DOWNLOAD LG LWC1260ACG Service Manual ↓ Size: 3.43 MB | Pages: 127 in PDF or view online for FREE

Model
LWC1260ACG
Pages
127
Size
3.43 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
lwc1260acg.zip
Date

LG LWC1260ACG Service Manual ▷ View online

—32—
COMPLAINT
CAUSE
REMEDY
Test capacitor.
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean of replace.
Close if open.
Determine if the unit is properly sized for the area to
be cooled.
Check the set screw or clamp. If loose or missing,
correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.
Remove the cabinet and carefully rearrange tubing
not to contact cabinet, compressor, shroud, and
barrier.
Set the knob to HIGH COOL or LOW COOL while
rocker switch is ON.
Check terminals. If loose, repair or replace.
Check the synchronous motor for open circuit.
Capacitor
Wiring
Refrigerating system
Air filter
Exhaust damper door
Unit undersized
Blower or fan
Copper tubing
Rotary switch.
Wiring
Synchronous motor.
Insufficient cooling or
heating
Excessive noise.
Auto air-swing fails.
—23—
4.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two kinds.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling.
Ineffective Cooling 
Check of outdoor coil
(heat exchanger) & the fan
operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the
unit is beyond repair.
Satisfactory operation with
temperature difference of
inlet & outlet air ; 
44~50
°
F(7~10
°
C) 
Check heat load 
increase.
Clean condenser.
Not on separate circuit.
Check inside gas
pressure.
Adjusting of refrigerant
charge.
Malfunction of compressor.
Replacement of
compressor.
Check of cold  air circulation
 for smooth flow.
Dirty indoor coil
(Heat exchanger)
Stop of auto air-swing
Correct above trouble
Check clogging in refrigera-
tion circuit.
Repair clogging in refrigera-
tion circuit.
Obstruction at air outlet
Clogged of air filter.
Malfunction of fan
—24—
Fails to Start
Check of circuit breaker
and fuse.
Gas leakage of feeler bulb
of thermostat
Check of control switch.
Fan only fails to start.
Improper wiring.
Defect of fan motor
capacitor.
Irregular motor resistance
(    ).
Irregular motor insulation
(    ).
Replacement of fan motor.
Regular but fails to start.
Replacement of compressor
(locking of rotor, metal).
Improper thermostat setting.
Loose terminal connection.
Improper wiring.
Irregular motor resistance (    ) 
Irregular motor insulation (     )
Replacement of compressor
(Motor damaged)
Drop of power voltage.
 Capacitor check.
Replacement
Compressor only fails to
start.
Defect of compressor
capacitor.
Check of power source.
Check of control switch
setting.
—25—
Is the Trans output power
AC 220V?
Is the Trans output power
about AC 13V?
Is shorted the Trans. output?
Is output Voltage of IC2
DC 12V?
Is output Voltage of IC3
DC 5V?
Is the voltage No.20 of IC1
DC 5V?
Exchange Main PCB Ass'y.
Is the 
connection between
Main and Display 
all right?
Is the reset circuit all right?
(The No.16 of 
IC1 is 5V..)
• Check the Fuse.
• Check the wiring diagram.
• Check the Main 
  PCB pattern.
• Exchange the Trans.
• Exchange BD1.
• Exchange IC2.
• Exchange IC3.
• Exchange IC4, C07.
• Connect connector
  exactly.
• Check the PCB 
  pattern.
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES
ELECTRIC PARTS TROUBLESHOOTING GUIDE 
Possible Trouble 1
• The unit does not operate.
Page of 127
Display

Click on the first or last page to see other LWC1260ACG service manuals if exist.