DOWNLOAD LG LS-J0961HL Service Manual ↓ Size: 1.16 MB | Pages: 71 in PDF or view online for FREE

Model
LS-J0961HL
Pages
71
Size
1.16 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ls-j0961hl.zip
Date

LG LS-J0961HL Service Manual ▷ View online

-27-
Connecting 
cable
Drain hose
Indoor/outdoor
connecting cable
Connecting
cable
Taping
Gas side piping
Liquid side piping
Drain hose
Press the lower left and right side of the unit against the
Installation Plate until the hooks engage with their slots
(sound click).
6. Wrap the insulation material around the connect-
ing portion.
7. Wrap the tubing, the drain hose and the connect-
ing cable with tape.
8. Indoor unit installation
• Hook the indoor unit onto the upper portion of
installation plate. (Engage the two hooks of the
rear top of the indoor unit with the upper edge of
the installation plate.)
Ensure the hooks are properly seated on the instal-
lation plate by moving it left and right.
CAUTION
Take care to arrange the piping, drain hose and
cables as the figure 7 page for inserting it into the
indoor unit and mount the indoor unit on the installa-
tion plate.
-28-
Outdoor unit 
Liquid side piping
(Smaller Dia.)
Torque wrench
Gas side piping
(Bigger Dia.)
1) Connecting the piping to the Outdoor
unit
1. Align the center of the piping and sufficiently
tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow
on the wrench.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring,
be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source.
5) Confirm that electrical capacity is sufficient.
6) See to it that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the nor-
mal function of a overload protection device.
• Proper starting power is not given to the compressor.
3. Connecting Piping and Cable to the outdoor unit
Outdoor unit
Pipe Size
Torque
Liquid Side (1/4")
1.8kg.m
Gas Side (3/8")
4.2kg.m
Gas Side (1/2")
5.5kg.m
Connecting 
cable
Terminal block
(Pillar terminal)
Cover control
Outdoor unit
Over
5mm
Holder for 
connecting 
cable
Over 5mm
Terminal block
(Pillar terminal)
Holder for 
power supply 
cord
Cover control
Connecting cable
Over 5mm
Terminal block
(Pillar terminal)
Holder for
power supply
cord
Cover control
Connecting cable
-29-
2) Connection of the cable
1. Remove the cover control from the unit by loos-
ening the screw.
Connect the wires to the terminals on the control
board individually as the following.
Outdoor unit
Outdoor unit
(LS-F1260HL)
(9K Btu Series)
2. Secure the cable onto the control board with the holder
(clamper).
3. Refix the cover control to the original position with the
screw.
4. Use a recognized circuit breaker 16A between the power
source and the unit. A disconnection device to adequately
disconnect all supply lines must be fitted.
1(L)
Terminals on the outdoor unit
Terminals on the outdoor unit
Terminals on the indoor unit
Terminals on the indoor unit
1(L)
1(L)
1(L)
2(N)
2(N)
2(N)
3
4
3
4
2(N)
BROWN BLUE
G/Y
BLACK
RED
BROWN BLUE
G/Y
RED
BROWN
BROWN BLUE
BLACK
BLACK
G/Y
RED
RED
G/Y
BLUE
BROWN
BLUE GREEN/YELLOW
BROWN
BLUE GREEN/YELLOW
1) Cooling only type
2) Cooling & Heating type
The power cord connected to the indoor unit should
be complied with the following specifications (Type
H05VV-F approved by HAR or SA).
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications (Rubber insulation, type H07RN-F
approved by HAR or SA).
NORMAL CROSS-
SECTIONAL AREA
1.0mm
2
NORMAL CROSS-
SECTIONAL AREA
1.0mm
2
Color of Wires
Color of Wires
The length of the power supply cord should be over 1.8m measured from the power supply cord entry of the cabinet to the
middle of the live pin of the plug.
Color of Wires
Color of Wires
(7K Btu Series)
Connecting 
cable
Terminal block
(Pillar terminal)
Cover control
Outdoor unit
Over
5mm
Holder for 
connecting 
cable
Over 5mm
Terminal block
(Pillar terminal)
Holder for 
power supply 
cord
Cover control
Connecting cable
Over 5mm
Terminal block
(Pillar terminal)
Holder for
power supply
cord
Cover control
Connecting cable
-29-
2) Connection of the cable
1. Remove the cover control from the unit by loos-
ening the screw.
Connect the wires to the terminals on the control
board individually as the following.
Outdoor unit
Outdoor unit
(LS-F1260HL)
(9K Btu Series)
2. Secure the cable onto the control board with the holder
(clamper).
3. Refix the cover control to the original position with the
screw.
4. Use a recognized circuit breaker 16A between the power
source and the unit. A disconnection device to adequately
disconnect all supply lines must be fitted.
1(L)
Terminals on the outdoor unit
Terminals on the outdoor unit
Terminals on the indoor unit
Terminals on the indoor unit
1(L)
1(L)
1(L)
2(N)
2(N)
2(N)
3
4
3
4
2(N)
BROWN BLUE
G/Y
BLACK
RED
BROWN BLUE
G/Y
RED
BROWN
BROWN BLUE
BLACK
BLACK
G/Y
RED
RED
G/Y
BLUE
BROWN
BLUE GREEN/YELLOW
BROWN
BLUE GREEN/YELLOW
1) Cooling only type
2) Cooling & Heating type
The power cord connected to the indoor unit should
be complied with the following specifications (Type
H05VV-F approved by HAR or SA).
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications (Rubber insulation, type H07RN-F
approved by HAR or SA).
NORMAL CROSS-
SECTIONAL AREA
1.0mm
2
NORMAL CROSS-
SECTIONAL AREA
1.0mm
2
Color of Wires
Color of Wires
The length of the power supply cord should be over 1.8m measured from the power supply cord entry of the cabinet to the
middle of the live pin of the plug.
Color of Wires
Color of Wires
(7K Btu Series)
Page of 71
Display

LG LS-J0961HL Service Manual ▷ Download