Normal Deicing Time Diagram
Overload Deicing Time Diagram
29
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /
8.6. Indoor Fan Speed Control
 • 
Indoor Fan Speed can be set using remote control.
8.6.1. Fan Speed Rotation Chart
Fan Speed (rpm)
CS-A7DKD
CS-A9DKD
CS-A12DKD
S Hi
1220
1270
1310
Hi
1050
1160
1280
Me
920
960
1120
H Lo
840
840
960
C Lo
780
780
880
Lo-
750
750
850
S Lo
700
700
750
SS Lo
300
300
300
Q S Hi
1120
1170
1210
Q Hi
950
1060
1180
Q Me
820
860
1020
Q H Lo
770
770
890
Q Lo
680
680
780
8.6.2. Automatic Fan Speed Control
 • 
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
 − 
Fan speed rotates in the range of Hi, Me and Lo-.
 − 
Deodorizing Control will be activated.
30
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /
 • 
Auto Fan Speed during cooling operation:
 1. Indoor fan will rotate alternately between off and on as shown in below diagram.
 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
 3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the
start of compressor. This cause the room temperature to achieve the setting temperature quickly.
 4. During compressor stop, indoor fan will operate at Lo- for the beginning 20 seconds to prevent higher volume of refrigerant
in liquid form returning to the compressor.
 5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the room.
This is to obtain the actual reading of the intake air temperature.
 6. When the compressor resume operation, indoor fan will operate at Me fan speed (after 70 seconds from the restart of
compressor) to provide comfort and lesser noise environment.
 • 
Auto Fan Speed during Soft Dry operation:
 1. Indoor fan will rotate alternately between off and Lo-.
 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
 3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
31
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /
(Cooling and Soft Dry Operation condition)
 • 
When the vertical airflow direction is set to Auto using the
remote control, the louver swings up and down as shown in
the diagram.
 • 
When stop operation using the remote control, the
discharge vent is reset, and stop at the closing position.
 • 
During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging and rest at the upper
limit.
 • 
During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0°-32° to 20°-30° under
Cooling and Soft Dry operation mode.
Cooling and Soft Dry Operation
 • 
Auto Fan Speed during Heating operation.
 1. Indoor fan will rotate in the range of SLo
Me according to the heat exchanger temperature.
8.6.3. Manual Fan Speed Control
 • 
Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
 • 
There are 3 types of fan speed settings: Lo, Me, Hi.
8.7. Outdoor Fan Speed Control
 • 
There is only one speed for outdoor fan motor.
 • 
When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
 • 
Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
8.8. Vertical Airflow Direction Control
8.8.1. Auto Control
32
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /
Page of 88