(No refrigerant in the refrigeration cycle)
 1. Connect the vacuum pump to the charge set’s centre
hose.
 2. Evacuation for approximately one hour.
 • 
Confirm that the gauge needle has moved toward -0.1
MPa (-76 cmHg) [vacuum of 4 mmHg or less.]
 3. Close the valve (Low side) on the charge set, turn off
the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning
off the vacuum pump).
 4. Disconnect the charge hose from the vacuum pump.
 • 
Vacuum pump oil
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.
11.1.5. Evacuation (Installation)
Procedure:
61
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /
11.1.6. Gas charging
(After Evacuation)
 1. Connect the charge hose to the charging cylinder.
 • 
Connect the charge hose which you disconnected from
the vacuum pump to the valve at the bottom of the
cylinder.
 2. Purge the air from the charge hose.
 • 
Open the valve at the bottom of the cylinder and press
the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
 3. Open the valve (Low side) on the charge set and charge
the system with liquid refrigerant.
 • 
If the system cannot be charged with the specified
amount of refrigerant, it can be charged with a little at a
time (approximately 150 g each time) while operating
the air conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1 minute and
then repeat the procedure. (pumping down-pin)
This is different from previous procedures. Because you are
charging with liquid refrigerant from the gas side, absolutely do
no attempt to charge with large amount of liquid refrigerant
while operating the air conditioner.
 4. Immediately disconnect the charge hose from the 3-
way valve’s service port.
 • 
Stopping partway will allow the refrigerant to be
discharged.
 • 
If the system has been charged with liquid refrigerant
while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
 5. Mount the valve stem caps and the service port cap.
 • 
Use torque wrench to tighten the service port cap to a
torque of 18 N.m.
 • 
Be sure to check for gas leakage.
Procedure:
62
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /
 • 
Electronic controller and Display Complete unit can be seen
by following the below removal procedures.
Fig. 1
 − 
Remove the 2 caps and 2 screws at the bottom of the
Front Grille. (Fig. 1)
Fig. 2
 − 
Remove the Front Grille Complete. (Fig. 2)
Fig. 3
 − 
Release the taps on top and on the right side of metal
plate cover. (Fig. 3)
 − 
Then remove the metal plate cover. (Fig. 3)
 − 
Remove the indicator complete screw, and then remove
the indicator complete. (Fig. 3)
12 Servicing Information
12.1. Distinction Of Lead Free (PbF) Printed Circuit Board
 • 
Printed circuit boards (manufactured) using lead free solder will have a PbF stamp on the Printed Circuit board.
CAUTION
 • 
Pb free solder has a higher melting point than standard solder; typically the melting point is 50 - 70°F (30 - 40°C) higher.
Please use a high temperature solder iron and set it to 700 ± 20°F (370 ± 10°C).
 • 
Pb free solder will tend to splash when heated too high (about 1100°F/600°C).
 • 
If you must use Pb solder, please completely remove all of the Pb free solder on the pin or solder area before applying Pb
solder. If this is not practical, be sure to heat the Pb free solder until it melts, before applying Pb solder.
12.2. Indoor Electronic Controllers Removal Procedures
63
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /
Fig. 4
 − 
To remove the electronic controller.
 − 
Release CN-FM connectors. (Fig. 4)
 − 
Release CN-Sonic connector. (Fig. 4)
 − 
Release CN-FB connector. (Fig. 4)
 − 
Release CN-ION connector. (Fig. 4)
 − 
Release CN-TH connector. (Fig. 4)
 − 
Release CN-STM connector. (Fig. 4)
 − 
Release CN-REC/DISP connector. (Fig. 4)
 • 
Remove Control Board Cover
Fig. 6
 − 
Remove the screw on the left of the unit. (Fig. 6)
 − 
Pull the hook to the left and lift up the evaporator.
(Fig. 6)
 − 
Pull down the Discharge Grille Complete. (Fig. 6)
Fig. 5
 − 
Press the hook to the right then take out the PCB. (Fig.
5)
 − 
Release Ry-Pwr connector (black and brown) and Ac-
Wht connector from the PCB. (Fig. 5)
Fig. 7
Fig. 8
 − 
Remove indoor pipe sensor and air intake sensor from
the evaporator. (Fig. 7)
 − 
Remove the earth wire from the evaporator. (Fig. 7)
12.3. Indoor Fan Motor And Cross Flow Fan Removal Procedures