16. Portection from overheating of power module
• If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
• It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
• It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
17. Portection from overheating of compressor
• If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
• It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
-25-
Comp. off
Comp. free
Fc-1
Fc-2
Target frequency
Toff (84
°
C)
Ton + 2
°
C (78
°
C)
Ton + 5
°
C (81
°
C)
Ton (76
°
C)
130
°
C
118
°
C
111
°
C
108
°
C
-13
°
C
-30
°
C
101
°
C
93
°
C
Fhmin
OFF
OFF
0Hz
Fc-2
Fc-1
Setting frequency
[The control graph from heat–sink TH]
18 . Defrosting control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing,
reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
• Defrosting control is available 50 minutes later since heating cycle started and the pipe temperature of out-
door unit reaches below -6°C.
-26-
50 min
Setting frequency
Setting speed
Setting
speed
OFF
OFF
ON
OFF
OFF(Cooling cycle)
Setting
frequency
30 sec
Fc-1 step
Operating
frequency
of compressor
4 Way valve
Outdoor fan
Indoor fan
Defrost LED
Fc-1
Fh+1
OFF
ON
ON(Heating cycle)
ON
ON
Low
(FhMAX-2 or
FhMAX-3)
30 sec
30 sec
8 min or
over 25˚C(120sec)
30 sec
1 min
How to operate the power display (LS-_NL Series)
• It must be displayed the power level that will be operating frequency of compressor.
• It indicates power levels that compressor operating frequency is controlled to depend on indoor and outdoor
conditions.
• It is displayed as below.
Heat mode operation
- Power level 1: below Step 3 of COMP. operating frequency
- Power level 2: below Step 6 of COMP. operating frequency
- Power level 3: below Step 10 of COMP. operating frequency
- Power level 4: below Step 14 of COMP. operating frequency
- Power level 5: over Step 14 of COMP. operating frequency
Operation mode except heat mode operation
- Power level 1: below Step 2 of COMP. operating frequency
- Power level 2: below Step 8 of COMP. operating frequency
- Power level 3: below Step 10 of COMP. operating frequency
- Power level 4: below Step 12 of COMP. operating frequency
- Power level 5: over Step 12 of COMP. operating frequency
-13-
Power Level 1
Power Level 2
Power Level 3
Power Level 4
Power Level 5
-14-
2. Protection of the evaporator pipe from frosting
• If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in
cooling cycle operation mode, 
➔ 
compressor, outdoor fan are turned off.
• When indoor pipe temp. is 7°C or higher after 2 min pause of compressor 
➔ 
compressor, outdoor fan is turned on according to the condition of the room temperature.
3. Protection of the indoor fan from droplet formation (Enclosure
sweat and condensed disposal test)
• Control condition : The system operates standard operation without this condition as follows.
- Setting temperature <25°C
- Indoor fan speed  
low speed
- Outdoor temperature < 31°C
• Control method
- Operation frequency of compressor must be below 
(refer to the comp. Freq. table)
- The indoor fan operates at medium speed.
Comp. free
Comp. off
0˚C
7˚C
Indoor pipe
temp.
Comp. free
Comp. Step 4
3˚C
3
°
C
Indoor pipe
temp.
Page of 127