12.3.4.  EVACUATION OF THE EQUIPMENT
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
 1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
  • Be sure to connect the end of the charging hose with the push pin to the service port.
 2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
 4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
 5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
 6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
 7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
 8. Mount valve caps onto the 2-way valve and the 3-way valve.
  • Be sure to check for gas leakage.
CAUTION
  • If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
  • If the leak stops when the piping connections are tightened further, continue working from step 3.
  • If the leak does not stop when the connections are retightened, repair the location of leak.
  • Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
12.3.5. CONNECT THE CABLE TO THE OUTDOOR UNIT
(FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT)
 1. Remove the control board cover from the unit by loosening the screw.
 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 1.5 mm
2
flexible cord,
type designation 245 IEC 57 or heavier cord.
89
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
  • If a drain elbow is used, the unit should be placed on a
stand which is taller than 3 cm.
  • If the unit is used in an area where temperature falls below
0°C for 2 or 3 days in succession, it is recommended not to
use a drain elbow, for the drain water freezes and the fan
will not rotate.
CHECK THE DRAINAGE
  • Open front panel and remove air filters.
(Drainage checking can be carried out without removing the
front grille.)
  • Pour a glass of water into the drain tray-styrofoam.
  • Ensure that water flows out from drain hose of the indoor
unit.
EVALUATION OF THE PERFORMANCE
  • Operate the unit at cooling operation mode for fifteen
minutes or more.
  • Measure the temperature of the intake and discharge air.
  • Ensure the difference between the intake temperature and
the discharge is more than 8°C.
 3. Secure the cable onto the control board with the holder (clamper).
 4. Cable connection to the power supply (220 - 240V, 50Hz) through knife switch (Disconnecting means).
  • Connect the approved polychloroprene sheathed power supply cable (3 x 1.5 mm
2
), type designation 245 IEC 57 or heavier
cord to the terminal board, and connect the other end of the cable to knife switch (Disconnecting means).
Note: Knife switch (Disconnecting means) should have minimum 3 mm contact gap.
  • Secure the cable onto the control board with the holder (clamper).
  • Power supply earth cable must connect to the left earth terminal.
12.3.6. PIPE INSULATION
 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM
with thickness 6 mm or above.
90
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at flare nut
connection?
Is the connecting cable being fixed to terminal board firmly?
Is the connecting cable being clamped firmly?
Is the drainage OK?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the installation plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
Is the super alleru-buster filter is installed?
CHECK ITEMS
91
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
1.
Rated Frequency Operation
13 Servicing Information
Caution:
  • Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use
a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
  • Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
13.1. Troubleshooting
During troubleshooting and servicing, rated compressor operating frequency must be obtained in order to check the
specification and technical data. Below are the methods used to obtain rated compressor operating specification.
(a) Cooling
(i) Press the Auto button continuously for 5 seconds or less than 8 seconds, the air conditioner starts operation at Cooling rated frequency.
(“beep” will be heard at the 5th second.)
(ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The operation of air conditioner is Cooling rated frequency.
(b) Heating
Press the Auto button continuously for 8 seconds or less than 11 seconds, the air conditioner starts operation at Heating rated
frequency. (“beep” “beep” will be heard at the 8th second.)
92
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
Page of 122
Display

Click on the first or last page to see other CS-E15DKDW / CU-E15DKD / CS-E18DKDW / CU-E18DKD / CS-E21DKDS / CU-E21DKD service manuals if exist.