During Anti-Dew condensation prevention, Airflow Direction Manual Control angle change from 10°, 15°, 20°, 32° to 22°,
24°, 26°, 28°, 30°.
8.5. Indoor Fan Speed Control
 • 
Indoor Fan Speed can be set using remote control.
8.5.1. Fan Speed Rotation Chart
Speed
Fan Speed
CS-C7DKD
CS-C9DKD
CS-C12DKD
S Hi
1210
1290
1300
Hi
1100
1210
1270
Me
990
1040
1050
H Lo
940
940
980
C Lo
860
860
890
Lo-
810
810
840
S Lo
760
760
790
SS Lo
-
-
-
Q S Hi
-
-
-
Q Hi
1000
1110
1170
Q Me
890
940
950
QH Lo
-
-
-
Q Lo
760
760
790
25
CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD
8.5.2. Automatic Fan Speed Control
 • 
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
 − 
Fan speed rotates in the range of Hi and Me.
 − 
Deodorizing Control will be activated.
 • 
Auto Fan Speed during cooling operation:
 1. Indoor fan will rotate alternately between off and on as shown in below diagram.
 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
 3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the
start of compressor. This cause the room temperature to achieve the setting temperature quickly.
 4. During compressor stop, indoor fan will operate at Lo for the beginning 20 seconds to prevent higher volume of refrigerant
in liquid form returning to the compressor.
 5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the room.
This is to obtain the actual reading of the intake air temperature.
 6. For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and lesser noise
environment, after 70 seconds from the restart of compressor.
26
CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD
 • 
When the vertical airflow direction is set to Auto using the
remote control, the louver swings up and down as shown in
the diagram.
 • 
When stop operation using the remote control, the
discharge vent is reset, and stop at the closing position.
 • 
During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging and rest at the upper
limit.
 • 
When the vertical airflow direction is set to Manual using the
remote control, the automatic airflow is released and the
airflow direction louver move up and down in the range
shown in the diagram.
 • 
The louver can be adjusted by pressing the button to the
desired louver position.
 • 
When stop operation using the remote control, the
discharge vent is reset, and stop at the closing position.
 • 
Auto Fan Speed during Soft Dry operation:
 1. Indoor fan will rotate alternately between off and Lo-.
 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
 3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
8.5.3. Manual Fan Speed Control
 • 
Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
 • 
There are 3 types of fan speed settings: Lo, Me, Hi.
8.6. Outdoor Fan Speed Control
 • 
There is only one speed for outdoor fan motor.
 • 
When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
 • 
Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
8.7. Vertical Airflow Direction Control
8.7.1. Auto Control
8.7.2. Manual Control
27
CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD
8.8. Horizontal Airflow Direction Control
 • 
The horizontal airflow direction louvers can be adjusted manually by hand.
8.9. Powerful Operation
 • 
The Powerful operation is to achieve the setting temperature quickly.
 • 
When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present
setting temperature (Lower temperature limit: 16°C).
 • 
This operation automatically will be running under SHi Fan Speed (Cooling), Lo- Fan Speed (Soft Dry).
 • 
Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10° lower than previous.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
 • 
Powerful Mode will operate for 15 minutes only and operation will shift back to previous setting mode.
 • 
Powerful operation stops when:-
- Powerful mode button is pressed again.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
- Quiet mode button is pressed.
- Operation mode button is changed.