49
13.3. Protection Control For Heating Operation
13.3.1.
Intake Air Temperature Control
Compressor will operate at limited frequency if indoor intake air temperature is 30
qC or above.
13.3.2.
Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14
qC in order to avoid compressor
overloading.
13.3.3.
Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
13.3.4.
Cold Draught Prevention Control
When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
13.3.5.
Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor and outdoor fan
motor stop and operation LED blinks.
50
14 Servicing Mode
14.1. Auto OFF/ON Button
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be used to
operate air conditioner with limited function if remote control is misplaced or malfunction.
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds. A “beep”
sound will occur at the fifth seconds, in order to identify the starting of Test Run operation (Forced cooling operation). Within 5
minutes after Forced cooling operation start, the Auto OFF/ON button is pressed for more than 5 seconds. A 2 “beep” sounds
will occur at the fifth seconds, in order to identify the starting of Forced heating operation.
The Auto OFF/ON button may be used together with remote control to set / change the advance setting of air conditioner
operation.
3. REMOTE CONTROL NUMBER SWITCH MODE
The Remote Control Number Switch Mode will be activated if the Auto OFF/ON button is pressed continuously for more than
11 seconds (3 “beep” sounds will occur at 11th seconds to identify the Remote Control Number Switch Mode is in standby
condition) and press “AC RESET” button and then press any button at remote control to transmit and store the desired
transmission code to the EEPROM.
There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor unit. The indoor
unit will only operate when received signal with same transmission code from remote control. This could prevent signal
interference when there are 2 or more indoor units installed nearby together.
To change remote control transmission code, short or open jumpers at the remote control printed circuit board
Remote Control Printed Circuit Board
Jumper A (J-A)
Jumper B (J-B)
Remote Control No.
Short
Open
A (Default)
Open
Open
B
Short
Short
C
Open
Short
D
51
4. REMOTE CONTROL RECEIVING SOUND OFF/ON MODE
The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for
more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound Off/On
Mode is in standby condition) and press “AC Reset” button and then press “Check” button at remote control.
Press “Auto OFF/ON button” to toggle remote control receiving sound.
- Short “beep”: Turn OFF remote control receiving sound.
- Long “beep”: Turn ON remote control receiving sound.
After Auto OFF/ON Button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON Mode is
restarted.
14.2. Remote Control Button
14.2.1.
SET BUTTON
• To check remote control transmission code and store the transmission code to EEPROM.
- Press “SET” button for more than 10 seconds by using pointer.
- Press “TMER SET” button until a “beep” sound is heard as confirmation of transmission code change.
• To change the air quality sensor sensitivity
- Press and release by using pointer.
- Press the Timer Decrement button to select sensitivity:
1. Low Sensitivity
2. Standard (Default)
3. Hi Sensitivity
- Confirm setting by pressing Timer Set button, a “Beep” sound will be heard. LCD returns to original display after 2 seconds.
- LCD returns to original display if remote control does not operate for 30 seconds.
14.2.2.
CLOCK BUTTON
• To change the remote control’s time format
- Press for more than 5 seconds.
14.2.3.
RESET (RC)
• To clear and restore the remote control setting to factory default
- Press once to clear the memory.
14.2.4.
RESET (AC)
• To restore the unit’s setting to factory default
- Press once to restore the unit’s setting.
14.2.5.
TIMER 
• To change indoor unit indicator’s LED intensity
- Press continuously for 5 seconds.
14.2.6.
TIMER 
• To change remote control display from Degree Celsius to Degree Fahrenheit.
- Press continuously for 10 seconds.
52
15 Troubleshooting Guide
15.1. Refrigeration Cycle System
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table on the right.
Page of 108