Service Manual  45
Troubleshooting Guide 
1. Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 220V/AC240V, 50Hz)
• Main power's voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting cable
• Check PWB Ass'y
- Fuse
- Pattern damage
- Varistor(ZNR01N)
Check the connection housing for contacting
• Connector related to CN-POWER
• Connector related to CN-MOTOR
• Connector contacting of Outdoor Fan/Compressor
• Display PWB Ass'y Check
Check each load(Indoor/Outdoor Fan Motor,
Compressor, Stepping Motor) and contacting 
condition of related connector
NO
YES
(After 10 seconds)
Electronic Parts
Main PCB Board Operation Check
Items
• SMPS Transformer
(Indoor unit)
- Input Voltage
- Output Voltage
• IC04D(7805) Output
• IC01A(Reset IC)
OSL01B(8MHz)
• Replace P/Module
• Replace IC04D
• Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About DC12V±115V
- About DC15V±2V (Motor Drive)
• DC +5V
• Voltage of Micom No. 36,
(DC +4.5V over) and Soldering condition.
Content
Remedy
46 Room Air Conditioner
Troubleshooting Guide 
2. The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote controller
Cause by the remote controller
When the mark(       ) is displayed in LCD screen, replace
battery.
Check the contact of CN-DI, 2 connector.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the
low speed by force.)
Check DISP PWB Ass'y
- Voltage between CN DISP 
: DC +5V
When the detect switch(double key) inside the remote 
controller door is fault, it is impossible to operate 
temperature regulating( / ) and wind speed selecting.
Check the connecting circuit between the remote controller
MICOM (No. 
61
) - R1 - TR - TR - LED - R2
Check point
• Check the connecting circuit between PIN 
-
Rø1L(1K) - Cø1L(680PF) - MICOM PIN
• Check Receiver Ass'y
Service Manual  47
Troubleshooting Guide 
3. Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode(     )" by setting the desired temperature of the
remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.
• Check R02H(12.1k), R04H(6.2k), Micom Pin 
26
27
• Check the indoor temperature sensor is disconnected or not(About 10k
/ at 25°C).
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor.
• Check the "open" or "short" of conmecting wires between indoor and
outdoor.
Check Relay(RY - COMP) for driving compressor.
• When the power(About AC220V/240V) is applied to the connecting wire
terminal support transferred to compressor, PWB Assembly is normal.
• Check the circuit related to the relay.
Check point
COMP ON
COMP OFF
Between Micom(No.
DC5V
DC0V
63) and GND
Between IC02M(No. 12)
Below DC 1V
About DC12V
and GND
(app)
48 Room Air Conditioner
Troubleshooting Guide 
Fan couln't operate for dehumidifying mode.
- Change operation for cooling mode.
Turn off Main power
Check the connection of CN-MOTOR1, 2
Check the Fan Motor (Motor resistance) (fig 1)
Check the Fuse(AC250V/3.15A)
Turn OFF Main Power
- Check the soldering on AC PWB Assembly/DC PWB.
- AC PWB Assembly : check the connection CN-AC/DC 
and 
- DC PWB Assembly : check the connection CN-AC/DC 
and 
4. When indoor Fan does not operate.