–24–
Checking the Drainage and Form the Piping
1. Checking the Drainage
¤
Remove the inlet grille with your hands as
shown (right and left) and pull in the direction
indicated by the arrow.
¤Ł
Check the drainage
• Pour a glass of water into the drain pan.
• Ensure if water flows drain hose of indoor unit.
–25–
2. Form the Piping
¤
Wrap the connecting port of indoor unit with the
insulation material and secure it with two Plastic
Bands. (for the right Piping) 
• If you connect an additional drain hose, the end of
the drain-outlet should be water, and fix it on the
wall to avoid swinging in the wind.)
¤Ł
Tape the Piping, and Connecting Cable from down
to up.
¤Ø
From the piping gathered by taping along the exte-
rior wall fix it on the wall by saddle or equivalent.
¤
Tape the piping and connecting cable from down
to up.
¤Ł
In order to prevent water from entering the room,
tape the piping from a trap.
¤Ø
Fix the piping onto the wall with saddle or bracket.
¤
When using the drain elbow hose, use a mount of
3cm of higher.
¤Ł
In the cold district (0°c continued for 2~3 days),
the drain water is frozen and the fan fails to func-
tion, do not use the drain elbow.
In case the outdoor unit is installed below 
position of the indoor unit.
In case the outdoor unit is installed upper position
of the indoor unit.
Drain water treatment of outdoor Unit(Heat Pump
Only)
,
,
,
,
,
Trap
Trap
Seal a small opening around
the piping with gum type sealer.
Gas side
piping
Main cable
Liquid side
piping
Connecting
cable
Trap is required to prevent the electrical parts
from entering the water.
Drain elbow
Hose(inner diameter ø20)
Arrange the hose downward slope without waving.
–16–
2. Indoor Unit installation
¥L
The mounting floor should be strong and solid
enough to prevent it from vibration.
¥M
Drill the piping hole with 70mm diameter hole-
core drill at either the right or the left of indoor
unit. The hole should be sightly slant to the out-
door side.
¥N
Insert the plastic tube through the hole.
¥O
Cut the extruded outside part of the plastic tube,
if necessary.
3. Outdoor unit Installation
¥L
Install the outdoor unit on the concrete or any
solid base securely and horizontally by securing
it with bolts (Ø12mm) and nuts.
¥M
If there is any vibration transmitted to the build-
ing, mount the rubber underneath the outdoor
unit.
4. Refrigerant amount
Before shipment, this air conditioner is filled with
the rated amount of refrigerant including additional
amount required for air-purging, subject to 5m pip-
ing length. (The rated amount of refrigerant is indi-
cated on the name plate.) But when the piping
length exceeds 5 meters, additional charge is
required according to the following table.
(Unit: g)
Example)  
In case of 10m long pipe(one-way), the amount of
refrigerant to be replenished is:
(10 - 5) x 30 = 150g
Wall
Core Drill
Tilt 
Cut if necessary
More than 15mm
Wall
Plastic tube
(Bushing)
INSIDE
OUTSIDE
200mm
70mm
70mm
90mm
MODEL
30K
(BTU/h) 
REFRIGERANT CHARGE
30 per 1m
–17–
Installation Method
No.
Installation works
Descriptions
1
Preparation of tools and installation parts
Preparation of installation
2
Flaring the pipes
To insert the flare nuts, mounted on the 
connection parts of both indoor and 
outdoor unit, onto the copper pipes.
3
Pipe bending
To reduce the flow resistance of refrigerant.
4
Connection of installation parts
Connection of long piping
(elbows, socket etc)
5
Tighten the flare nut (outdoor) 
Connecting the pipings of the outdoor unit.
6
Blowing the pipings
To remove dust and scale in working.
7
Tighten the flare nut (indoor)
Connecting the pipings of the indoor unit.
8
Check a gas-leakage of the connecting 
part of the pipings.
9
Air purging of the piping and indoor unit
The air which contains moisture and which
remains in the refrigeration cycle may cause a malfunction on the
compressor
10
Open the 3-way (liquid side) and 
3-way (gas side) valves.
11
Form the pipings
To prevent heat loss and sweat
12
Checking the drainage (indoor unit) 
To ensure if water flow drain hose of indoor unit.
13
Connecting the cable between outdoor 
Preparation of the operating
and indoor unit 
14
Connecting the main cable to outdoor unit
15
Supply the power to the crankcase heater
To prevent the liquid back to the compressor. 
(Before the operating the unit)
(Heat pump only)
16
Cooling operation, Heating operation
(Use the remote control or display of the
indoor unit)
1. Procedure