-58-
When indoor Fan does not operate.
Trouble 4
Check the SSR high speed operation by remote control.
(the Indoor Fan Motor is connected)
Turn off main power.
Check the connection of CN-FAN.
Check the Fan Motor.
Check the Fuse(AC250V, T2A).
Turn on the main power
Check the related circuit of indoor Fan Motor.
• The pin No.10 of micom and the part for driving SSR.
• Check the related pattern.
• Check the SSR.
- SSR Open: Indoor Fan Motor never operate.
- SSR short: Indoor Fan Motor always operates in case of ON or OFF.
The voltage of Pin No 1(orange) and 3(black) of CN-FAN.
About AC 180V over
About AC 50V over
SSR is not damaged
Check SSR
-59-
• Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the vertical louver with hands
Normal
• Check the connecting condition of CN-U/D Connector
• Check the soldering condition(on PCB) of CN-U/D Connector
Check the operating circuit of the vertical louver
• Confirm that there is DC +12V between pin 
of CN-U/D and GND.
• Confirm that there is a soldering short at following terminals.
- Between
,
,
➂ 
and 
of MICOM
- Between 
4
,  
5  ,   6   
and  
7
of IC01M  
- Between 
10
11 ,  12 
and 
13
of IC01M
When the horizontal louver does not operate.
Trouble 5
If there are no problems after above checks.
• Confirm the assembly condition that are catching and interfering parts in the link of the
vertical louver
-60-
Does the Operating LED of indoor unit blink
when Operation's ON?
Is the Connection between indoor power
relay Pin 
and terminal block No. 1 right?
Refer to the self-diagnosis function.
The Outdoor Unit does not operate at all.
Trouble 6
YES
Check the connecting state of connector
NO
NO
Is the connection of cable between indoor
and outdoor unit right?
Indoor
Outdoor
1(Brown)
1(Brown)
2(Blue)
2(Blue)
3(Green/YL)
3(Green/YL)
4(Red)
4(Red)
NO
YES
Is the voltage of CN-POWER 
,
in
outdoor PCB Ass'y about AC220V / 240V
when Operation's ON?
Check the Fuse of Outdoor PCB Ass'y.
NO
YES
Is the voltage of CN-AC 
,
in outdoor
PCB Ass'y about AC220V / 240V?
Check the PTC and RY-PWR.
NO
YES
Is the Bridge Diode(DB01Z) right?
Replace the Bridge Diode.
NO
YES
Replace the PCB Ass'y.
NO
-61-
Does the LED01M of outdoor PCB Ass'y
blink 6 times?
Check the state of connecting cable (3 line)
between indoor and outdoor uint.
When compressor does not operate normally.
DC Peak Error(Error Code 
)
Trouble 7-1
NO
YES
Is the connecting state of connectors in
outdoor Sub. PCB Ass'y right?
(CN-UVW, CN-IPM)
• Electrical wiring diagram (Colors)
• Check the connecting state of connectors
in PCB Ass'y(Main/Sub)
• If CN-UWV is connected, the comprressor
can be operated a opposite direction.
NO
YES
Is the power module in Sub PCB Ass'y
right?
• Check the short P-N P-U, V, W, and N-U,
V, W of IPM and then collector, emiter of
IGBT
• Replace the Sub PCB Ass'y.
NO
YES
Is the voltage of CN-AC over than
AC170V?
Check the supplied voltage.
NO
YES
Is the voltage of CN-DC over than about
DC380V?
• Check CN-IPM connector(Pin No. 12)
• Replace the Sub PCB Ass'y.
NO
YES
Is the refrigerant pressure right?
Replace the PCB Ass'y.
• Main PCB Ass'y
• Sub PCB Ass'y
• Control Box Ass'y
Supply the refrigerant.
NO
NO
Page of 68