14.4. Error Codes Table
Note:
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard
following by pressing the “CHECK” button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is
changed from one “beep” to four “beep” sounds.
Abnormality / Protection control
Abnormality
Judgement
Emergency 
operation
Primary location to verify
Diagnosis
display
H00
No abnormality detected
Normal operation
H11
Indoor / outdoor abnormal 
communication
> 1 min after starting 
operation
Indoor fan operation 
only
• Internal / external cable connections
• Indoor / Outdoor PCB
H14
Indoor intake air temperature sensor 
abnormality
Continue for 5 sec.
• Intake air temperature sensor 
(defective or disconnected)
H15
Outdoor compressor temperature sensor 
abnormality
Continue for 5 sec.
• Compressor temperature sensor 
(defective or disconnected)
H16
Outdoor Current Transformer open 
circuit
• Outdoor PCB
• IPM (Power transistor) module
H19
Indoor fan motor merchanism lock
• Indoor PCB
• Fan motor
H23
Indoor heat exchanger temperature 
sensor abnormality
Continue for 5 sec.
O
 (Cooling only)
• Heat exchanger temperature sensor 
(defective or disconnected)
H26
Ion abnormality
• Indoor PCB
• Ionizer
H27
Outdoor air temperature sensor 
abnormality
Continue for 5 sec.
O
• Outdoor temperature sensor 
(defective or disconnected)
H28
Outdoor heat exchanger temperature 
sensor abnormality
Continue for 5 sec.
O
• Outdoor heat exchanger temperature 
sensor (defective or disconnected)
H30
Discharge temperature sensor 
abnormality
H33
Indoor/Outdoor wrong connection
• Indoor/Outdoor supply voltage
H38
Indoor/Outdoor mismatch
H98
Indoor high pressure protection
• Air filter dirty
• Air circulation short circuit
H99
Indoor heat exchanger anti-freezing 
protection
• Insufficient refrigerant
• Air filter dirty
F11
Cooling / Heating cycle changeover 
abnormality
4 times occurance 
within 30 minutes
• 4-way valve
• V-coil
F90
PFC control
4 times occurance 
within 10 minutes
• Voltage at PFC
F91
Refrigeration cycle abnormality
7 times occurance 
continuously
• No refrigerant
(3-way valve is closed)
F93
Outdoor compressor abnormal revolution
4 times occurance 
within 20 minutes
• Outdoor compressor
F95
Cool high pressure protection
4 times occurance 
within 20 minutes
• Outdoor refrigerant circuit
F96
IPM (power transistor) overheating 
protection
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
F97
Outdoor compressor overheating 
protection
4 times occurance 
within 20 minutes
• Insufficient refrigerant
• Compressor
F98
Total running current protection
3 times occurance 
within 20 minutes
• Excess refrigerant
• Improper heat radiation
F99
Outdoor Direct Current (DC) peak 
detection
7 times occurance 
continuously
• Outdoor PCB
• IPM (Power transistor)
• Compressor
50
15 Disassembly and Assembly Instructions
15.1. Indoor Electronic Controller and Control Board
High voltages are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding
with repair work. Failure to heed this caution may result in electric shocks.
51
52
15.2. Indoor Cross Flow Fan and Fan Motor
Page of 77