13.3. Remote Control Button
13.3.1.
SET BUTTON
• To check current remote control transmission code
- Press for more than 10 seconds.
• To change the air quality sensor sensitivity
- Press and release with pointer.
- Press the Timer Decrement button to select sensitivity:
1. Low Sensitivity
2. Standard (Default)
3. Hi Sensitivity
- Confirm setting by pressing Timer Set button, a “Beep” sound will be heard. LCD returns to original display after 2 seconds.
- LCD returns to original display if remote control does not operate for 30 seconds.
13.3.2.
CLOCK BUTTON
• To change the remote control’s time format
- Press for more than 5 seconds.
13.3.3.
RESET (RC)
• To clear and restore the remote control setting to factory default
- Press once to clear the memory.
13.3.4.
RESET (AC)
• To restore the unit’s setting to factory default
- Press once to restore the unit’s setting.
13.3.5.
TIMER 
• To change indoor unit indicator’s LED intensity
- Press continuously for 5 seconds.
13.3.6.
TIMER 
• To change remote control display from Degree Celsius to Degree Fahrenheit.
- Press continuously for 10 seconds.
Remote Control Printed Circuit Board
Jumper A (J-A)
Jumper B (J-B)
Remote Control No.
Short
Open
A (Default)
Open
Open
B
Short
Short
C
Open
Short
D
46
14 Troubleshooting Guide
14.1. Refrigeration Cycle System
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table on the right.
47
14.1.1.
Relationship between the condition of the air conditioner and pressure and electric
current
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
Cooling Mode
Heating Mode
 
Low Pressure
High Pressure
Electric current 
during operating
Low Pressure
High Pressure
Electric current 
during operating
Condition of the air 
conditioner
Insufficient refrigerant 
(gas leakage)
Clogged capillary tube 
or Strainer
Short circuit in the      
indoor unit
Heat radiation deficiency   
of the outdoor unit
Inefficient compression
48
14.2. Breakdown Self Diagnosis Function
14.2.1.
Self Diagnosis Function (Three Digits Alphanumeric Code)
• Once abnormality has occurred during operation, the unit
will stop its operation, and Timer LED blinks.
• Although Timer LED goes off when power supply is turned
off, if the unit is operated under a breakdown condition, the
LED will light up again.
• In operation after breakdown repair, the Timer LED will no
more blink. The last error code (abnormality) will be stored in
IC memory.
• To make a diagnosis
1. Timer LED start to blink and the unit automatically stops
the operation.
2. Press the CHECK button on the remote controller
contiguously for 5 seconds.
3. “- -” will be displayed on the remote controller display.
Note: Display only for “- -”. (No transmitting signal, no
receiving sound and no Power LED blinking.)
4. Press the “TIMER”   or   button on the remote
controller. The code “H00” (no abnormality) will be
displayed and signal will be transmitted to the main unit.
5. Every press of the button (up or down) will increase
abnormality numbers and transmit abnormality code
signal to the main unit.
6. When the latest abnormality code on the main unit and
code transmitted from the remote controller are matched,
power LED will light up for 30 seconds and a beep sound
(continuously for 4 seconds) will be heard. If no codes are
matched, power LED will light up for 0.5 seconds and no
sound will be heard.
7. The breakdown diagnosis mode will be canceled unless
pressing the CHECK button continuously for 5 seconds or
operating the unit for 30 seconds.
8. The LED will be off if the unit is turned off or the RESET
button on the main unit is pressed.
• To display memorized error (Protective operation)
status
1. Turn power on.
2. Press the CHECK button on the remote controller
contiguously for 5 seconds.
3. “- -” will be displayed on the remote controller display.
Note: Display only for “- -”. (No transmitting signal, no
receiving sound and no Power LED blinking.)
4. Press the “TIMER”   or   button on the remote
controller. The code “H00” (no abnormality) will be
displayed and signal will be transmitted to the main unit.
The power LED lights up. If no abnormality is stored in the
memory, three beeps sound will be heard.
5. Every press of the button (up or down) will increase
abnormality numbers and transmit abnormality code
signal to the main unit.
6. When the latest abnormality code on the main unit and
code transmitted from the remote controller are matched,
power LED will light up for 30 seconds and a beep sound
(continuously for 4 seconds) will be heard. If no codes are
matched, power LED will light up for 0.5 seconds and no
sound will be heard.
7. The breakdown diagnosis mode will be canceled unless
pressing the CHECK button continuously for 5 seconds or
operating the unit for 30 seconds.
8. The same diagnosis can be repeated by turning power on
again.
• To clear memorized error (Protective operation) status
after repair:
1. Turn power on.
2. Press the AUTO button for 5 seconds (A beep receiving
sound) on the main unit to operate the unit at Forced
Cooling Operation modes.
3. Press the CHECK button on the remote controller for
about 1 second with a pointed object to transmit signal to
main unit. A beep sound is heard from main unit and the
data is cleared.
• Temporary Operation (Depending on breakdown status)
1. Press the AUTO button (A beep receiving sound) on the
main unit to operate the unit. (Remote control will become
possible.)
2. The unit can temporarily be used until repaired.
Error Code
Operation
Temporary items
H23
Cooling
Emergency Operation
with limited power
H27, H28
Cooling, Heating