Panasonic CS-E9PD3EA / CS-E12PD3EA / CU-E9PD3EA / CU-E12PD3EA Service Manual ▷ View online
9
MODEL
INDOOR CS-E12PD3EA
OUTDOOR
CU-E12PD3EA
Indoor Fan
Type
Sirocco
Material
ABS
Motor Type
DC Motor (8-poles)
Output Power
W
30
Speed
QLo
Cool rpm
980
Heat rpm
1020
Lo
Cool rpm
1050
Heat rpm
1100
Me
Cool rpm
1170
Heat rpm
1250
Hi
Cool rpm
1300
Heat rpm
1400
SHi
Cool rpm
1380
Heat rpm
1450
Outdoo
r Fa
n
Type
Propeller
Fan
Material
PP
Motor Type
DC (8-poles)
Output Power
W
40
Speed Hi
Cool rpm
620
Heat rpm
560
Moisture Removal
L/h (Pt/h)
2.0 (4.2)
Indoor Airflow
QLo
Cool m
3
/min (ft
3
/min) 5.6
(198)
Heat m
3
/min (ft
3
/min) 6.3
(222)
Lo
Cool m
3
/min (ft
3
/min) 6.4
(226)
Heat m
3
/min (ft
3
/min) 7.2
(254)
Me
Cool m
3
/min (ft
3
/min) 7.6
(268)
Heat m
3
/min (ft
3
/min) 8.8
(311)
Hi
Cool m
3
/min (ft
3
/min) 9.0
(320)
Heat m
3
/min (ft
3
/min) 10.5
(370)
SHi
Cool m
3
/min (ft
3
/min) 9.8
(346)
Heat m
3
/min (ft
3
/min) 11.0
(388)
Outdoor Airflow
Hi
Cool m
3
/min (ft
3
/min) 34.2
(1205)
Heat m
3
/min (ft
3
/min) 30.6
(1080)
Refrigeration
Cycle
Control Device
Expansion Valve
Refrigerant Oil
cm
3
FV50S
(450)
Refrigerant Type
g (oz)
R410A, 1.14k (40.2)
Dimension
Height (I/D / O/D)
mm (inch)
285 (11-1/4) / 695 (27-3/8)
Width (I/D / O/D)
mm (inch)
750 (29-17/32) / 875 (34-15/32)
Depth (I/D / O/D)
mm (inch)
370 (14-19/32) / 320 (12-5/8)
Weight
Net (I/D / O/D)
kg (lb)
18 (40) / 45 (99)
Piping
Pipe Diameter (Liquid / Gas)
mm (inch)
6.35 (1/4) / 9.52 (3/8)
Standard Length
m (ft)
5.0 (16.4)
Length Range (min - max)
m (ft)
3 (9.8) ~ 20 (65.6)
I/D & O/D Height Different
m (ft)
15 (49.2)
Additional Gas Amount
g/m (oz/ft)
20 (0.2)
Length for Additional Gas
m (ft)
7.5 (24.6)
Drain Hose
Inner Diameter
mm
14
Length mm
255
10
MODEL
INDOOR CS-E12PD3EA
OUTDOOR
CU-E12PD3EA
Indoor Heat
Exchanger
Fin Material
Aluminium (Pre Coat)
Fin Type
Slit Fin
Row x Stage x FPI
3 x 12 x 18
Size (W x H x L)
mm
620 x 252 x 38.1
Outdoor Heat
Exchanger
Fin Material
Aluminium
Fin Type
Corrugated Fin
Row x Stage x FPI
2 x 31 x 17
Size (W x H x L)
mm
36.4 x 651 x 640
Power Supply
Outdoor Power Supply
Power Supply Cord
A
Nil
Thermostat
Electronic
Control
Protection Device
Electronic Control
Dry Bulb
Wet Bulb
Indoor
Operation
Range
Cooling
Maximum °C
32
23
Minimum °C
16
11
Heating
Maximum °C
30
-
Minimum °C
16
-
Outdoor
Operation
Range
Cooling
Maximum °C
43
26
Minimum °C
-10
-
Heating
Maximum °C
24
18
Minimum °C
-10
-
1.
Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
2.
Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb
(44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
(44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
3 Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C
4 Heating extreme low temperature capacity, Input Power and COP measured at 230 V indoor temperature 20°C, outdoor -7/-8°C
5
Standby power consumption ≤0.7W (when switched OFF by remote control, except under self protection control).
6
Specifications are subjected to change without notice for further improvement.
11
Multi Split Combination Possibility:
o
A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E15PBE, CU-2E18PBE.
o
A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E18PBE.
o
A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE.
o
A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E27PBE.
o
A single outdoor unit enables air conditioning of up to five separate rooms for CU-5E34PBE.
CONNECTABLE
INDOOR UNIT
OUTDOOR UNIT
CU-2E15PBE
CU-2E18PBE
CU-3E18PBE CU-4E23PBE
Type/ROOM
A B A B A B C A B
C
D
Wall
1.6kW CS-ME5PKE
●
●
●
●
●
●
●
●
●
●
●
2.0kW
CS-E7PKEW
CS-XE7PKEW
CS-XE7PKEW
●
●
●
●
●
●
●
●
●
●
●
2.5kW
CS-E9PKEW
CS-XE9PKEW
CS-ME9PD3EA
CS-ME9PB4EA
CS-E9GFEW
CS-E9GFEW-2
CS-E9PD3EA
CS-XE9PKEW
CS-ME9PD3EA
CS-ME9PB4EA
CS-E9GFEW
CS-E9GFEW-2
CS-E9PD3EA
●
●
●
●
●
●
●
●
●
●
●
3.2kW
CS-E12PKEW
CS-XE12PKEW
CS-ME12PD3EA
CS-ME12PB4EA
CS-E12GFEW
CS-E12GFEW-2
CS-E12PD3EA
CS-XE12PKEW
CS-ME12PD3EA
CS-ME12PB4EA
CS-E12GFEW
CS-E12GFEW-2
CS-E12PD3EA
●
●
●
●
●
●
●
●
●
●
●
4.0kW
CS-E15PKEW
CS-XE15PKEW
CS-XE15PKEW
– – – – ●
●
●
●
●
●
●
5.0kW
CS-E18PKEW
CS-XE18PKEW
CS-ME18PD3EA
CS-ME18PB4EA
CS-E18GFEW
CS-E18GFEW-2
CS-XE18PKEW
CS-ME18PD3EA
CS-ME18PB4EA
CS-E18GFEW
CS-E18GFEW-2
– – – – ●
●
●
●
●
●
●
6.0kW
CS-E21PKEW
CS-XE21PKEW
CS-ME21PB4EA
CS-XE21PKEW
CS-ME21PB4EA
– – – – – – – ●
●
●
●
Capacity range of connectable
indoor units
From 3.2kW
to 5.6kW
From 3.2kW
to 6.4kW
From 4.5kW
to 9.0kW
From 4.5kW
to 11.0 kW
Pipe length
1 room maximum
pipe length (m)
20 20 25
25
Allowable elevation (m)
10
10
15
15
Total allowable pipe
length (m)
30 30 50
60
Total pipe length for
maximum chargeless
length (m)
20 20 30
30
Additional gas
amount over
chargeless length (g/m)
15 15 20
20
Note: “●” : Available
Remarks for CU-2E15PBE / CU-2E18PBE
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-2E15PBE.
(Total nominal capacity of indoor units is between 3.2kW to 5.6kW)
1) Two CS-E7PKEW only (Total nominal cooling capacity is 4.0kW)
2) One CS-E7PKEW and one CS-E9PKEW. (Total nominal cooling capacity is 4.5kW)
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-2E15PBE.
(Total nominal capacity of indoor units is between 3.2kW to 5.6kW)
1) Two CS-E7PKEW only (Total nominal cooling capacity is 4.0kW)
2) One CS-E7PKEW and one CS-E9PKEW. (Total nominal cooling capacity is 4.5kW)
Remarks for CU-3E18PBE / CU-4E23PBE
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-3E18PBE.
(Total nominal capacity of indoor units is between 4.5kW to 9.0kW)
1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW)
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-3E18PBE.
(Total nominal capacity of indoor units is between 4.5kW to 9.0kW)
1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW)
2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW)
12
CONNECTABLE
INDOOR UNIT
OUTDOOR UNIT
CU-4E27PBE CU-5E34PBE
Type/ROOM
A B C D A B C D E
Wall
2.0kW
CS-E7PKEW
CS-XE7PKEW
CS-XE7PKEW
●
●
●
●
●
●
●
●
●
2.5kW
CS-E9PKEW
CS-XE9PKEW
CS-ME9PD3EA
CS-ME9PB4EA
CS-E9GFEW
CS-E9GFEW-2
CS-E9PD3EA
CS-XE9PKEW
CS-ME9PD3EA
CS-ME9PB4EA
CS-E9GFEW
CS-E9GFEW-2
CS-E9PD3EA
●
●
●
●
●
●
●
●
●
3.2kW
CS-E12PKEW
CS-XE12PKEW
CS-ME12PD3EA
CS-ME12PB4EA
CS-E12GFEW
CS-E12GFEW-2
CS-E12PD3EA
CS-XE12PKEW
CS-ME12PD3EA
CS-ME12PB4EA
CS-E12GFEW
CS-E12GFEW-2
CS-E12PD3EA
●
●
●
●
●
●
●
●
●
4.0kW
CS-E15PKEW
CS-XE15PKEW
CS-XE15PKEW
●
●
●
●
●
●
●
●
●
5.0kW
CS-E18PKEW
CS-XE18PKEW
CS-ME18PD3EA
CS-ME18PB4EA
CS-E18GFEW
CS-E18GFEW-2
CS-XE18PKEW
CS-ME18PD3EA
CS-ME18PB4EA
CS-E18GFEW
CS-E18GFEW-2
●
●
●
●
●
●
●
●
●
6.0kW
CS-E21PKEW
CS-XE21PKEW
CS-ME21PB4EA
CS-XE21PKEW
CS-ME21PB4EA
●
●
●
●
●
●
●
●
●
7.0kW CS-E24PKEW
●
●
●
●
●
●
●
●
●
Capacity range of connectable
indoor units
From 4.5kW
to 13.6kW
From 4.5kW
to 17.5 kW
Pipe length
1 room maximum
pipe length (m)
25 25
Allowable elevation (m)
15
15
Total allowable pipe
length (m)
70 80
Total pipe length for
maximum chargeless
length (m)
45 45
Additional gas
amount over
chargeless length (g/m)
20 20
Note: “●” : Available
Remarks for CU-4E27PBE / CU-5E34PBE
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-4E27PBE.
(Total nominal capacity of indoor units is between 4.5kW to 13.6kW)
1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW)
2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW)
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-4E27PBE.
(Total nominal capacity of indoor units is between 4.5kW to 13.6kW)
1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW)
2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW)
Click on the first or last page to see other CS-E9PD3EA / CS-E12PD3EA / CU-E9PD3EA / CU-E12PD3EA service manuals if exist.