7  Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor 
unit according to the diagram below. 
 
 
 
8  Secure the power supply cord and connection cable onto the control board with the holder. 
9  Close grille door by tighten with screw and close the front panel. 
 
Note: 
  Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap. 
  Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively. 
  Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires as shown in the figure for the 
electrical safety in case of the slipping out of the cord from the anchorage. 
11.2.4.1  Wire Stripping and Connecting Requirement  
 
 
 
 
 
 
 
 
 
 
3
2
1
t
i
n
u
 
r
o
o
d
t
u
o
 
e
h
t
 
n
o
 
s
l
a
n
i
m
r
e
T
Colour of wires (connection cable)
Terminals on the indoor unit
L
N
1
2
3
(Power supply cord)
Terminals on the isolating devices 
(Disconnecting means)
(L) (N)
Recommended 
length (mm)
a b
c
d e
f
g
55 35 35 50 40 35 60
 WARNING
 This equipment must 
be properly earthed.
Recommended 
length (mm)
Tape
Connection cable
Tape
Power supply cord
Terminal Board
Control 
Board
Earth wire 
longer than 
others 
AC wires 
for safety 
reason
Holder
Holder
Indoor & outdoor 
connection cable 
Isolating Devices
Outdoor unit
Power supply 
cord
OR
OR
OR
  Do not joint wires
  Use complete wire without joining.
  Use approved socket and plug with earth pin.
   Wire connection in this area must follow to national wiring rules.
Conductor 
over inserted
Wire stripping
No loose strand 
when inserted
10 ± 1 mm
Conductor 
fully inserted
PROHIBITED
Conductor not 
fully inserted
PROHIBITED
ACCEPT
Indoor/outdoor 
connection 
terminal board
5 mm or more 
(gap between wires)
WARNING
RISK OF FIRE
JOINING OF WIRES 
MAY CAUSE 
OVERHEATING AND 
FIRE.
26 
11.3 Outdoor Unit 
11.3.1  Install the Outdoor Unit 
  After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. 
1  Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). 
2  When installing at roof, please consider strong wind and earthquake. 
Please fasten the installation stand firmly with bolt, screws or nails. 
 
 
Model A 
BE20*** 
KE25***, BE25***, DE25***
KE35***, BE35***, DE35***
570 mm  105 mm  18.5 mm 320 mm
KE50***, BE50***, DE50*** 540 mm  160 mm  18.5 mm 330 mm
11.3.2  Connect the Piping 
11.3.2.1 Connecting 
the Piping to Indoor 
Please make flare after inserting flare nut (locate at 
joint portion of tube assembly) onto the copper pipe. 
(In case of using long piping) 
Connect the piping 
  Align the center of piping and sufficiently tighten 
the flare nut with fingers. 
  Further tighten the flare nut with torque wrench in 
specified torque as stated in the table. 
 
 
Do not overtighten, overtightening may cause gas leakage. 
 
 
Piping size 
Torque 
6.35 mm (1/4") 
[18 N•m (1.8 kgf•m)] 
9.52 mm (3/8") 
[42 N•m (4.3 kgf•m)] 
12.7 mm (1/2") 
[55 N•m (5.6 kgf•m)] 
15.88 mm (5/8") 
[65 N•m (6.6 kgf•m)] 
19.05 mm (3/4") 
[100 N•m (10.2 kgf•m)] 
 
11.3.2.2 Connecting 
the 
Piping to Outdoor 
Decide piping length and then cut by using pipe cutter. 
Remove burrs from cut edge. 
Make flare after inserting the flare nut (locate at valve) 
onto the copper pipe. 
Align center of piping to valve and then tighten with 
torque wrench to the specified torque as stated in the 
table. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
A
B
C
D
Torque 
wrench
Spanner or 
Wrench
27 
11.3.3  Evacuation of the Equipment 
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND 
PIPES in the following procedure. 
 
 
 
1  Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way 
valve. 
o
 
Be sure to connect the end of the charging hose with the push pin to the service port. 
2  Connect the center hose of the charging set to a vacuum pump. 
3  Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from  
0 cmHg (0 MPa) to –76 cmHg (–0.1 MPa). Then evacuate the air approximately ten minutes. 
4  Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the 
gauge does not move after approximately five minutes. 
Note : BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE. 
5  Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve. 
6  Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench. 
7  Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” 
using a hexagonal wrench (4 mm). 
8  Mount valve caps onto the 2-way valve and the 3-way valve. 
o
 
Be sure to check for gas leakage. 
 
 
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure: 
If the leak stops when the piping connections are tightened further, continue working from step 3. 
If the leak does not stop when the connections are retightened, repair location of leak. 
Do not release refrigerant during piping work for installation and reinstallation. 
Take care of the liquid refrigerant, it may cause frostbite. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
OPEN
CLOSE
Gas side
Liquid side
Outdoor unit
Two-way valve
Three-way valve
Indoor unit
Vacuum 
pump
Close
Close
28 
11.3.4  Connect the Cable to the Outdoor Unit 
1  Remove the control board cover from the unit 
by loosening the screw. 
2  Connection cable between indoor unit and 
outdoor unit shall be approved 
polychloroprene sheathed 4 x 1.5 mm
2
  
(3/4 ~ 1.5HP) or 4 x 2.5 mm
2
 (2.0HP) flexible 
cord, type designation 60245 IEC 57 or 
heavier cord. Do not use joint connection 
cable. Replace the wire if the existing wire 
(from concealed wiring, or otherwise) is too 
short. Allowable connection cable length of 
each indoor unit shall be 30 mm or less. 
 
 
 
3  Secure the cable onto the control board with 
the holder. 
4  Attach the control board cover back to the 
original position with screw. 
5  For wire stripping and connection requirement, 
refer to instruction 11.2.4.1 of indoor unit. 
 
 
 
 
WARNING
 
 
 This equipment must be properly earthed. 
 
  Earth wire shall be Yellow/Green (Y/G) in colour 
and longer than other AC wires for safety reason. 
 
 
11.3.5 Piping 
Insulation 
1  Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation 
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 
2  If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by 
using POLY-E FOAM with thickness 6 mm or above. 
11.3.6  Cutting and Flaring the Piping 
1  Please cut using pipe cutter and then remove the burrs. 
2  Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end 
down to avoid the metal powder entering the pipe. 
3  Please make flare after inserting the flare nut onto the copper pipes. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Terminals on the outdoor unit
1
2
3
Colour of wires
Terminals on the indoor unit
1
2
3
Earth Wire 
longer than 
others AC 
wires for 
safety reason
Terminal 
Board
Holder
Indoor and outdoor 
cable connection
Indoor Unit
When properly fl ared, the internal surface of the 
fl are will evenly shine and be of even thickness. 
Since the fl are part comes into contact with the 
connections, carefully check the fl are fi nish.
 Improper  fl aring 
Inclined Surface 
damaged
Cracked Uneven 
thickness
1.  To cut
2.  To remove burrs
3.  To fl are
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle
Bar
0 – 0.5 mm
Copper pipe
Reamer
Point down
Pipe
Page of 92