DOWNLOAD LG LS-T186CEL Service Manual ↓ Size: 2.73 MB | Pages: 58 in PDF or view online for FREE

Model
LS-T186CEL
Pages
58
Size
2.73 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ls-t186cel.zip
Date

LG LS-T186CEL Service Manual ▷ View online

2) Balance refrigerant of the 2-way, 3-way valves  
(Gas leakage)
• Procedure 
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat. 
(2) Connect the charge set to the 3-way valve’s
port.  
–  Leave the valve on the charge set closed. 
– Connect the charge hose with the push pin to
the service port.  
(3) Open the valve (Lo side) on the charge set
and discharge the refrigerant until the gauge
indicates 0 kg/cm
2
G.
–  If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not
running is higher than 1 kg/cm
2
G), discharge
the refrigerant until the gauge indicates 0.5 to 1
kg/cm
2
G. if this is the case, it will not be
necessary to apply a evacuatin. 
– Discharge the refrigerant gradually; if it is
discharged too suddenly, the refrigeration oil
will also be discharged. 
Lo
Open
Open
3-Way
valve
2-Way
valve
Gas side
CLOSE
OPEN
Outdoor unit
Liquid side
Indoor unit
-40-
3. Evacuation 
(All amount of refrigerant leaked)
• Procedure 
(1) Connect the vacuum pump to the charge set’s
center hose 
(2) Evacuation for approximately one hour.  
–  Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).  
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump. 
–  Vacuum pump oil.
If the vacuum pump oil becomes dir ty or
depleted, replenish as needed. 
Lo
Open
Open
Vacuum pump
2-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
OPEN
-41-
4. Gas Charging 
(After Evacuation)
• Procedure 
(1) Connect the charge hose to the charging
cylinder. 
–  Connect the charge hose which you dis-
connected from the vacuum pump to the valve
at the bottom of the cylinder. 
– If you are using a gas cylinder, also use a scale
and revers the cylinder so that the system can
be charged with liquid. 
(2) Purge the air from the charge hose.   
–  Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid
refrigerant).  The procedure is the same if
using a gas cylinder. 
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
–  If the system can not be charged with the
specified amount of refrigerant, it can be
charged with a little at a time (approximately
150g each time) while operating the air
conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1
minute and then repeat the procedure
(pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port. 
–  Stopping par tway will allow the gas to be
discharged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose. 
(5) Mount the valve stem nuts and the service
port nut. 
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage. 
\
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner. 
Lo
Charging
cylinder 
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way
valve
3-Way
valve
OPEN
Open
Check valve
(1)
-42-
Cycle Troubleshooting Guide 
Trouble analysis 
1. Check temperature difference between intake and discharge air and operating current. 
Temp. Difference 
Temp. difference   :   approx. 0°C
Current                  :   less than 80% of 
rated current  
Temp. difference   :   approx. 8°C
Current                  :   less than 80% of 
rated current  
Temp. difference   :   less than 8°C
Current                  :   over the reated
current 
Temp. difference   :   over 8°C 
Operating Current 
• All amount of refrigerant leaked
out. Check refrigeration cycle.
• Refrigerant leakege
Clog of refrigeration cycle
Defective compressor 
• Excessive amount of refrigerant
• Normal 
Notice : 
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger. 
2. Check temperature and pressure of refrigeration cycle. 
Notice : 
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G(Cooling) at normal condition. 
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty. 
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal valve)
Defective compressor
Current is low.
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of 
operation.
Insufficient amount of 
Current is low.
Lower Higher
refrigerant 
(Leakage)
Clogging
Current is low.
High 
Higher  
-43-
Page of 58
Display

Click on the first or last page to see other LS-T186CEL service manuals if exist.