š  Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below 
and the positions of the vane are as Figure 2 above. 
 
Pattern  1 2 3 4 5 
Airflow Direction 
Patterns at Remote 
Control 
 
 
 
 
 
Vane Angle (°) 
90 
65 
77.5 
102.5 
115 
 
12.5  Quiet operation (Cooling Mode/Cooling area of Dry Mode) 
š Purpose 
o
  To provide quiet cooling operation compare to normal operation. 
 
š Control 
condition 
o
  Quiet operation start condition 
ƒ
  When “POWERFUL/QUIET” button at remote control is pressed twice. 
QUIET LED illuminates. 
 
o
  Quiet operation stop condition 
ƒ
  When one of the following conditions is satisfied, quiet operation stops: 
š  POWERFUL/QUIET button is pressed again. 
š  Stop by OFF/ON switch. 
š  Timer “off” activates. 
š  AUTO COMFORT button is pressed. 
š  ECONAVI button is pressed. 
š  Mild Dry Cooling button is pressed. 
ƒ
  When quiet operation is stopped, operation is shifted to normal operation with previous setting. 
ƒ
  When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed. 
ƒ
  When operation mode is changed, quiet operation is shifted to quiet operation of the new mode. 
ƒ
  During quiet operation, if timer “on” activates, quiet operation maintains. 
ƒ
  After off, when on back, quiet operation is not memorised. 
 
š Control 
contents 
o
  Fan speed is changed from normal setting to quiet setting of respective fan speed. 
Fan speed for quiet operation is reduced from setting fan speed. 
 
12.6  Quiet operation (Heating) 
š Purpose 
o
  To provide quiet heating operation compare to normal operation. 
 
š Control 
condition 
o
  Quiet operation start condition 
ƒ
  When “POWERFUL/QUIET” button at remote control is pressed. 
QUIET LED illuminates. 
 
 
 
 
 
38 
o
  Quiet operation stop condition 
ƒ
  When one of the following conditions is satisfied, quiet operation stops: 
š  POWERFUL/QUIET button is pressed again. 
š  Stop by OFF/ON switch. 
š  Timer “off” activates. 
š  AUTO COMFORT button is pressed. 
š  ECONAVI button is pressed. 
š  Mild Dry Cooling button is pressed. 
ƒ
  When quiet operation is stopped, operation is shifted to normal operation with previous setting. 
ƒ
  When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed. 
ƒ
  When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except 
fan mode only. 
ƒ
  During quiet operation, if timer “on” activates, quiet operation maintains. 
ƒ
  After off, when on back, quiet operation is not memorised. 
 
š Control 
contents 
o
  Fan speed manual 
ƒ
  Fan speed is changed from normal setting to quiet setting of respective fan speed. 
ƒ
  Fan speed for quiet operation is reduced from setting fan speed. 
o
  Fan Speed Auto 
ƒ
  Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger. 
 
12.7 Powerful Mode Operation 
š  When the powerful mode is selected, the internal setting temperature will shift lower up to 2°C (for Cooling/Soft 
Dry) or higher up to 3.5°C (for Heating) than remote control setting temperature for 20 minutes to achieve the 
setting temperature quickly. 
 
12.8 Timer Control 
š  There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time. 
š  If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence. 
12.8.1 ON 
Timer 
Control 
š  ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier than 
the setting time. 
This is to provide a comfortable environment when reaching the set ON time. 
š  60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to 
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting 
time. 
š  From the above judgment, the decided operation will start operate earlier than the set time as shown below. 
 
 
 
12.8.2  OFF Timer Control 
OFF timer 1 and OFF timer 2 can be set using remote control, the unit with timer set will stop operate at set time. 
 
39 
12.9 Auto Restart Control 
š  When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within 
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be 
selected randomly) after power supply resumes. 
š  This type of control is not applicable during ON/OFF Timer setting. 
š  This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board. 
 
12.10   Indication Panel 
 
LED POWER  TIMER  POWERFUL QUIET 
nanoe-G 
ECONAVI 
AUTO 
COMFORT 
Color Green  Orange 
Orange  Orange 
Blue Green 
Green 
Light ON 
Operation ON  Timer Setting ON 
POWERFUL Mode 
ON 
QUIET Mode 
ON 
nanoe-G ON ECONAVI ON 
AUTO COMFORT 
ON 
Light OFF 
Operation OFF  Timer Setting OFF 
POWERFUL Mode 
OFF 
QUIET Mode 
OFF 
nanoe-G 
OFF 
ECONAVI OFF 
AUTO COMFORT 
OFF 
 
Note: 
š  If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation 
mode judgment, or ON timer sampling. 
š  If Timer LED is blinking, there is an abnormality operation occurs. 
 
12.11   nanoe-G Operation 
š  This operation provides clean air by producing great amount of negative ions and distribute through the 
discharge airflow to capture or deactivate molds, bacteria or viruses. 
 
š  nanoe-G operation start condition 
o
  During unit running at any operation mode, if nanoe-G operation is activated, combination operation 
(operation mode + nanoe-G operation) starts. 
o
  During unit is OFF, if nanoe-G operation is activated, nanoe-G individual operation starts. 
 
š  nanoe-G operation stop condition 
o
  When OFF/ON button is pressed to stop the operation. 
o
  When nanoe-G button is pressed. 
o
  When OFF Timer activates. 
 
š  nanoe-G operation pause condition 
o
  When indoor fan stop (during deice, odor cut control, thermostat off, etc.). nanoe-G operation resume after 
indoor fan restarts. 
o
  When indoor intake temperature ≥ 40°C. nanoe-G operation resume after indoor intake temperature ≤ 40°C 
continuously for 30 minutes. 
 
š Indoor 
fan 
control 
o
  During any operation mode combines with nanoe-G operation, fan speed follows respective operation mode. 
However, nanoe-G system enabled when fan speed ≥ 500rpm to ensure proper negative ion distribution, 
nanoe-G system disabled when fan speed < 500 rpm. 
o
  During nanoe-G individual operation, only Auto Fan Speed and no Powerful operation is allowed. Even if Fan 
Speed button is pressed, no signal is sent to the unit and no change on remote control display. Auto Fan 
Speed for nanoe-G operation changes from SHi to Hi after 4 hours of operation. 
 
š  Airflow direction control 
o
  During any operation mode combines with nanoe-G operation, airflow direction follows respective operation 
mode. 
o
  During nanoe-G individual operation, only Auto Air Swing is allowed. Even if Air Swing button is pressed, no 
signal is sent to the unit and no change on remote control display. 
 
 
 
 
 
40 
š Timer 
control 
o
  When ON Timer activates when unit stops, previous operation resumes and restored last saved nanoe-G 
operation status. 
o
  When ON Timer activates during any operation, no change on current operation. 
o
  When OFF Timer activates during any operation, all operation stops and the latest nanoe-G operation status 
is saved. 
 
š Indicator 
o
  When nanoe-G starts, nanoe-G indicator ON. 
 
š  Remote Control Receiving Sound 
o
 Normal 
Operation 
 
Î
 nanoe-G Operation   
     : Beep 
o
 Nanoe-G 
Operation   
Î
 Normal Operation 
 
     : Beep 
o
 
 
Stop 
   Î nanoe-G individual Operation      : Beep 
o
  Nanoe-G individual Operation  Î Stop  
 
 
     : Long Beep 
 
š Power 
failure 
o
  During nanoe-G individual operation, if power failure occurs, after power resumes, nanoe-G individual 
operation resumes immediately. 
o
  During combination operation, if power failure occurs, after power resumes, combination operation resume 
immediately. 
 
š nanoe-G 
check 
mode 
o
  To enable nanoe-G check mode, during nanoe-G operation ON: 
 
 
 
o
  If there is abnormal discharge, nanoe-G indicator blinks immediately. 
 
š  Error detection control 
When nanoe-G indicator blinks, it indicates error listed below: 
o
  nanoe-G connector at main PCB open 
ƒ
 Judgment 
method 
š  During nanoe-G operation, nanoe-G connector at main PCB is opened. 
 
 
 
 
Page of 108
Display

Click on the first or last page to see other CS-HE9PKD / CS-HE12PKD / CU-HE9PKD / CU-HE12PKD service manuals if exist.