DOWNLOAD LG LS-C322MLD0_MMB0_MMM0 / LS-H322MLD0_MMB0_MMM0 / LS-C366NLD0_NMM0 / LS-H366NLB0_NLD0_NMM0 / S36LHP Service Manual ↓ Size: 6.27 MB | Pages: 95 in PDF or view online for FREE

Model
LS-C322MLD0_MMB0_MMM0 LS-H322MLD0_MMB0_MMM0 LS-C366NLD0_NMM0 LS-H366NLB0_NLD0_NMM0 S36LHP
Pages
95
Size
6.27 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ls-c322mld0-mmb0-mmm0-ls-h322mld0-mmb0-mmm0-ls-c36.zip
Date

LG LS-C322MLD0_MMB0_MMM0 / LS-H322MLD0_MMB0_MMM0 / LS-C366NLD0_NMM0 / LS-H366NLB0_NLD0_NMM0 / S36LHP Service Manual ▷ View online

- 35 -
4. AIR PURGING 
1) Air purging
Air and moisture remaining in the refrigerant system
have undesirable effects as indicated below.
■ Pressure in the system rises.
■ Operating current rises.
■ Cooling(or heating) efficiency drops.
■ Moisture in the refrigerant circuit may freeze and
block capillary tubing.
■ Water may lead to corrosion of parts in the refrig-
eration system.
Therefore, the indoor unit and tubing between the
indoor and outdoor unit must be leak tested and
evacuated to remove any noncondensables and
moisture from the system.
2) Air purging with vacuum pump
1. Preparation
■ Check that each tube(both liquid and gas side
tubes) between the indoor and outdoor units have
been properly connected and all wiring for the test
run has been completed. Remove the service
valve caps from both the gas and the liquid side
on the outdoor unit. Note that both the liquid and
the gas side service valves on the outdoor unit
are kept closed at this stage.
2. Leak test
■ Connect the manifold valve(with pressure gauges)
and dry nitrogen gas cylinder to this service port
with charge hoses.
■ Pressurize the system to no more than 150 P.S.I.G.
with dry nitrogen gas and close the cylinder valve
when the gauge reading reached 150 P.S.I.G.
Next, test for leaks with liquid soap.
■ Do a leak test of all joints of the tubing(both indoor
and outdoor) and both gas and liquid side service
valves. 
Bubbles indicate a leak. Be sure to wipe off the
soap with a clean cloth.
■ After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder.
When the system pressure is reduced to normal,
disconnect the hose from the cylinder.
Be sure to use a manifold valve for air purging. If it is not
available, use a stop valve for this purpose. The "Hi"
knob of the manifold valve must always be kept close.
CAUTION
To avoid nitrogen entering the refrigerant system in a
liquid state, the top of the cylinder must be higher than
its bottom when you pressurize the system. Usually,
the cylinder is used in a vertical standing position.
CAUTION
Lo
Hi
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas
cylinder(in vertical
standing position)
Pressure 
gauge
30K, 32K
36K, 38K
- 36 -
3. Evacuation
■ Connect the charge hose end described in the 
preceding steps to the vacuum pump to evacuate
the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is
open. Then, run the vacuum pump.
The operation time for evacuation varies with tubing
length and capacity of the pump. The following
table shows the time required for evacuation.
■ When the desired vacuum is reached, close the
"Lo" knob of the manifold valve and stop the 
vacuum pump.
4. Finishing the job
■ With a service valve wrench, turn the valve stem
of liquid side valve counter-clockwise to fully
open the valve.
■ Turn the valve stem of gas side valve counter-
clockwise to fully open the valve.
■ Loosen the charge hose connected to the gas
side service port slightly to release the pressure,
then remove the hose.
■ Replace the flare nut and its bonnet on the gas
side service port and fasten the flare nut securely
with an adjustable wrench. This process is very
important to prevent leakage from the system.
■ Replace the valve caps at both gas and liquid
side service valves and fasten them tight.
This completes air purging with a vacuum pump. 
The air conditioner is now ready to test run.
(1) Remove the caps from the gas side and liquid side valves.
(2) Remove the service-port cap from the gas side valve.
(3) To open the gas side valve turn the valve stem counter-
clockwise approximately 90°, wait for about 2~3 sec, and
close it.
(4) Apply a soap water or a liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a
soft brush to check for leakage of the connecting points of
the piping.
(5) If bubbles come out, the pipes have leakage.
Soap water method
Gas side
Liquid side
Cap
Hexagonal wrench
3-way valve
(Open)
3-way valve
(Close)
Required time for evacuation 
when 30 gal/h vacuum pump is used
10 min. or more
15 min. or more
If tubing length is less
than 10m (33 ft).
If tubing length is longer
than 10m (33 ft).
Indoor unit
Outdoor unit
Lo
Hi
Manifold valve
Vacuum pump
Pressure 
gauge
Open
Close
Indoor unit
Outdoor unit
30K, 32K
36K, 38K
- 37 -
5. TEST RUNNING
1. Check that all tubing and wiring have been prop-
erly connected.
2. Check that the gas and liquid side service valves
are fully open.
1. Prepare remote control
Remove the battery cover 
by pulling it according to the
arrow direction.
Insert new batteries making 
sure that the (+) and (–) of 
battery are installed correctly.
Reattach the cover by
pushing it back into position.
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use
rechargeable batteries.
• Remove the batteries from the remote control if
the system is not going to be used for a long time.
2. Settlement of outdoor unit
■ Anchor the outdoor unit with a bolt and
nut(ø10mm) tightly and horizontally on a concrete
or rigid mount.
■ When installing on the wall, roof or rooftop, anchor
the mounting base securely with a nail or wire
assuming the influence of wind and earthquake.
■ In the case when the vibration of the unit is con-
veyed to the hose, secure the unit with an 
anti-vibration rubber.
3. Evaluation of the performance
Operate unit for 15~20 minutes, then check the sys-
tem refrigerant charge:
1. Measure the pressure of the gas side service
valve.
2. Measure the temperature of the intake and dis-
charge of air.
NOTE: If the actual pressure are higher than shown,
the system is most likely over-charged, and
charge should be removed. If the actual pres-
sure are lower than shown, the system is most
likely undercharged, and charge should be
added.
The air conditioner is now ready for use.
Bolt
Tubing connection
Outside ambient TEMP The pressure of the gas side service valve
35°C(95°F)
4~5kg/cm
2
G(56.8~71.0 P.S.I.G.)
This is performed when the unit is to be relocated
or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the out-
door unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the
unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the
charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the
air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cool-
ing operation.
5. When the low-pressure gauge reading becomes 1 to
0.5kg/cm
2
G(14.2 to 7.1 P.S.I.G.), fully close the gas
side valve stem and then quickly turn off the unit. At
that time, Pump Down has been completed and all
refrigerant gas will have been collected in the outdoor
unit.
PUMP DOWN
3. Ensure the difference between the intake temper-
ature and the discharge is more than 8°C
(Cooling) or reversely (Heating).
4. For reference; the gas side pressure of optimum
condition is as below.(Cooling)
Discharge
temperature
Discharge air
Intake temperature
- 38 -
Operation 
■ Name and Function-Remote Control
The remote control transmits the signals to the system.
START/STOP BUTTON
Operation starts when this button is pressed and stops
when the button is pressed again.
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high
and CHAOS.
JET COOL
Used to start or stop the speed cooling. (Speed cooling
operates  super high fan speed in cooling mode.)
CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired
up/down airflow direction.
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation. 
TIME SETTING BUTTONS
Used to adjust the time. 
TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained
and to cancel the Timer operation.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating. 
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
PLASMA(OPTIONAL)
Used to start or stop the plasma-purification function. 
HORIZONTAL AIRFLOW DIRECTION CONTROL 
BUTTON (NOT ON ALL MODELS)
Used to set the desired horizontal airflow direction.
RESET BUTTON
Used prior to resetting time or after replacing batteries.
2nd F Button
Used prior to using modes printed in blue at the bottom of
buttons. 
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON
OFF
CANCEL
SET
1
3
5
4
9
10
12
14
16
7
2
8
13
15
11
6
Cooling Operation
Auto Operation
Healthy Dehumidification Operation
Flip-up door
(opened)
Heating Operation
Signal transmitter
• Cooling Model(
), Heat Pump Model(
)
Remote Control
Page of 95
Display

Click on the first or last page to see other LS-C322MLD0_MMB0_MMM0 / LS-H322MLD0_MMB0_MMM0 / LS-C366NLD0_NMM0 / LS-H366NLB0_NLD0_NMM0 / S36LHP service manuals if exist.