Manual 
Lo 
  
  
  
  
  
  
  
  
Cooli
ng 
Normal 
Auto 
  
  
  
  
 
Manual       o   o 
Dr
 
Auto 
 
 
 
 
 
 
 
Hi 
     o 
o o 
Me 
 
   o    o o o o 
Manual 
Lo  
     o  o o o o 
Heatin
Normal 
Auto 
 
   o o  o o o o 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
35 
•  Auto Fan Speed during cooling operation: 
1  Indoor fan will rotate alternately between off and on as shown in below diagram. 
2  At the beginning of each compressor starts operation, indoor fan speed increases gradually for deodorizing 
purpose. 
3  For the first time the compressor operates, indoor fan will be switched to Hi fan speed from Lo- after 70 
seconds from the start of compressor. This cause the room temperature to achieve the setting temperature 
quickly. 
4  During compressor stops, indoor fan will operate at Lo- for the beginning 20 seconds to prevent higher 
volume of refrigerant in liquid form returning to the compressor. 
5  After the compressor turned off for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the 
room. This is to obtain the actual reading of the intake air temperature. 
6  For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and 
lesser noise environment, after 70 seconds from the restarts of compressor. 
 
 
 
•  Auto Fan Speed during Soft Dry operation. 
o
  Indoor fan will rotate alternately between off and Lo-. 
o
  At the beginning of each compressor starts operation, indoor fan will increase fan speed gradually for 
deodorizing purpose. 
o
  When compressor turned off for 6 minutes, indoor fan will start at Lo- to circulate the air in the room. This is 
to obtain the actual reading of intake air temperature. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
36 
•  Auto Fan Speed during Heating operation. 
o
  Indoor fan will rotate in the range of SLo → Me according to the heat exchanger temperature. 
 
 
 
 
12.5.3  Manual Fan Speed Control 
•  Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control. 
•  There are 3 types of fan speed settings: Lo, Me, Hi. 
 
12.6  Outdoor Fan Speed Control 
•  There is only one speed for outdoor fan motor. (Apply for PW18MK). 
•  There is 2 speeds for outdoor fan motor. Outdoor fan speed can be changed to Hi or Lo according to outdoor 
temperature (Apply for PW24MK). 
•  For Cooling and Soft Dry operation, when outdoor temperature reaches to 31°C (Hi-speed), 29°C (Lo-speed). 
•  For heating operation, when outdoor temperature reaches to 13.5°C (Hi-speed), 15.5°C (Lo-speed). 
•  When air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously. 
•  Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off. 
 
12.7  Vertical Airflow Direction Control 
12.7.1 Auto 
Control 
(Cooling and Soft Dry Operation Condition) 
•  When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as 
shown in the diagram. 
•  When stops operation using the remote control, the discharge vent is reset and stops at the closing position. 
•  During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that 
condition, the louver will stop swinging. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Upper limit for cooling mode 
and soft dry mode/17° 
22° 
Closing 
position  
/ 148° 
Swing up and down 
Lower limit for cooling mode and 
soft dry mode/39° 
Horizontal 