15.5.20. H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error code will not display (no TIMER LED blinking) but store in EEPROM
Malfunction Decision Conditions
• Freeze prevention control takes place (when indoor pipe temperature is lower than 2
qC).
Malfunction Caused
• Clogged air filter of the indoor unit.
• Dust accumulation on the indoor unit heat exchanger.
• Air short circuit.
• Detection error due to faulty indoor pipe temperature sensor.
• Detection error due to faulty indoor unit PCB.
Troubleshooting
82
15.5.21. F11 (4-way valve Abnormality)
Malfunction Decision Conditions
• When heating operation, when indoor pipe temperature is below 10
qC.
• When cooling operation, when indoor pipe temperature is above 45
qC.
Malfunction Caused
• Connector in poor contact.
• Faulty sensor.
• Faulty outdoor unit PCB.
• 4-way valve defective.
Troubleshooting
83
15.5.22. F17 (Indoor Standby Units Freezing Abnormality)
Malfunction Decision Conditions
• When the different between indoor intake air temperature and indoor pipe temperature is above 10
qC or indoor pipe temperature
is below -1.0
qC.
Remark:
When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to
other indoor unit(s).
Malfunction Caused
• Wrong wiring connection.
• Faulty sensor.
• Faulty expansion valve.
Troubleshooting
84
15.5.23. F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
• During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit
main PCB senses abnormal high DC voltage level.
Malfunction Caused
• DC voltage peak due to power supply surge.
• DC voltage peak due to compressor windings not uniform.
• Faulty outdoor PCB.
Troubleshooting