8.1.9.1. Vertical Airflow
Operation Mode
Airflow Direction
Vane Angle (°)
1
2
3
4
5
Heating
Auto with Heat Exchanger
A
Upward fix
3
Temperature
B
Downward fix
64
C
Upward fix
3
D
Downward fix
3
Manual
3
17
33
49
63
Cooling, Soft Dry and Ion
Auto
8 ~ 36
Manual
8
15
22
30
36
Mode Judgment in Auto
Auto
8
Manual
8
15
22
30
36
 1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.
 2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions
of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close position.
8.1.9.2. Horizontal Airflow
 1. Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as stated
below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below.
Operation Mode
Vane Angle (°)
Heating, with heat exchanger temperature
A
65 ~ 115
B
90
Cooling, Soft Dry and Ion
65 ~ 115
 2. Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the positions
of the vane are as Figure 2 above.
Pattern
1
2
3
4
5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)
90
65
78
102
115
29
CS-E9DKDW CU-E9DKD / CS-E12DKDW CU-E12DKD
8.1.10. Quiet operation (Cooling Mode/Cooling area of Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
  • When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Powerful button is pressed.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. Quiet button is pressed again.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
C. Control contents
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -1 step from setting fan speed.
8.1.10.1. Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
  • When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Powerful button is pressed.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. Quiet button is pressed again.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
30
CS-E9DKDW CU-E9DKD / CS-E12DKDW CU-E12DKD
C. Control contents
a. Fan Speed manual
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -1 step from setting fan speed.
 3. Fan Speed Auto
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.
8.1.11. Powerful Mode Operation
When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature quickly.
(a) Cooling Operation
(b) Soft Dry Operation
(c) Heating Operation
8.1.12. Delay ON Timer Control
Delay ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to
provide a comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine the
indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
31
CS-E9DKDW CU-E9DKD / CS-E12DKDW CU-E12DKD
8.1.13. Delay OFF Timer Control
Delay OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
8.1.14.  Auto Restart Control
 1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power
supply resumes.
 2. This type of control is not applicable during ON/OFF Timer setting.
8.1.15. Indication Panel
LED
POWER
TIMER
QUIET
POWERFUL
ION
ALLERGEN
BUSTER
Color
Green
Orange
Orange
Orange
Green
Blue
Light ON
Operation ON
Timer Setting ON
Quiet Mode ON
Powerful Mode ON
Ion Mode ON
Operation ON
Light OFF
Operation OFF
Timer Setting OFF
Quiet Mode OFF
Powerful Mode OFF
Ion Mode OFF
Operation OFF
Note:
  • If POWER LED is blinking, the possible operations of the unit are Hot Start, during Deice operation, operation mode
judgment, or delay ON timer sampling.
  • If Timer LED is blinking, there is an abnormality operation occurs.
  • If Ionizer, LED is blinking, there is an abnormality of Ionizer occurs.
8.1.16.  Auto Operation Switch
32
CS-E9DKDW CU-E9DKD / CS-E12DKDW CU-E12DKD