Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CU-YL24HBE5 / CU-YL28HBE5 / CU-YL34HBE5 / CU-YL43HBE5 Simplified Service Manual ▷ View online

33
12. Be sure to leave enough space around the outdoor unit to maintain proper performance and to allow access for routine
maintenance.
• Allow enough space from any obstacles as shown in Fig.1.2 below in order to prevent short-circuits from occurring.
(If installing more than one outdoor unit, make the necessary space available as outlined in 14.)
However, there should be at least 1 meter of free space above the unit.
• The height of any obstacles at the air intake and outlet sides should not be greater than the height of the outdoor unit.
13. If installing more than one outdoor unit, allow enough space around each unit as shown below.
• The distance given above are the minimum distance required in order to maintain proper performance.
Allow as much space as possible in order to get the best performance from the units.
10.1.4.
Transporting And Installing The Outdoor Unit
• Transporting
1. The outdoor unit should be transported in its original packaging as close to the installation location as possible.
2. If suspending the outdoor unit, use a rope or belt, and use cloth or wood as padding in order to avoid damaging the unit.
• Installation
1. Read the “Selecting the outdoor unit installation location” section thoroughly before installing the outdoor unit.
2. If installing the unit to a concrete base or other solid base, use M10 or W3/8 bolts and nuts to secure the unit, and ensure
that the unit is fully upright and level.
(The anchor bolt positions are shown in the diagram at the right side.)
In particular, install the unit at a distance from the
neighbouring building which conforms to regulations
specified by local noise emission regulation
standards.
3. Do not install the outdoor unit to the building’s roof.
4. If there is a possibility that vibration may be
transmitted to the rooms of the building, place rubber
insulation between the unit and the installation
surface.
5. Drain water will be discharged from the outdoor unit
when operating the system in heating or defrosting
modes. Select an installation location which will allow
the water to drain away properly, or provide a
drainage channel so that the water can drain away.
(If this is not done, the drain water may freeze during
winter, or the water may spill down to areas
underneath the installation location.)
Maintain sufficient space above the unit.
34
• If a drain pipe needs to be installed, insert the accessory drain elbow into the mounting hole at the bottom of the outdoor unit, and
connect a hose with an inside diameter of 15mm to this drain elbow.
(The hose is not supplied.)
In cold regions (where the outdoor air temperature can drop to 0°C or below continuously for 2-3 days), the drain water may freeze,
and this may prevent the fan from operating. Do not use the drain elbow in such cases.
10.1.5.
Notes On Reuse Of Existing Refrigerant Piping
• In the circumstances listed below, do not reuse any refrigerant piping. Instead, make sure to install a new piping.
(Reuse is not allowed.)
- Heat insulation is not provided for either liquid-side or gas-side piping or both.
- The existing refrigerant pipe has been left in an open condition.
- The size of the existing refrigerant piping does not meet the applicable size requirement. (Applicable piping size is as
indicated in the table below.)
- The length of the existing refrigerant piping is not within the range of allowable piping length. (Allowable length range is as
indicated in the table below.)
- Branch pipe is used for twin type or branch piping is run on indoor side.
• In the circumstances listed below, do not reuse the refrigerant piping as it is but wash it thoroughly before reusing it.
- Pump down operation cannot be performed for the existing air conditioner.
- The compressor has a failure history.
- Oil is discolored.
- The existing air conditioner is gas/oil heat pump type.
- Refrigerant oil used for the existing air conditioner is other than “ester oil, ethereal oil, ATMOS, SUNISO or H.A.B”.
• Do not reuse the flare to prevent gas leak. Make sure to install a new flare.
• If there is a welded part on the existing refrigerant piping, conduct a gas leak check on the welded part.
• Replace deteriorated heat insulating material with a new one. Heat insulating material is required for both liquid-side and gas-
side piping.
10.1.6.
Refrigerant Piping Size And Allowable Piping Length
1. Refrigerant piping size
• In case of new installation, make sure to use standard piping size.
• In case of reuse of existing piping, the size must be within the range of refrigerant piping size combination as specified in the
above table.
If using the drain elbow, install the outdoor unit on a base which is at least 5cm high.
NOTE
Observe the followings when reusing the existing refrigerant piping.
Inadequate refrigerant piping could result in failure.
Outdoor unit capacity
Liquid-side applicable piping size (mm)
1 size down
Standard
1 size up
YL24, YL28 type
ø6.35 x t0.8
ø9.52 x t0.8
ø12.7 x t0.8
Outdoor unit capacity
Gas-side applicable piping size (mm)
Standard
1 size up
YL24, YL28 type
ø15.88 x t0.8
35
2. Allowable piping length
3. Additional limitations for twin-type
• Maximum allowable one-way piping length is the larger
numerical value between (Lo + La) and (Lo + Lb).
• For twin type, only the main piping can be reused among
the existing piping. Brandnew standard pipe should be
installed for branch pipe/branch piping.
10.1.7.
Connecting The Pipes
• Use a clean pipe which does not include water or dust for inside of piping.
• When cutting the refrigerant pipes, a piping cutter must be used. Before connecting the refrigerant pipes, blow nitrogen and blow
off dust in the pipes.
(Never use tools which cause a lot of dust such as a saw and a magnet.)
• When waxing replace nitrogen inside the piping after removing dirt and dust. (In order to prevent oxidization scale from forming
inside the piping).
• The refrigerant pipes are of particular importance.
The installation work for refrigerant cycles in separate-type air conditioners must be carried out perfectly.
• Set the lower limit of the allowable pipe length to 7.5m.
If the pipe is shorter than 7.5m, the refrigerant may become overfilled and a problem such as abnormal high pressure could
occur.
1. Refer to the table below for the pipe diameters equivalent lengths and indoor/outdoor unit difference of elevation.
Pipe diameter
Gas side
Standard
Liquid side
1 size down
Standard
1 size up
Allowable piping length (min. ~ max.)
7.5m ~ 10m
7.5m ~ 30m
7.5m ~ 15m
Height difference
between indoor and
outdoor unit
Outdoor unit is
located on upper side
5m or less
25m or less
15m or less
Outdoor unit is
located on lower side
5m or less
20m or less
10m or less
Pipe diameter
Gas side
Standard
Liquid side
1 size down
Standard
1 size up
Allowable piping length
Lo + La + Lb
7.5m ~ 10m
7.5m ~ 30m
7.5m ~ 15m
Max. allowable
one-way piping length
Lo + La
Lo + Lb
10m or less
20m or less
10m or less
Branch pipe length
La , Lb
5m or less
10m or less
10m or less
Difference in branch
pipe lengt
La - Lb
3m or less
5m or less
5m or less
Height
difference
H2
Height
difference
between indoor
and outdoor
unit
Outdoor unit is
located on upper side
5m or less
25m or less
15m or less
Outdoor unit is
located on lower side
5m or less
20m or less
10m or less
H1
Height difference between indoor units
0.5m or less
0.5m or less
0.5m or less
Outdoor unit on upper side
Outdoor unit on lower side
Pipe diameter (mm)
Equivalent
length (m)
Difference of
elevation (m)
Difference of
elevation (m)
Liquid-side pipes
Gas-side pipes
ø9.52 x t1.0
ø15.88 x t1.2
30
25
20
36
2. CUTTING AND FLARING THE PIPING.
a. Please cut using pipe cutter and then remove the burrs.
b. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to
avoid the metal powder entering the pipe.
c. Please make flare after inserting the flare nut onto the copper pipes.
3. Notes when connecting the refrigerant pipes.
• Use clean copper, pipes with no water or dust on the insides.
• Use phosphorus-free, unjointed copper pipes for the refrigerant pipes.
• If it is necessary to cut the refrigerant pipes, be sure to use a pipe cutter, and use compressed nitrogen or an air blower to
clean out any foreign particles from inside the pipe.
• Be careful not to let any dust, foreign materials or water get inside the pipes during connection.
• If bending the pipes, allow as large a bending radius as possible. Do not flex the pipes any more than necessary.
• If joining pipe ends, do so before tightening the flare nut.
• Always blow the pipe end with nitrogen while joining pipe ends.
(This will prevent any oxide scaling from occurring inside the pipe.)
• If using long pipe lengths with several joined pipe ends, insert strainers inside the pipes.(Strainers are not supplied.)
• When tightening the flare nuts, coat the flares (both inside surfaces) with a small amount of refrigerator oil, and screw in
about 3-4 turns at first by hand.
• Refer to the following table for the tightening torques. Be sure to use two spanners to tighten.
(If the nuts are overtightened, it may cause the flares to break or leak.)
4. After piping connection has been completed, make sure that the joint areas of the indoor and outdoor units are free from gas
leakage by the use of nitrogen, etc.
5. Air purge within connection piping shall be carried out by evacuation.
10.1.8.
Heat Insulation
Charging With Refrigerant
• At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30m. If the
equivalent pipe length used will be 20m or less, no additional charging will be necessary.
- For standard type
Flare nut fastening torque N•m {kgf•cm}
ø6.35mm
18 (180)
ø15.88mm
65 (660)
ø9.52mm
42 (430)
ø19.05mm
100 (1020)
ø12.7mm
55 (560)
Use a material with good heat-resistant
properties as the heat insulation for the pipes.
Be sure to insulate both the gas-side and
liquid-side pipes. If the pipes are not
adequately insulated, condensation or water
leakages may occur.
Liquid-side pipes
Material that can
withstand 120
°C or
higher
Gas-side pipes
Equivalent length
Minimum length
30m
7.5m
Page of 113