Panasonic CS-E18HKDW / CU-E18HKD Service Manual ▷ View online
17
5 Dimensions
5.1.
Indoor Unit & Remote Control
18
5.2.
Outdoor Unit
5.2.1.
CU-E18HKD
19
6 Refrigeration Cycle Diagram
Piping size
Rated
Length
(m)
Max
Elevation
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Model
Gas
Liquid
E18HKD
1/2”
1/4”
5
15
3
20
20
* If piping length is over common length, additional refrigerant should be added as shown in the table.
20
7 Block Diagram
7.1.
CS-E18HKDW CU-E18HKD