16.4.19. H98 (Indoor High Pressure Protection)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Decision Conditions
During heating operation, the temperature detected by the indoor pipe temperature sensor is above 60
C.
Malfunction Caused
• Air short circuit at indoor unit
• Clogged indoor unit air filter
• Dust accumulation on the indoor unit heat exchanger
• 2/3 way valve closed
• Faulty indoor unit fan motor
• Excessive refrigerant
• Clogged expansion valve or strainer
• Faulty indoor pipe temperature sensor
• Faulty indoor unit PCB
• Clogged indoor unit air filter
• Dust accumulation on the indoor unit heat exchanger
• 2/3 way valve closed
• Faulty indoor unit fan motor
• Excessive refrigerant
• Clogged expansion valve or strainer
• Faulty indoor pipe temperature sensor
• Faulty indoor unit PCB
Troubleshooting
98
16.4.20. H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error code will not display (no TIMER LED blinking) but store in EEPROM
Malfunction Decision Conditions
Freeze prevention control takes place (when indoor pipe temperature is lower than 2
C)
Malfunction Caused
• Air short circuit at indoor unit
• Clogged indoor unit air filter
• Dust accumulation on the indoor unit heat exchanger
• 2/3 way valve closed
• Faulty indoor unit fan motor
• Refrigerant shortage (refrigerant leakage)
• Clogged expansion valve or strainer
• Faulty indoor pipe temperature sensor
• Faulty indoor unit PCB
• Clogged indoor unit air filter
• Dust accumulation on the indoor unit heat exchanger
• 2/3 way valve closed
• Faulty indoor unit fan motor
• Refrigerant shortage (refrigerant leakage)
• Clogged expansion valve or strainer
• Faulty indoor pipe temperature sensor
• Faulty indoor unit PCB
Troubleshooting
99
16.4.21. F11 (4-way valve Abnormality)
Malfunction Decision Conditions
• When heating operation, when indoor pipe temperature is below 10
C
• When cooling operation, when indoor pipe temperature is above 45
C
Malfunction Caused
• Connector in poor contact
• Faulty sensor
• Faulty outdoor unit PCB
• 4-way valve defective
• Faulty sensor
• Faulty outdoor unit PCB
• 4-way valve defective
Troubleshooting
100
16.4.22. F17 (Indoor Standby Units Freezing Abnormality)
Malfunction Decision Conditions
• When the different between indoor intake air temperature and indoor pipe temperature is above 10
C or indoor pipe temperature
is below -1.0
C
Remark:
When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to
other indoor unit(s).
When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to
other indoor unit(s).
Malfunction Caused
• Wrong wiring connection
• Faulty sensor
• Faulty expansion valve
• Faulty sensor
• Faulty expansion valve
Troubleshooting