Remote Control Operation Mode
• When the remote control is selected by the slide switch on the main unit, the appliance operates according to
the input by the remote controller.
Protection of the evaporator pipe from frosting
• If the indoor pipe temp is below 0°C in 7 min after the compressor operates without any pause while in cooling
cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evapora-
tor pipe from frosting.
• When the indoor pipe temp is 7°C or higher after 3 min pause of the compressor, the compressor and the out-
door fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
• When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds.
• When the appliance-pause key is input by the remote controller, the long “beep—” sounds.
• When a key is input by the remote controller while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound “beep-beep-beep-beep-beep-” is made 10 times to indicate that the
remote control signal cannot be received.
Self Diagnosis Operation
Thermistor Error Indicator
• When the indoor pipe sensor or the room temperature sensor is open or is shorted, the error is indicated.
• To indicate the error, the operation LED (or the cooling LED) flashed at 3 sec interval.
• When the error is cleared, the LED stops flashing, the operation (or cooling) LED is on.
• While in appliance pause, the error is not indicated.
• Since the airflow quantity and speed are controlled by the adjustment of the vane angle using the Wind-up
effect, you can enjoy the natural and pleasant wind uniformly at any location in the room.
• Since the indoor outflow air is sucked again by the upper/lower vanes, the indoor temperature drop is mini-
mized and the pleasant humidity is maintained.
Air Cleaner Operation
• When an air cleaner function is selected during Air Conditioner operation
- Plasma air cleaner function will be operated while in any operation mode with selecting the function.
- The function is to be stopped while it is operating with selecting the function.
• When an air cleaner function is selected during operation off
- The function will be only operated.
• When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be
stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B)
will be operated again.
- 22 -
- 23 -
Display Function
1. Heating Model
2. Cooling Model
• Cooling, Soft Dry, Fan, Heating
• Cooling, Soft Dry, Fan
• Sleep Mode
• Sleep Mode
• Timer Mode
• Timer Mode
• Hot-start, Deice
Self-diagnosis Function
Thermistor Cut Off or Short
Cut Off/Short : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)
Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below 0°C after 7 minutes from starting the compressor, the compressor
and outdoor fan is stopped, and then after 3 minutes delay of operating of the compressor, when the tempera-
ture of the indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Deicer Indicator
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Compressor on Indicator
OUT
DOOR
- 23 -
Display Function
1. Heating Model
2. Cooling Model
• Cooling, Soft Dry, Fan, Heating
• Cooling, Soft Dry, Fan
• Sleep Mode
• Sleep Mode
• Timer Mode
• Timer Mode
• Hot-start, Deice
Self-diagnosis Function
Thermistor Cut Off or Short
Cut Off/Short : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)
Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below 0°C after 7 minutes from starting the compressor, the compressor
and outdoor fan is stopped, and then after 3 minutes delay of operating of the compressor, when the tempera-
ture of the indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Deicer Indicator
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Compressor on Indicator
OUT
DOOR
- 23 -
Display Function
1. Heating Model
2. Cooling Model
• Cooling, Soft Dry, Fan, Heating
• Cooling, Soft Dry, Fan
• Sleep Mode
• Sleep Mode
• Timer Mode
• Timer Mode
• Hot-start, Deice
Self-diagnosis Function
Thermistor Cut Off or Short
Cut Off/Short : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)
Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below 0°C after 7 minutes from starting the compressor, the compressor
and outdoor fan is stopped, and then after 3 minutes delay of operating of the compressor, when the tempera-
ture of the indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.