7. Block Diagram 
 
 
 
15 
8. Wiring Connection Diagram 
 
 
 
 
16 
9. Installation Instruction 
9.1  Select The Best Location  
9.1.1 Indoor 
Unit 
•  There should not be any heat source or steam near the 
unit.  
•  There should not be any obstacles blocking the air 
circulation. 
•  A place where air circulation in the room is good. 
•  A place where drainage can be easily done. 
•  A place where noise prevention is taken into 
consideration. 
•  Do not install the unit near the door way.  
•  Ensure the spaces indicated by arrows from the wall, 
ceiling, fence or other obstacles. 
•  Recommended installation height for indoor unit shall be 
at least 2.5m. 
9.1.2 Outdoor 
Unit 
•  If an awning is built over the unit to prevent direct 
sunlight or rain, be careful that heat radiation from the 
condenser is not obstructed. 
•  There should not be any animal or plant which could be 
affected by hot air discharged. 
•  Keep the spaces indicated by arrows from wall, ceiling, 
fence or other obstacles. 
•  Do not place any obstacles which may cause a short 
circuit of the discharged air. 
•  If piping length is over the rated length, additional 
refrigerant should be added as shown in the table below: 
 
 
 
 
 
 
 
 
Example: For PA12KKD 
If the unit is installed at a 10m distance, the quantity  
of additional refrigerant should be 60 g. 
…… (10-7) m x 20g/m = 60 g 
 
 
 
Piping size 
Model 
Gas Liquid 
Rated 
Length 
(m) 
Max 
Elevati
on (m) 
Min 
Piping 
Length 
(m) 
Max 
Piping 
Length 
(m) 
Additional 
Refrigera
nt (g/m) 
CS/CU-PA7KKD 
3/8” 
1/4" 
-  5 3 
7 - 
CS/CU-PA9KKD 
3/8” 
1/4” 
-  5 3 
7 - 
CS/CU-PA12KKD 
1/2” 
1/4” 
7 5 3 
10 
20 
CS/CU-PA16KKD 
1/2” 
1/4” 
7 5 3 
10 
20 
8.1.3 Indoor/Outdoor Unit
Note: 
*For optimum performance,  at least two sides 
should be 1m or more away from obstacles. 
 
*This illustration is for explanation purposes 
only. The indoor unit will actually face a 
different way. 
17 
Wall
Indoor
Outdoor
15 mm
Sleeve for
tube ass’y
Approx. 5 - 7 mm
Bushing for tube ass’y
Putty or caulking compound
Ø 70 through hole
 
9.2 Indoor 
Unit 
9.2.1 
How to Fix Installation Plate 
The mounting wall is strong and solid enough to prevent if from the vibration. 
 
The centre of installation plate should be at more 
than 450 mm at right and left of the wall. 
 
The distance from installation plate edge to 
ceiling should more than 75mm. 
 
From installation plate left edge to unit’s left side 
is 62 mm. 
 
From installation plate right edge to unit’s right 
side is 79 mm. 
 
B  
: For left side piping, piping connection for gas should be about 45 mm from this line. 
 
: For left side piping, piping connection cable should be about 785 mm from this line. 
 
1  Mount the installation plate on the wall with 5 screws or more. (If mounting the unit on the wall, consider 
using anchor bolts.) Always mount the installation plate horizontally by aligning the marking-off line with 
the thread and using a level gauge. 
2   Drill the piping plate hole with ø70 mm hole-core drill. 
z  Put measuring tape at position as shown in the diagram above. The hole centre is 
obtained by measuring the distance namely 115 mm and 120 mm for left and right hole 
respectively. 
z  Drill the piping plate hole at either the right or left and the hole should be slightly slanted 
to the outdoor side. 
 
9.2.2 
To Drill a Hole in the Wall and Install a Sleeve of 
Piping 
Insert the piping sleeve to the hole. 
Fix the busing to the sleeve. 
Cut the sleeve until it extrudes about 15mm from the wall  
 
 
 
Finish by sealing the sleeve with putty or caulking compound at the final 
stage.  
 
 
Caution 
When the wall is hollow, please be sure to use the sleeve for tube 
ass’y to prevent dangers caused by mice biting the connecting 
cable. 