—8—
2.3.3 CAPACITOR
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control board. (Refer to Section 2.1.3)
3. Discharge the capacitor by placing a 20 K
resistor across the capacitor terminals.
4. Remove the screw which fastens the capacitor clamp.
5. Remove all the leads of capacitor terminals.
6. Re-install the components by referring to the removal
procedure above. (See Figure 15)
2.3.4 THERMOSTAT
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control board. (Refer to Section 2.1.3)
3. Remove 2 screws which fasten the thermostat. (See
Figure 16)
4. Remove all the leads of the thermostat terminals.
5. Remove the thermostat.
6. Re-install the components by referring to the removal
procedure above.
2.3.5 ROTARY SWITCH
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control board. (Refer to Section 2.1.3)
3. Remove 2 screws which fasten the rotary switch. (See
Figure 17)
4. Remove all the leads of the rotary switch terminals.
5. Remove the rotary switch.
6. Re-install the components by referring to the removal
procedure above.
2.3.6 POWER CORD
1. Disconnect the unit from source of power.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove a screw that secures control board to base
pan. (Refer to Section 2.1.3)
5. Pulls the control board toward you.
6. Disconnect the 2 receptacles and remove the grounding
screw.
7. Remove a screw securing the clip with cord to the
control board. (See Figure 18)
8. Pull the power cord.
9. Re-install by referring to procedures above.
2.4 REFRIGERANT CYCLE
2.4.1 CONDENSER
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Discharge the refrigerant by using a refrigerant recovery
system.
3. Remove the air guide. (Refer to Section 2.2.1)
4. Remove 2 screws which fasten the condenser.
5. After discharging the refrigerant completely, unbraze the
interconnecting tube at the condenser connections.
6. Remove the condenser.
7. Re-install by referring to the procedures above.
Figure 15
Figure 16
Figure 17
Figure 18
2.4.2 EVAPORATOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant by using a refrigerant
recovery system.
3. Remove the air guide upper. (Refer to Section
2.2.1)
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the evaporator
connections.
5. Remove the evaporator.
6. Re-install by referring to the procedures above.
2.4.3 CAPILLARY TUBE
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant by using a refrigerant
recovery system.
3. Remove the air guide upper. (Refer to Section
2.2.1)
4. After discharging the refrigerant completely,
unbraze the interconnecting tube of the capillary
tube.
5. Remove the capillary tube.
6. Re-install by referring to the procedures above.
NOTES
Replacement of the refrigeration cycle.
1. When replacing the refrigerating cycle, be sure to
discharge the refrigerant by using a refrigerant
recovery system.
2. After discharging the unit completely, remove the
desired components, and unbraze the pinch-off
tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Solder the pinch-off tubes with service valves.
5. After completing the above procedures, the valve
must be closed and left in place on the system for
any subsequent procedures.
6. Evacuate as follows:
6-1. Connect the vacuum pump, as illustrated in
figure 20A.
6-2. Start the vacuum pump. Slowly open manifold
valves A and B with two full turns counter-
clockwise and leave the valves closed.
The vacuum pump is now pulling through
valves A and B up to valve C by means of
manifold and the entire system.
CAUTION : If high vacuum equipment is used,
just crack valves A and B for a few minutes, then
open slowly with the two full turns counter-clock-
wise. This will keep oil from foaming and being
drawn into the vacuum pump.
6-3. Operate the vacuum pump for 20 to 30 min-
utes, until 600 micron vacuum is obtained.
Close valves A and B and observe vacuum
gauge for a few minutes.
A rise in pressure would indicate a possible
leak or moisture remaining in the system.
With valves A and B closed, stop the vacuum
pump.
6-4. Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure
20B. Open valve C.
Discharge the line at the manifold connection.
6-5. The system is now ready for final charging.
7. Recharge as follows:
7-1. Rotary compressor systems are charged from
the high-side. If the total charge cannot be put
in the high-side, the balance will be put in the
suction line through the access valve which is
installed as the system is opened.
7-2. Connect the charging cylinder as shown in fig-
ure 20B. With valve C open, discharge the
hose at the manifold connection.
7-3. Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
7-4. If more charge is required, the high-side will
not take it. Close valve A.
7-5. With the unit running, open valve B and add
the balance of the charge.
a. Do not add the liquid refrigerant to the low-
side.
b. Watch the low-side gauge, allow pressure to
rise to 30 lbs.
c. Turn off valve B and allow the pressure to
drop.
d. Repeat steps B and C until the balance of
the charge is in the system.
7-6. When the unit is operating correctly, use the
pinch-off tool with the unit still running and the
clamp on the pinch-off tube. Using a tube cut-
ter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos solder and solder
the pinch-off tube closed. Turn off the unit,
allow setting for a while and then test the leak-
age of the pinch-off connection.
—9—
—10—
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment, pinch-off tool capable
of making a vapor proof seal, leak detector, tubing cutter, hand tools to remove components and service valve.
B
A
B
A
B
A
COMPOUND GAUGE 
SEE INSETS
BELOW
CAPILLARY TUBE 
EVAPORATOR
(LOW PRESSURE SIDE)
COMPRESSOR
CONDENSER
(HIGH PRESSURE SIDE)
EXTERNAL VACUUM PUMP
LO      HI    CHARGING CYLINDER
MANIFOLD
GAUGE
C
Figure 20A-Pulling Vacuum
Figure 20B-Charging
—11—
3. INSTALLATION
This air conditioner is designed with a button-
down chassis so that it can be installed simply in
a window.
3-1. SELECT THE BEST LOCATION
1. To prevent vibration and noise, make sure the unit
is installed securely and firmly.
2. Install the unit where the sunlight does not shine
directly on the unit.
3. The outside of the cabinet must extend outward for
at least 10" and there should be no obstacles,
such as a fence or wall, within 20" from the back of
the cabinet because it will prevent heat radiation of
the condenser.
Restriction of outside air will greatly reduce the
cooling efficiency of the air conditioner.
4. Install the unit a little slanted so the back is slightly
lower than the front (about 1/4"). This will force
condensed water to the outside.
5. Install the unit with the bottom about 30"~60"
above the floor level.
3-2. CHECK OF INSTALLATION
The setting conditions must be checked prior to
initial starting.
The under mentioned items are especially
important checking points when the installation
is finished.
1. Grounding wire (Green of Green Yellow) is pro-
vided in the power cord. The green wire must be
grounded.
2. Connect to a single-outlet 15AMP circuit.
3. To avoid vibration or noise, make sure the air
conditioner is installed securely.
4. Avoid placing furniture or dreperies in front of the
air inlet and outlet.
3.3 HOW TO DRAIN
(When using drain pipe)
The air conditioner must be installed level or
titled slightly to the outside for proper water
drainage. On exceptionally hot and humid days
the air conditioner may drain condensation
water through overflow. If the air conditioner is
used in hot and a high humidity zone, exchange
the
HOLE RUBBER for the
DRAIN PIPE.
(See figure 22, figure 23)
ABOUT  / "
Over 20"
HEAT
RADIATION
FENCE
AWNING
COOLED AIR
30"~60"
1
4
BOTTOM
BASE PAN
DRAIN PIPE
BOTTOM
HOLE RUBBER
BASE PAN
1
2
All side louvers of the cabinet must remain
exposed to the outside of the structure.
CAUTION
Figure 21
Figure 22
Figure 23