Panasonic CS-HE9MKD / CU-HE9MKD / CS-HE12MKD / CU-HE12MKD Service Manual ▷ View online
61
15.4.3. H14 (Indoor Intake Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are
used to determine sensor errors.
used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
62
15.4.4. H15 (Compressor Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor
are used to determine sensor errors.
are used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
63
15.4.5. H16 (Outdoor Current Transformer Open Circuit)
Malfunction Decision Conditions
A current transformer (CT) is detected by checking the compressor running frequency ( rated frequency) and CT detected
input current (less than 0.65A) for continuously 20 seconds.
input current (less than 0.65A) for continuously 20 seconds.
Malfunction Caused
• CT defective
• Outdoor PCB defective
• Compressor defective (low compression)
• Outdoor PCB defective
• Compressor defective (low compression)
Troubleshooting
64
15.4.6. H19 (Indoor Fan Motor - DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of
rotation > 2550rpm or < 50rpm)
rotation > 2550rpm or < 50rpm)
Malfunction Caused
• Operation stops due to short circuit inside the fan motor winding.
• Operation stops due to breaking of wire inside the fan motor.
• Operation stops due to breaking of fan motor lead wires.
• Operation stops due to Hall IC malfunction.
• Operation error due to faulty indoor unit PCB.
• Operation stops due to breaking of wire inside the fan motor.
• Operation stops due to breaking of fan motor lead wires.
• Operation stops due to Hall IC malfunction.
• Operation error due to faulty indoor unit PCB.
Troubleshooting