Soft Dry Operation Time Diagram
21
CS-A75KE CU-A75KE / CS-A95KE CU-A95KE / CS-A125KE CU-A125KE
Heating in operation according to Remote Control setting.
Time Delay Safety Control
30 minutes Time Save Control
Overload Protection Control
Compressor Reverse Rotation Protection Control
4-way Valve Control
Outdoor Fan Motor Control
8.3. Heating Mode Operation
  • 
When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
  • 
When the setting temperature is reached during heating operation, the compressor stops and it will not start for 4 minutes.
  • 
The compressor will start automatically if it has stopped for 30 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
  • 
If the temperature of the indoor heat exchanger rises to 51°C, Outdoor Fan stops.
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
  • 
If the indoor heat exchanger becomes 65°C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
  • 
If the compressor is operating continuously for 5 minutes or longer and temperature difference between intake air and indoor
heat exchanger is 5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid).
s
T = Indoor heat exchanger temperature - intake air temperature.
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
  • 
4-way valve always ON during Heating operation. (Except Deicing operation)
  • 
When the unit is switched to “OFF” during Heating operation, 4-way valve stay at Heating position for 5 minutes.
  • 
When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds.
(30 seconds Forced Operation).
22
S-A75KE CU-A75KE / CS-A95KE CU-A95KE / CS-A125KE CU-A125KE
Hot Start Control
Anti Cold Draft Control
When Heating operation starts, Indoor Fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
Hot Start is completed when indoor heat exchanger rises to 39°C.
  • 
This operation is to prevent the Cold Draft during Heating mode operation.
  • 
The operation will start when compressor OFF (Thermo OFF) during Heating operation.
  • 
For the first 30 sec from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat
exchanger temperature as shown below:
Note: SSLo: Fan will be running at Lo speed with Indoor heat exchanger temperature 1.5 sec ON and 5.5 sec OFF.
  • 
After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
  • 
Anti Cold Draft Control will stop when:
  − 
Intake temperature < set temperature -1.5°C. (Time Delay Safety Control 4 minutes waiting is valid)
  − 
After 30 minutes time saved control.
(see page 22).
23
CS-A75KE CU-A75KE / CS-A95KE CU-A95KE / CS-A125KE CU-A125KE
Automatic Fan Speed Mode
Heating Operating Time Diagram
When Automatic Fan Speed is selected at Remote Control during heating operation.
  • 
Fan speed rotates in the range of Me
Lo according to the heat exchanger temperature.
  • 
If use Manual Fan Speed,
at above diagram will operate with setting Fan Speed.