-54-
• Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands 
Normal
• Check the connecting condition of CN-U/D Connector
• Check the soldering condition(on PWB) of CN-U/D Connector
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts
in the rotation radial of the Vertical Louver
5. When Vertical Louver does not operate.
Check the operating circuit of the Vertical Louver
• Confirm that there is DC +12V between pin
(RED) of CN-U/D and
GND.
• Confirm that there is a soldering short at following terminals.
- Between 
,    , 
and 
of MICOM
- Between 
,    ,    and 
of IC01M
- Between 
,    ,      and 
of IC01M
60
3
4
5
11
12
13
61
62
63
6
14
-55-
6. When Heating does not operate
Operate “Heating Mode(     )” by setting the desired temperature of the
remote control is higher than one of the indoor temperature by 2°C at
least.
In heating Mode, the indoor fan operates in case the pipe temperature
is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
• Check the related circuit of R02H(12.1K), R04H(6.2K), 
Micom(No. 26, 27).
• Check the indoor room temperature is disconnected or not (about
10K
/at 25°C).
• Check the indoor pipe temperature is disconnected or not (about
5K
/at 25°C).
Turn ON Main Power
Check the DC voltage on the PWB ASS’Y
• The details of check are as followings
Check point
Between Micom
(NO.59) and GND
Between IC01M
(NO.15) and GND
Comp ON
DC 5V
Below DC 1V
Comp OFF
DC 0V
About DC
12V
Check point
Between Micom
(NO.51) and GND
Between IC02M
(NO.15) and GND
4 way ON
DC 5V
Below DC 1V
4 way OFF
DC 0V
About DC 12V
Check point
Between Micom
(NO.53) and GND
Between IC02M
(NO.14) and GND
Fan ON
DC 5V
Below DC 1V
Fan OFF
DC 0V
About DC 12V
• Comp Relay.
• 4 way Relay
• Outdoor fan Relay
-56-
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor, 4 way.
• Check the "open" or "short" of connecting wires between indoor and
outdoor.
-57-
Electronic Control Device 
1
LS-L1261CL/1263DL
6871A10009B
6.8K
OPEN
1K
5.1K
10K
39K
2
LS-L1262CL
6871A10009D
6.8K
OPEN
1K
5.1K
10K
39K
3
LS-L1261HL/EL
6871A10009A
91K
56K
1K
5.1K
10K
91K
4
LS-L1262HL
6871A10009M
91K
56K
1K
5.1K
10K
91K
5
LS-L1220HL
6871A10009C
91K
56K
1K
3K
6.8K
56K
PCB ASS'Y SVC PART LIST
NO.
MODEL
P/NO
OPTIONAL FUNCTION
OR1H
OR2H
OR3H
OR4H
OR5H
OR6H
(1) MAIN P.W.B ASM
(2) MAIN P.W.B ASM
Page of 75
Display

Click on the first or last page to see other LS-L1261HL service manuals if exist.