DOWNLOAD LG LWH0560ACG_ACL Service Manual ↓ Size: 555.64 KB | Pages: 14 in PDF or view online for FREE

Model
LWH0560ACG_ACL
Pages
14
Size
555.64 KB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
lwh0560acg-acl.zip
Date

LG LWH0560ACG_ACL Service Manual ▷ View online

2.4.2 EVAPORATOR
1. Remove the cabinet. (Refer to Section 2.1.2) 
2. Discharge the refrigerant by using a refrigerant
recovery system.
3. Remove the orifice. (Refer to Section 2.2.1)
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the evaporator 
connections.
5. Remove the evaporator.
6. Re-install by referring to the procedures above.
2.4.3 CAPILLARY TUBE
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Discharge the refrigerant by using a refrigerant
recovery system.
3. Remove the orifice. (Refer to Section 2.2.1)
4. After discharging the refrigerant completely,
unbraze the interconnecting tube of the capillary
tube.
5. Remove the capillary tube.
6. Re-install by referring to the procedures above.
NOTES
Replacement of the refrigeration cycle. 
1. When replacing the refrigerating cycle, be sure to
discharge the refrigerant by using a refrigerant
recovery system.
2. After discharging the unit completely, remove the
desired components, and unbraze the pinch-off
tubes. 
3. Solder service valves into the pinch-off tube ports,
leaving the valves open. 
4. Solder the pinch-off tubes with service valves.  
5. After doing the above procedures, the valve must
be closed and left in place on the system for any
subsequent procedures.
6. Evacuate as follows: 
6-1. Connect the vacuum pump, as illustrated figure
21A. 
5-2.  Start the vacuum pump. Slowly open manifold
valves A and B with two full turns counterclock-
wise and leave the valves closed. 
The vacuum pump is now pulling through valves
A and B up to valve C by means of manifold and
the entire system. 
CAUTION : If high vacuum equipment is used,
just crack valves A and B for a few minutes, then
open slowly with the two full turns counter-clock-
wise. This will keep oil from foaming and being
drawn into the vacuum pump. 
6-3.  Operate the vacuum pump for 20 to 30 minutes,
until 600 micron vacuum is obtained. 
Close valves A and B and observe vacuum
gauge for a few minutes. 
A rise in pressure would indicate a possible leak
or moisture remains in the system. 
With valves A and B closed, stop the vacuum
pump. 
6-4.  Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure 23B.
Open valve C. 
Discharge the line at the manifold connection. 
6-5. The system is now ready for final charging. 
7. Recharge as follows : 
7-1.  Rotary compressor systems are charged from
the high-side. If the total charge cannot be put in
the high-side, the balance will be put in the 
suction line through the access valve which is
installed as the system is opened. 
7-2.  Connect the charging cylinder as shown in figure
21B. With valve C open, discharge the hose at
the manifold connection. 
7-3.  Open valve A and allow the proper charge to
enter the system. Valve B is still closed. 
7-4.  If more charge is required, the high-side will not
take it. Close valve A. 
7-5.  With the unit running, open valve B and add the
balance of the charge. 
a. Do not add the liquid refrigerant to the low-side. 
b. Watch the low-side gauge, allow pressure to rise
to 30 lbs. 
c. Turn off valve B and allow the pressure to drop. 
d. Repeat steps B and C until the balance of the
charge is in the system. 
7-6. When the unit is operating correctly, use the
pinch-off tool with the unit still running and the
clamp on the pinch-off tube. Using a tube cutter,
cut the pinch-off tube about 2 inches from the
pinch-off tool. Use sil-fos solder and solder the
pinch-off tube closed. Turn off the unit, allow 
setting for a while and then test the leakage of
the pinch-off connection. 
—10—
—11—
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment, pinch-off tool capable
of making a vapor proof seal, leak detector, tubing cutter, hand tools to remove components, service valve. 
B
A
B
A
B
A
COMPOUND GAUGE 
SEE INSETS
BELOW
CAPILLARY TUBE 
EVAPORATOR
(LOW PRESSURE SIDE)
COMPRESSOR
CONDENSER
(HIGH PRESSURE SIDE)
EXTERNAL VACUUM PUMP
LO      HI    CHARGING CYLINDER
MANIFOLD
GAUGE
C
Figure 21A-Pulling Vacuum
Figure 21B-Charging 
—20—
5. CIRCUIT DIAGRAM 
• MODEL : LWH0560ACG/ACL
MOTOR
C
F
H
7
8
6
4
2
1
5
3
H
L
M
POWER INPUT 
ROTARY SWITCH
THERMOSTAT
BR
BK
RD
BL
BK
RD
BL
OR(BR)
YL
BK(BR)
(Plain)
WH(BL)
(Ribbed)
GN(GN/YL)
COMP.
YL
OR(BR)
R
S
C
YL
ROCKER SWITCH
BR
BR
SYNC. M.
CAPACITOR
BK
RD
BL
BK
RD
BL
BR
OLP
5
1
2
9
6
8
7
3
4
10
3854AR2330A
WIRING DIAGRAM
Q'TY 
PER SET
1
1
1
1
1
1
1
1
1
1
LOCATION
NO.
1
2
3
4
5
6
7
8
9
10
DESCRIPTION
POWER CORD ASM
FAN MOTOR
COMPRESSOR
ROTARY SWITCH
THERMOSTAT
CAPACITOR
CONDUCTOR ASM
OVERLOAD PROTECTOR
CONNECTOR ASM
CONNECTOR ASM
LWH0560ACG
2H01580M
4681A20001B
5416A20001E
2H00154H
2H01109H
6120AR2194H
2H01045E
6750U-L047A
6631AR3843K
6877A20001A
PART NO.
3828AR3735S  —1—
6. EXPLODED VIEW
2
3
4
E
F
A
1
1
10
3
4
1
2
1
2
1
2
9
6
2
5
7
5
8
10
8
4
7
1
2
3
4
5
6
7
11
6
12
9
8
9
10
5
4
3
4
3
7
6
B
D
C
3
Page of 14
Display

Click on the first or last page to see other LWH0560ACG_ACL service manuals if exist.