31 
12.4  Indoor Fan Speed Control 
x  Indoor fan speed can be set using remote control 
12.4.1 
Fan Speed Rotation Chart 
 
12.4.2 
Automatic Fan Speed Control 
x  When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the 
table. 
o  Fan speed rotates in the range of Hi and Me. 
o  Deodorizing Control will be activated. 
 
 SHi 
Hi 
Me 
HLo 
CLo 
Lo- 
SLo 
Stop 
Hi          
Me 
         
Manual 
Lo         
Normal 
Auto  
 
 
 
 
 
 
 
QHi 
 
Hi-70 
       
QMe 
  
Me-70 
      
Manual 
QLo 
    
CLo-70 
   
Quiet 
Auto  
Hi-70 
Me-70 
 
 
 
 
 
Manual 
         
Cooling 
Powerful 
Auto 
         
Manual 
       
  
Normal 
Auto 
       
  
Manual 
       
  
Quiet 
Auto 
       
  
Manual 
       
  
Soft Dry 
Powerful 
Auto 
       
  
Mode 
Judgment 
       
  
 
x  Auto Fan Speed during cooling operation: 
Indoor fan will rotate alternately between off and on as shown in below diagram. 
At the beginning of each compressor starts operation, indoor fan speed increases gradually for deodorizing 
purpose. 
For the first time the compressor operates, indoor fan will be switched to Hi fan speed from Lo- after 70 
seconds from the start of compressor. This cause the room temperature to achieve the setting temperature 
quickly. 
During compressor stops, indoor fan will operate at Lo- for the beginning 20 seconds to prevent higher 
volume of refrigerant in liquid form returning to the compressor. 
After the compressor turned off for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the 
room. This is to obtain the actual reading of the intake air temperature. 
For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and 
lesser noise environment, after 70 seconds from the restarts of compressor. 
 
Fan Speed (rpm) 
Speed 
CS-C7JKD CS-C9JKD CS-C12JKD 
SHi 1050 
1170 
1150 
Hi 960 
1150 
1080 
Me 840 
930 
940 
HLo 820 
820 
840 
CLo 740 
740 
800 
Lo- 700 
700 
760 
SLo 680 
680 
740 
QHi 890 
1080 
1010 
QMe 770 
860 
870 
QLo 690 
690 
730 
32 
 
 
 
 
 
*1 
   
 
 
*2 
 
 
Lo-  Lo-  Lo- 
 
Lo- 
 
 Variable 
RPM
Indoor Fan 
 
Stop  
 
 
 
 Stop    
40” 30” 
20”  160” 
40” 30” 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Compressor 
 
 
ON     OFF   
ON 
 
*1 
Fan Speed is Hi until the compressor stops (when the room temperature reaches setting 
temperature). 
*2 
Fan Speed is Me after the compressor restarts. 
 
x  Auto Fan Speed during Soft Dry operation: 
Indoor fan will rotate alternately between off and Lo-. 
At the beginning of each compressor starts operation, indoor fan will increase fan speed gradually for 
deodorizing purpose. 
When compressor turned off for 6 minutes, indoor fan will start at Lo- to circulate the air in the room. This is 
to obtain the actual reading of intake air temperature. 
 
  
 
Lo-  Lo- 
 
Lo- 
 Stop 
 
Stop 
 
Stop 
 
Indoor Fan 
 
 
 
 
 
 
 
40”  
6’ 
 40” 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Compressor  
ON 
OFF 
ON 
 
12.4.3 
Manual Fan Speed Control 
x  Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control. 
x  There are 3 types of fan speed settings: Lo, Me, Hi. 
12.4.4 
Indoor Fan Motor rpm Abnormal Control 
x  Immediate after the fan motor is started, rpm abnormal control is performed every second. 
x  During fan motor on, if fan motor feedback  2550 rpm or < 50 rpm continuously for 10 seconds, the fan motor 
error counter increased; fan motor is then stopped and restarted. If the fan motor error counter increased to 7, 
then air conditioner will stop operation. 
 
12.5  Outdoor Fan Speed Control 
x  There is only one speed for outdoor fan motor. 
x  When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously. 
x  Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off. 
 
33 
12.6  Vertical Airflow Direction Control 
12.6.1 Auto 
Control 
x  When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as 
shown in the diagram. 
x  When stops operation using the remote control, the discharge vent is reset and stops at the closing position. 
x  During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that 
condition, the louver will stop swinging. 
 
 
 
 
 
 
 
 
 
 
 
 
 
12.6.2 Manual 
Control 
x  When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and 
the airflow direction louver move up and down in the range shown in the diagram. 
x  The louver can be adjusted by pressing the button to the desired louver position. 
x  When stop operation using the remote control, the discharge vent is reset, and stop at the closing position. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
12.7  Horizontal Airflow Direction Control 
The horizontal airflow direction louvers can be adjusted manually by hand. 
 
12.8 Powerful Operation 
x  To achieve the setting temperature quickly. 
x  When powerful operation is set, the setting temperature will be automatically decreased 3°C internally against 
the present setting temperature (Lower temperature limit: 16°C). 
x  This operation automatically running under Shi fan speed (Cooling), Lo- Fan Speed (Soft Dry). 
x  Vertical Airflow Direction: 
o  In “Manual” setting, the vane will automatically shift down 10° lower than previous setting. 
o  In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° 
downward. 
x  Powerful operation stops when: 
o  Quiet/Powerful button is pressed again 
o  Powerful operation has operate for 15 minutes 
o  Stopped by OFF/ON operation button. 
o  Timer OFF activates 
o  Operation mode is changed 
Closing 
position  
/ 135° 
Lower limit for cooling mode 
and soft dry mode 
Horizontal 
11° 
16° 
27° 
21° 
33° 
Upper limit for 
cooling mode and 
soft dry mode 
Upper limit for cooling mode 
and soft dry mode/11° 
22° 
Closing 
position  
/ 135° 
Swing up and down 
Lower limit for cooling mode and 
soft dry mode/33° 
Horizontal 
34 
12.9 Quiet Operation 
(For Cooling Operation or cooling region of Soft Dry Operation) 
x  To provide quiet cooling operation condition. 
x  Once the Quiet Operation is set at the remote control, the Quiet LED illuminated. The sound level will reduce 
around 2dB(A) for Lo fan speed or 3dB(A) for Hi/Me fan speed against the present operation sound level. 
x  Dew formation become severe at Quite Lo Cool, therefore Quiet Lo cool operated only for 2 hours (1 hour QLo, 1 
hour QLo + 80 rpm). After that, it goes back to Lo cool (However Quiet LED remains illuminated). 
x  Manual Airflow Direction: 
o  RPM control during Lo cool 
 
 
 
Press 
Quiet 
 
Press 
Quiet 
 
Press 
Quiet 
 
Speed 
Lo to QLo : about 20 rpm / 0.05 sec 
QLo to QLo+80 
: about 10 rpm / 2 sec 
Or QLo+80 to QLo+140 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Quiet 
LED 
OFF ON OFF 
ON 
 
Lo  
Lo 
 
  QLo+140 
Lo 
     
QLo+140 
 
  
 
QLo+80    
 
QLo+80   
 
 
 Fan 
 
 
       
 
 
     
 
 
  
  QLo 
    
  QLo 
   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  
 
      
 
     
 
Time 
(Hour) 
 
 
 
1.0 H 
1.0 H 
 
 
 
1.0 H 
1.0 H 
 
 
 
 
 
o  RPM control during Hi & Me cool 
 
 
 
Press Quiet 
 
Cancel Quiet
 
Press Quiet
 
 
 
 
 
 
 
 
 
 
 
 
 
Quiet 
LED 
OFF   ON   OFF   ON  
 
 
 
 
 
 
 
 
 
 
 
Hi/Me      Hi/Me      
 
Fan 
 
Q Hi/Q Me 
 
Q Hi/Q Me 
 
   
 
   
 
 
Time 
(Hour) 
 
x  Auto Fan Speed 
 
 
 
 
 
Quiet Hi (if before thermo off)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Quiet ME (after thermo off) 
 
 
Lo-  Lo-
Variable 
Lo-
 
Lo-
 
 
Indoor 
fan 
 
Stop 30”  20”
RPM 
 
Stop 30”
 
 
 
 
40” 
   
160” 
 
40” 
  
 
 
 
 
 
 
 
 
 
 
 
 
 
Compressor 
ON 
 OFF  
ON 
 
 
x  Quiet operation stops when: 
o  Quiet button is pressed again. 
o  Stopped by OFF/ON operation button. 
o  Timer OFF activates. 
o  Operation mode button is changed. 
 