8.2.7. IPM (Power transistor) Prevention Control
This control is applicable to all kinds of operation mode.
A. DC Peak Current Control
 1. When electric current to IPM exceeds set value of 22.5 ± 3.5 A, the compressor will stop operate. Then, operation will restart
after three minutes.
 2. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
B. Overheating Prevention Control
 1. When the IPM temperature rises to 110°C, compressor operation will stop immediately.
 2. Compressor operation restarts after three minutes the temperature decreases to 95°C.
8.2.8. Compressor Overheating Prevention Control
This control is applicable to all kinds of operation mode.
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below figure.
8.2.9. Low Pressure Control (Gas Leakage Detection)
This control is applicable to all kinds of operation mode.
 1. When the conditions listed in below table occur, the compressor stops and restarts after three minutes.
 2. If this phenomenon is continuously occurring for twice within 20 minutes, all indoor and outdoor relays will be cut off.
 3. This control is not applicable for deice operation.
Conditions
E9CKP
E12CKP/E15CKP
Cooling/Soft Dry
Heating
Cooling/Soft Dry
Heating
1. Compressor frequency (Hz)
47
56
67
68.5
2. Outdoor total running current (A)
1.21
1.21
1.21
1.21
3. Indoor heat exchanger temperature
25
25
25
25
Note: Conditions 1 and 2 needed to be happened continuously for 5 minutes.
25
CS-E15CKP CU-E15CKP5
8.2.10. Minimum Operation Frequency Protection Control
This control is applicable to all kinds of operation mode.
When the compressor operate at frequency lower than 26 Hz (E9CKP) or 28 Hz (E12CKP/E15CKP) for 240 minutes, the operation
frequency will be increased to 26 Hz (E9CKP) or 28 Hz (E12CKP/E15CKP) for two minutes.
8.2.11. Low Operation Frequency Protection Control
This control is applicable to all kinds of operation mode.
When all the below conditions occur, minimum value (Freq. MIN) for the frequency instructed to compressor will change to 30 Hz
(E9CKP) and 32 Hz (E12CKP/E15CKP) for cooling mode operation, and 21 Hz (E9CKP & E12CKP/E15CKP) for heating mode
operation.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (°C)
T
15 or T
30
Outdoor air (°C)
T
16 or T
38
T
4 or T
24
Indoor heat exchanger (ºC)
T
30
T
0
8.2.12.  Auto Restart Control
This control is applicable to all kinds of operation mode.
 1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power
supply resumes.
 2. This type of control is not applicable during ON/OFF Timer setting.
8.2.13. Outdoor Air Temperature Control
 1. For Cooling Mode and Soft Dry Mode operation, the compressor operating frequency is regulated in accordance to the outdoor
air temperature as shown in the diagram below. This control will begin one minute after the compressor starts.
26
CS-E15CKP CU-E15CKP5
 2. For Heating Mode operation, the compressor operating frequency is regulated in accordance to outdoor air temperature as
shown in the below figures. This control will begin 50 seconds after the compressor starts.
8.2.14. Deodorizing Control
This type of control is applicable on Cooling Mode and Soft Dry Mode operation only.
 1. During cooling or soft dry operation with automatic fan speed, the unit will operate as state below for deodorizing purpose.
 2. When compressor is in operation, the steps follow: 1
→ 2 → 3.
 3. When compressor stops operation, the steps follow: 4
→ 5 → 4 → 5
 4. If the compressor still stops operation after three minutes, the step will start from 4.
 5. This control is not applicable during sleep shift operation, ON timer preparation and anti-freezing control.
27
CS-E15CKP CU-E15CKP5
8.2.15. High Pressure at Minimum Frequency Control
This type of control is applicable on Cooling Mode and Soft Dry Mode operation only.
 1. When outdoor air temperature increases to 38.6°C, compressor operating frequency reduces to minimum of 30 Hz and 32 Hz
for E9CKP and E12CKP/E15CKP respectively.
 2. Compressor operating frequency will resume to normal when outdoor air temperature decrease to 37.8°C.
8.2.16. Anti-Freezing Control
This type of control is applicable on Cooling Mode and Soft Dry Mode operation only.
 1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
 2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
 3. At the same time, indoor fan speed increase its frequency as value of two steps up in Fan Speed Number compared to its
normal operation. (Refer Table on Fan Speed Level and Supplied Voltage).
 4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
8.2.17. Anti-Fog Discharge Control
This type of control is applicable on Cooling Mode and Soft Dry Mode operation only.
 1. When indoor fan speed is set at Me- or slower, the compressor operating frequency is regulated by operation time to prevent
fog discharged from indoor as shown in below table.
Operation time, T (min)
E9CKP
E12CKP/E15CKP
0
T
30
Max 33 Hz
Max 44 Hz
30
T
90
Max 26 Hz
Max 36 Hz
90
T
420
Max 26 Hz
Max 36 Hz
 2. After 420 minutes, the operation restarts again from the beginning.
 3. The operation will restart the above control whenever remote controller setting temperature or fan speed setting is changed.
28
CS-E15CKP CU-E15CKP5