7 Wiring Diagram
17
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
8.1. Basic Function
8 Operation Details
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes,
automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the
microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature
shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that
judging the condition according to internal setting temperature and intake air temperature.
8.1.1. Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting processes.
These shifting processes are depending on the air conditioner settings and the operation environment. The final shifted value
will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit.
Table (a): Auto Operation Mode Setting
Mode Shift:
Temperature Shift (°C)
Cooling/Soft Dry
→ Heating
-2.0
Heating
→ Cooling/Soft Dry
+2.0
18
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
Table (b): Outdoor Air Temperature Shifting
Mode:
Outdoor Temperature, X (°C):
Temperature Shift (°C)
Manual Operation
Auto Operation
Cooling/Soft Dry
38
X
1.50
2.00
30
X
38
1.25
1.25
23
X
30
1.25
1.25
X
23
1.75
1.75
Heating
21
X
-2.25
-1.50
17
X
21
-1.75
-1.00
13
X
17
-0.75
0.00
9
X
13
0.25
0.25
5
X
9
1.25
1.00
1
X
5
0.75
1.00
-3
X
1
1.50
1.00
X
-3
1.50
1.00
Table (c): Powerful Mode Shifting
Mode:
Period, X (min):
Temperature Shift (°C)
Cooling
X
20
-2.0
X
20
0.0
Soft Dry
X
20
-1.0
X
20
0.0
Heating
X
20
+3.5
X
20
+3.25
Table (d): Quiet (Lo) Mode Shifting
Mode:
Period, X (min):
Temperature Shift (°C)
Cooling, Soft Dry
20 min
X
50 min
-3.0
50 min
X
110 min
-4.0
110 min
X
440 min
-5.0
Table (e): Fan Speed Shifting
Mode:
Fan Speed:
Temperature Shift (°C)
Cooling
Lo
-0.25
Me-, Me, Me+, Auto
0.00
Hi
+0.25
Soft Dry
All
+0.25
Heating
Lo
+1.50
Me-, Me, Me+, Auto
+0.75
Hi
+0.75
Table (f): Start-Up Shifting
Mode within 60 Minutes from Start-up:
Temperature Shift (°C)
Cooling/Soft Dry
-1.0
Heating
+2.0
19
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
CompHz = Freq. A × Freq. H + Freq. C
Example Calculation:
Model No.: E18DK
Operation Mode: Cooling
When Intake Air Temperature - Internal setting Temperature:
1.5°C
CompHz
=
Freq. A × Freq. H + Freq. C
=
1.53 × 46 + 2.5
=
72 Hz (It cuts down less than a decimal point)
Cooling & Soft Dry
E18DK
E21DK
Freq. A
Freq. C
Freq. A
Freq. C
Low Load (Freq. H
9)
1.2
5.0
1.7
7.0
High Load (Freq. H > 10)
1.53
2.5
2.0
4.0
Heating
E18DK
E21DK
Freq. A
Freq. C
Freq. A
Freq. C
Low Load (Freq. H
11)
1.6
8.0
1.9
7.0
High Load (Freq. H > 12)
2.2
1.0
2.35
1.0
Freq. Range
E18DK
E21DK
Cooling
Fc
72
96
Operation Range
12 ~ 86
12 ~ 102
Heating
Fh
86
92
Operation Range
14 ~ 128
14 ~ 128
8.1.2. Compressor Operation Frequency
Intake Air Temperature - Internal Setting Temperature (°C)
Freq. H
Zone
Cooling & Soft Dry
Heating
Cooling
Soft Dry
Heating
Remark
1
-2.0
1.5
1
1
1
2
-1.5
1.0
1
1
1
3
-1.0
0.5
14
8
11
4
-0.5
0.0
20
8
15
5
0.0
-0.5
27
8
22
6
0.5
-1.0
35
11
27
7
1.0
-1.5
43
11
36
8
1.5
-2.0
46
11
39
Fc, Fh
9
2.0
-2.5
46
11
39
Fc, Fh
10
2.5
-3.0
46
11
39
Fc, Fh
11
Nil
-3.5
Nil
Nil
39
Fh
12
Nil
-4.0
Nil
Nil
39
Fh
Operating Frequency Calculation Formula:
Remarks:
When Freq. H is equal to 46 (Cooling), 39 (Heating) or above, the Comp. may run at the freq. higher than Fc or Fh up to max.
freq. operation.
Best Amenity Control
Every 90s (Cooling), 120s (Heating) maintain same zone Freq. H + 1 until Fc (46), Fh (39).
8.1.3. Cooling Operation
8.1.3.1. Thermostat control
  • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point +0.5°C.
20
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
Page of 122
Display