MODEL 
INDOOR CS-E12PD3EA 
OUTDOOR 
CU-E12PD3EA 
Indoor Fan
 
Type  
Sirocco 
Material  
ABS 
Motor Type 
 
DC Motor (8-poles) 
Output Power 
30 
Speed 
QLo 
Cool rpm 
980 
Heat rpm 
1020 
Lo 
Cool rpm 
1050 
Heat rpm 
1100 
Me 
Cool rpm 
1170 
Heat rpm 
1250 
Hi 
Cool rpm 
1300 
Heat rpm 
1400 
SHi 
Cool rpm 
1380 
Heat rpm 
1450 
Outdoo
r Fa
n
 
Type  
Propeller 
Fan 
Material  
PP 
Motor Type 
 
DC (8-poles) 
Output Power 
40 
Speed Hi 
Cool rpm 
620 
Heat rpm 
560 
Moisture Removal 
L/h (Pt/h) 
2.0 (4.2) 
Indoor Airflow 
QLo 
Cool m
3
/min (ft
3
/min) 5.6 
(198) 
Heat m
3
/min (ft
3
/min) 6.3 
(222) 
Lo 
Cool m
3
/min (ft
3
/min) 6.4 
(226) 
Heat m
3
/min (ft
3
/min) 7.2 
(254) 
Me 
Cool m
3
/min (ft
3
/min) 7.6 
(268) 
Heat m
3
/min (ft
3
/min) 8.8 
(311) 
Hi 
Cool m
3
/min (ft
3
/min) 9.0 
(320) 
Heat m
3
/min (ft
3
/min) 10.5 
(370) 
SHi 
Cool m
3
/min (ft
3
/min) 9.8 
(346) 
Heat m
3
/min (ft
3
/min) 11.0 
(388) 
Outdoor Airflow 
Hi 
Cool m
3
/min (ft
3
/min) 34.2 
(1205) 
Heat m
3
/min (ft
3
/min) 30.6 
(1080) 
Refrigeration 
Cycle 
Control Device 
 
Expansion Valve 
Refrigerant Oil 
cm
3
 FV50S 
(450) 
Refrigerant Type 
g (oz) 
R410A, 1.14k (40.2) 
Dimension 
Height (I/D / O/D) 
mm (inch) 
285 (11-1/4) / 695 (27-3/8) 
Width (I/D / O/D) 
mm (inch) 
750 (29-17/32) / 875 (34-15/32) 
Depth (I/D / O/D) 
mm (inch) 
370 (14-19/32) / 320 (12-5/8) 
Weight 
Net (I/D / O/D) 
kg (lb) 
18 (40) / 45 (99) 
Piping 
Pipe Diameter (Liquid / Gas) 
mm (inch) 
6.35 (1/4) / 9.52 (3/8) 
Standard Length 
m (ft) 
5.0 (16.4) 
Length Range (min - max) 
m (ft) 
3 (9.8) ~ 20 (65.6) 
I/D & O/D Height Different 
m (ft) 
15 (49.2) 
Additional Gas Amount 
g/m (oz/ft) 
20 (0.2) 
Length for Additional Gas 
m (ft) 
7.5 (24.6) 
Drain Hose 
Inner Diameter 
mm  
14 
Length mm 
255 
10 
MODEL 
INDOOR CS-E12PD3EA 
OUTDOOR 
CU-E12PD3EA 
Indoor Heat 
Exchanger 
Fin Material 
 
Aluminium (Pre Coat) 
Fin Type 
 
Slit Fin 
Row x Stage x FPI 
 
3 x 12 x 18 
Size (W x H x L) 
mm 
620 x 252 x 38.1 
Outdoor Heat 
Exchanger 
Fin Material 
 
Aluminium 
Fin Type 
 
Corrugated Fin 
Row x Stage x FPI 
 
2 x 31 x 17 
Size (W x H x L) 
mm 
36.4 x 651 x 640 
Power Supply 
 
Outdoor Power Supply 
Power Supply Cord 
Nil 
Thermostat  
Electronic 
Control 
Protection Device 
 
Electronic Control 
 
Dry Bulb 
Wet Bulb 
Indoor 
Operation 
Range 
Cooling 
Maximum °C 
32 
23 
Minimum °C 
16 
11 
Heating 
Maximum °C 
30 
Minimum °C 
16 
Outdoor 
Operation 
Range 
Cooling 
Maximum °C 
43 
26 
Minimum °C 
-10 
Heating 
Maximum °C 
24 
18 
Minimum °C 
-10 
 
1. 
Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air 
temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb) 
2. 
Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb 
(44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb) 
3  Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C 
4  Heating extreme low temperature capacity, Input Power and COP measured at 230 V indoor temperature 20°C, outdoor -7/-8°C 
Standby power consumption ≤0.7W (when switched OFF by remote control, except under self protection control). 
Specifications are subjected to change without notice for further improvement. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
11 
  Multi Split Combination Possibility: 
o
  A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E15PBE, CU-2E18PBE. 
o
  A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E18PBE. 
o
  A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE. 
o
  A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E27PBE. 
o
  A single outdoor unit enables air conditioning of up to five separate rooms for CU-5E34PBE. 
 
CONNECTABLE 
INDOOR UNIT 
OUTDOOR UNIT 
CU-2E15PBE
CU-2E18PBE
CU-3E18PBE CU-4E23PBE 
Type/ROOM 
A B A B A B C A B 
Wall
 
1.6kW CS-ME5PKE 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.0kW 
CS-E7PKEW 
CS-XE7PKEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.5kW 
CS-E9PKEW 
CS-XE9PKEW 
CS-ME9PD3EA 
CS-ME9PB4EA 
CS-E9GFEW 
CS-E9GFEW-2 
CS-E9PD3EA 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
3.2kW 
CS-E12PKEW 
CS-XE12PKEW 
CS-ME12PD3EA 
CS-ME12PB4EA 
CS-E12GFEW 
CS-E12GFEW-2 
CS-E12PD3EA 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
4.0kW 
CS-E15PKEW 
CS-XE15PKEW 
– – – – ● 
● 
● 
● 
● 
● 
● 
5.0kW 
CS-E18PKEW 
CS-XE18PKEW 
CS-ME18PD3EA 
CS-ME18PB4EA 
CS-E18GFEW 
CS-E18GFEW-2 
– – – – ● 
● 
● 
● 
● 
● 
● 
6.0kW 
CS-E21PKEW 
CS-XE21PKEW 
CS-ME21PB4EA 
– – – – – – – ● 
● 
● 
● 
Capacity range of connectable 
indoor units 
From 3.2kW
to 5.6kW 
From 3.2kW
to 6.4kW 
From 4.5kW 
to 9.0kW 
From 4.5kW 
to 11.0 kW 
Pipe length 
1 room maximum  
pipe length (m) 
20 20  25 
25 
Allowable elevation (m) 
10 
10 
15 
15 
Total allowable pipe 
length (m) 
30 30  50 
60 
Total pipe length for 
maximum chargeless 
length (m) 
20 20  30 
30 
Additional gas 
amount over 
chargeless length (g/m) 
15 15  20 
20 
Note: “●” : Available
Remarks for CU-2E15PBE / CU-2E18PBE 
1. At least two indoor units must be connected. 
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within 
    connectable capacity range of indoor unit. (as shown in the table above) 
    Example: The indoor units’ combination below is possible to connect to CU-2E15PBE. 
    (Total nominal capacity of indoor units is between 3.2kW to 5.6kW) 
    1) Two CS-E7PKEW only (Total nominal cooling capacity is 4.0kW) 
    2) One CS-E7PKEW and one CS-E9PKEW. (Total nominal cooling capacity is 4.5kW) 
Remarks for CU-3E18PBE / CU-4E23PBE 
1. At least two indoor units must be connected. 
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within 
    connectable capacity range of indoor unit. (as shown in the table above) 
    Example: The indoor units’ combination below is possible to connect to CU-3E18PBE. 
    (Total nominal capacity of indoor units is between 4.5kW to 9.0kW) 
    1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW) 
     2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW) 
 
 
 
 
 
12 
CONNECTABLE 
INDOOR UNIT 
OUTDOOR UNIT 
CU-4E27PBE CU-5E34PBE 
Type/ROOM 
A B C D A B C D E 
Wall
 
2.0kW 
CS-E7PKEW 
CS-XE7PKEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.5kW 
CS-E9PKEW 
CS-XE9PKEW 
CS-ME9PD3EA 
CS-ME9PB4EA 
CS-E9GFEW 
CS-E9GFEW-2 
CS-E9PD3EA 
● 
● 
● 
● 
● 
● 
● 
● 
● 
3.2kW 
CS-E12PKEW 
CS-XE12PKEW 
CS-ME12PD3EA 
CS-ME12PB4EA 
CS-E12GFEW 
CS-E12GFEW-2 
CS-E12PD3EA 
● 
● 
● 
● 
● 
● 
● 
● 
● 
4.0kW 
CS-E15PKEW 
CS-XE15PKEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
5.0kW 
CS-E18PKEW 
CS-XE18PKEW 
CS-ME18PD3EA 
CS-ME18PB4EA 
CS-E18GFEW 
CS-E18GFEW-2 
● 
● 
● 
● 
● 
● 
● 
● 
● 
6.0kW 
CS-E21PKEW 
CS-XE21PKEW 
CS-ME21PB4EA 
● 
● 
● 
● 
● 
● 
● 
● 
● 
7.0kW CS-E24PKEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
Capacity range of connectable 
indoor units 
From 4.5kW 
to 13.6kW 
From 4.5kW 
to 17.5 kW 
Pipe length 
1 room maximum  
pipe length (m) 
25 25 
Allowable elevation (m) 
15 
15 
Total allowable pipe 
length (m) 
70 80 
Total pipe length for 
maximum chargeless 
length (m) 
45 45 
Additional gas 
amount over 
chargeless length (g/m) 
20 20 
Note: “●” : Available 
Remarks for CU-4E27PBE / CU-5E34PBE 
1. At least two indoor units must be connected. 
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within 
    connectable capacity range of indoor unit. (as shown in the table above) 
    Example: The indoor units’ combination below is possible to connect to CU-4E27PBE. 
    (Total nominal capacity of indoor units is between 4.5kW to 13.6kW) 
    1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW) 
    2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 