-21-
2. Flaring Work and Connection of Piping
1) Flaring work
Main cause for refrigerant leakage is due to defect in
the flaring work. Carry out correct flaring work using the
following procedure.
1. Cut the pipes and the cable.
• Use the piping kit accessory or pipes purchased locally.
• Measure the distance between the indoor and the
outdoor unit.
• Cut the pipes a little longer than the measured
distance.
• Cut the cable 1.5m longer than the pipe length.
2. Burr removal
• Completely remove all burrs from the cut cross sec-
tion of pipe/tube.
• Put the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid drop-
ping burrs into the tubing.
3. Putting nut on
• Remove flare nuts attached to indoor and outdoor
unit, then put them on pipe/tube having completed
burr removal.
(not possible to put them on after flaring work)
4. Flaring work
• Firmly hold copper pipe in a die in the dimension
shown in the table above.
• Carry out flaring work using flaring tool as shown
below.
5. Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Copper
pipe
90
°
Slanted   Uneven  Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Pipe
Reamer
Point down
Flare nut
Copper tube
mm
inch
mm
Ø6.35
1/4
0~0.5
Ø9.52
3/8
0~0.5
Ø12.7
1/2
0~0.5
Ø15.88
5/8
0~1.0
Ø19.05
3/4
1.0~1.3
Outside diameter
Torque
2) Connection of piping Indoor
• Preparing the indoor unit's piping and drain hose for
installation through the wall.
1. Route the indoor tubing and the drain hose in the
direction of rear left or right.
2. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
NOTE: If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.
3. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
• Align the center of the pipes and sufficiently tighten
the flare nut by hand.
• Tighten the flare nut with a wrench.
• When extending the drain hose at the indoor unit,
install the drain pipe.
4. Wrap the insulation material around the connecting
portion.
• Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.
• Wrap the area which accommodates the rear piping
housing section with vinyl tape.
-22-
Drain hose
Connecting
cable
Gas side piping
Liquid side piping
Drain hose
Loop
Indoor unit tubing
Flare nut
Pipes
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
GAS
LIQUID
Capacity
(Btu/h)
18K
5/8"[6.6kg.m]
1/4"[1.8kg.m]
Pipe Size[Torque]
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection
pipe
Connecting cable
Vinyl tape
(wide)
Wrap with vinyl tape
Indoor 
unit pipe
Pipe
-23-
• Bundle the piping and drain hose together by wrap-
ping them with vinyl tape for enough to cover where
they fit into the rear piping housing section.
3) Connection of the pipes-Outdoor
1. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Outdoor unit 
Liquid side piping
(Smaller diameter)
Gas side
piping
(Bigger
diameter)
Torque wrench
Outdoor unit 
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
Installation Information (For right piping)
• Good case
For right piping. Follow the instruction below.
Press on the upper side of clamp and
unfold the tubing to downward slowly.
• Bad case
Following bending type from left to right could cause
problem of pipe damage.
CAUTION
mm
inch
kg.m
Ø6.35
1/4
1.8
Ø9.52
3/8
4.2
Ø12.7
1/2
5.5
Ø15.88
5/8
6.6
Ø19.05
3/4
6.6
Outside diameter
Torque
-24-
3. Connecting The Cable Between Indoor Unit and Outdoor Unit
1) Connect the cable to the Indoor unit.
• Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in
dividually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and
the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
Air 
Conditioner
Main power source
If a power plug is not to be used, provide a circuit breaker
between power source and the unit as shown below.
Circuit Breaker
Use a circuit
breaker or time
delay fuse.
CAUTION
CAUTION
The power cord connected to the "A" unit should be
complied with the following specifications
(Type "B" approved by HAR or SAA).
5k~9k 12k~14k
18k
24k~28k 30k, 32k 36k, 38k
0.75
1.0
1.5
2.5
2.5
5.5
Unit(A)
Indoor
Indoor
Indoor
Indoor Outdoor Outdoor
Cable Type(B) H05VV-F H05VV-F H05VV-F H05VV-F H05RN-F H05RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
5k~9K 12k~14k
18k
24k~28k
0.75
1.0
1.5
2.5
Cable Type(B) H07RN-F H07RN-F H07RN-F H07RN-F
NORMAL
CROSS
-SECTIONAL
AREA
Grade
30k, 32k
36k, 38k
0.75
0.75
Cable Type(B) H07RN-F H07RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm
2
)
(mm
2
)
(mm
2
)
The power connecting cable connected to the indoor
and outdoor unit should be complied with the following
specifications
(Type "B" approved by HAR or SAA).
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
 
• The above circuit diagram is subject to change with-
out notice.
• Be sure to connect wires according to the wiring dia-
gram.
• Connect the wires firmly, so that not to be pulled out
easily.
• Connect the wires according to color codes by refer-
ring the wiring diagram.
CAUTION
• When installing, refer to the circuit diagram on the
Control Box of Indoor Unit.
• When installing, refer to the wiring diagram on the
Control Cover Inside Outdoor Unit.