LG LP-E5082ZA Service Manual ▷ View online

– 5 –
POWER SOURCE (ø, V, Hz)
COOLING
CAPACITY
Btu/h
W
INPUT
W
CURRENT
A
HEATING
CAPACITY
Btu/h
W
INPUT
W
CURRENT
A
MAKER
TYPE
COMPRESSOR
MODEL
INPUT
W
CURRENT
A
CAPACITY
Kcal/h
NOISE 
INDOOR
dB(A)
LEVEL(1m)
OUTDOOR
AIR
INDOOR
CMM
VOLUME
OUTDOOR
REFRIGERANT R-22
Kg
HEAT
INDOOR
R/C/FPI
EXCHANGER
OUTDOOR
R/C/FPI
FAN
INDOOR
TYPE
OUTDOOR
ROOM TEMPERATURE CONTROL
NET
INDOOR
Kg
WEIGHT
OUTDOOR
DIMENSIONS
INDOOR
mm
(W ¥ H ¥ D)
OUTDOOR
SVC
LIQUID
Inch
VALVE
GAS
(mm)
3,220,60
3,220,60
3,380,60
3,380,60
44,000
44,000
44,000
44,000
12,896
12,896
12,896
12,896
6,000
6,000
4,600
4,600
10
10
8.2
8.2
48,000
48,000
14,069
14,069
5,000
4,500
9
8
Copeland
Copeland
Copeland
Copeland
Recipro
Recipro
Recipro
Recipro
CRNQ-0501-ES8
CRNQ-0501-ES8
CRNQ-0501-ES8
CRNQ-0501-ES8
6,210
6,210
6,210
6,210
19.0/11.0
19.0/11.0
19.0/11.0
19.0/11.0
61,500
61,500
61,500
61,500
53
53
53
53
58
58
58
58
35
35
35
35
104
104
104
104
3.5
3.9
4
4.2
3/28/17
3/28/17
3/28/17
3/28/17
2/44/16
2/44/18
2/44/16
2/44/18
SIROCO
SIROCO
SIROCO
SIROCO
PROPELLER
PROPELLER
PROPELLER
PROPELLER
MICOM CONTROL
MICOM CONTROL
MICOM CONTROL
MICOM CONTROL
62
62
62
62
90
90
90
90
590 
×
1,800 
×
440
590 
×
1,800 
×
440
590 
×
1,800 
×
440
590 
×
1,800 
×
440
900 
×
1225 
×
370
900 
×
1225 
×
370
900 
×
1225 
×
370
900 
×
1225 
×
370
3/8
3/8
3/8
3/8
3/4
3/4
3/4
3/4
MODEL
LP-E50B2CL/CA
LP-E50B2HL/HA
LP-E50B2ZL/ZA
LP-E5090CL
LP-E5092CA
LP-E5092HL/HA
– 6 –
1.4 Functions
Indoor Unit
Power Switch ON/OFF
Operation Mode Control
Sensing the room temperature
Controlling the room temperature
Starting Current Control
Sensing Heat Exchanger Temperature
Timer Delay Safety Control
Indoor Fan Speed Control
Operation Indication lamps
Temperature Setting
Airflow Direction Control
Room temperature Display
Timer Control
Sensing Discharge Air Temperature
• Cooling, Soft Dry, Auto, Fan 
¢¡
Cooling Model
• Cooling, Heating, Soft Dry, Fan 
¢¡
Heat Pump Model
• Room temperature sensor (Thermistor)
• Maintains the room temperature in accordance with the setting temperature.
• Indoor fan is delayed for 3 sec at the starting.
• Heat exchanger temperature sensor (Thermistor)
• Restarting is inhibited for approx. 3 minutes.
• High, Med, Low 
• Up : up to 30°C
• Down : down to 16°C 
• Airflow direction Automatic and Manual control
• Low, 10° ~ 35°C, Hi
• Off Timer (1, 2, 3....7 hour)
• Discharge temperature sensor <Thermistor>
• Apply Heat Pump Model Only.
– 7 –
Remote Control
Operation ON/OFF
Operation Mode Selection
• Cooling, Soft Dry, Auto, Fan 
¤I
Cooling Only Model
• Cooling, Heating, Soft Dry, Fan, 
¤I
E/heater  Heat Pump Model
Fan Speed Selection
Setting the temperature
Timer Control
Airflow Direction Control
• High, Medium, Low
• Up or Down
• Off Timer(1, 2, 3...7 hour)
• Airflow direction Auto-Swing and Manual control
Outdoor Unit
Deice Control
Outdoor Fan Speed Control
Sensing Heat Exchanger Temperature
• De-ice PCB
• One speed
• Heat exchanger temperature sensor (Thermistor)
– 24 –
6.1 Installation of indoor, Outdoor Unit
1) Select the best location
¥L
Indoor unit
• There should not be any heat source or steam near
the unit.
• There should not be any obstacles to prevent the air
circulation.
• The place where air circulation in the room will be
good.
• The place where drainage can be easily obtained.
• The place where noise prevention is taken into con-
sideration.
• Do not install the unit near the door way.
• Ensure the space indicated by arrows from the wall,
ceiling, fence, or the obstacles.
¥M
Outdoor unit
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat radia-
tion from the condenser is not restricted.
• There should not be any animals or plants which
could be affected by discharged hot air.
• Ensure the space indicated by arrows from the wall,
ceiling, fence, or other obstacles.
¥N
Piping length and the elevation.
6. INSTALLATION
MODEL
MAX. Piping length
A (m)
5HP
30
25
MAX. 
elevation
B (m)
A
B
Indoor unit
Outdoor unit
Wall
More
than
50cm
More than
50cm
More than
50cm
More than
100cm
Outdoor
unit
5cm 
5cm 
40cm 
1
0
0
c
m
 
Indoor unit
Page of 80