- 14 -
8. Deicer Control
• Deicing operation is controlled by timer and sensing the outdoor piping temperature in heating operation mode.
• The first deicing starts when 60 minutes or more passed after starting of heating operation and the outdoor
piping temperature is -6°C or lower. 
• Deicing ends after 12 minutes or when the outdoor piping temperature is 12 or higher.
• Heating operation is repeated automatically 60 min. Heating and 12min. Deicing after the first deicing ends.
• The operation diagram is as following.
• In deicing operation, only solenoid valve of the indoor unit operated at that time is ON.
9. Forced operation
• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• When you operate the unit with forced operation switch, the unit isn't always operated in operation mode which
you desire. So you can operate in uour operation mode by only remote controller.
• The standard conditions are as following :
The outdoor
piping Temp.
12°C
DEICING OFF
-6°C 
DEICING ON
COMPRESSOR
4-WAY VALVE
ON
INDOOR FAN
ON
OUTDOOR FAN
ON
ON
ON
ON
ON
ON
LOW
MORE THAN
60MINS
Deicing
Deicing
12MINS
60MINS
12MINS
30 SEC
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
Selecting
fan speed
Cooling
Model
Operation Mode
FAN Speed
Setting Temp.
Heat pump
Room Temp 
24°C
21°C 
Room Temp < 24°C
Room Temp <21°C
Cooling
Cooling
Soft Dry
Heating
High
High
High
High
24°C
24°C
25°C
22°C
- 15 -
10. Micom dehumidify
• In order to raise the efficiency of dehumidify, "Restarting temperature of compressor operation" set higher 1°C
than setting temperature.
• When room temperature is higher than "Restarting temperature of compressor operation", it will be operate by
fan speed setting.
• When room temperature reach "Stopping temperature of compressor operation", the fan and the compressor
will be stop. After 5mins passed, only fan start to operate in low mode for 2 min.
• When room temperature is between "Restarting temperature of kcompressor operation" amd "Stopping
temperature of compressor operation", operate micom dehumidify mode for 10 mins and fan operate low
speed.
• Fan will be stop after 10mins passed to operate imcom dehumidify or below or "Stopping temperature of com-
pressor operation" after 4 mins.
• When 5 mins passed after stopping compressor, fna start to low mode and 7 mins passed after stopping,
compressor start to operate micom dehumidify again. (When micom dehumidify operate, fan will operate at
low speed.)
• When room temperature is below of "Stopping temperature of compressor operation", fan will stop 5 mins and
operate 2 min in low mode.
• In micom dehumidify mode, control of fan speed is as following.
ROOM TEMP.
COMP ON
(SET TEMP. +1°C)
COMP. OFF
(SET TEMP. -1°C)
INDOOR FAN
COMPRESSOR
ON 
OFF
ON
ON
OFF
ON
2MINS
5MINS
5MINS
5MINS
10MINS
10MINS
MAX 4MINS
10MINS
OPERATION
COOLING
DELAY 3 MINS
OPERATION
COOLING
2 MINS
2MINS
MAX
OFF
FAN SPEED
SETTING
LOW
LOW
LOW
LOW
OFF
OFF
OFF
LOW
LOW
- 16 -
11. Different Operation Mode Control
When all units (A-Unit, B-Unit, C-Unit) are operated simultaneously, if each unit is not operated in the same
mode of the unit operated at first, it is not operated.
If operating mode of a unit is different from mode of the unit operated at first, operating LED will be blinking 3
times, besides the indoor and outdoor fan and the compressor will be off.
<Example>
After A-Unit operates in cooling mode at first, B and C-Units operate in heating mode.
¥L
A-Unit
• Cooling mode operation (
¤B
normal display)
¥M
B,C-Unit
• System error operation (
¤B
abnormal display)
After A, B-Unit opertes in heating mode at first, C-Units operate in cooling mode.
¥L
A,B-Unit
• Heating mode operation (
¤B
normal display)
¥M
C-Unit
• System error operation (
¤B
abnormal display)
¡
System error operation : The unit stops operation with blinking operation LED 3 times.
12. Communication control between INDOOR and OUTDOOR
The units are controlled by signal between indoor and outdoor, therefore the unit can be operated incorrectly by
any noise. In this case, you should reoperate the unit by remote controller.
Case 1
Case 2
or
- 17 -
<OUTDOOR UNIT>
1. Solenoid Valve Control
Solenoid valve controls mass of liquid flow of each unit.
(1) Before starting condition
• All teh solenoid valves are off.
(2) In operating mode
¥L
Heating operating mode
• After solenoid valve of each unit operated is ON,
the solenoid valve of units not operated also in ON 30 seconds later.
• But the solenoid valve for by-pass is always OFF.
¥M
Cooling operating mode
• Operating single unit: The solenoid valve operated and the valve for by-pass is ON.
• Operating dual unit: The solenoid valve of each unit operated is ON.
• Operating triple unit: The solenoid valve of each unit operated is ON.
(3) Stopping condition
The solenoid valve is off 3 minutes later.
2. Outdoor Fan Control
• Outdoor fan is set as control of the compressor. That is, as compressor operated, outdoor fan is operated.
• In heatin goperating mode, if discharge pressure of the compressor has been above 24kg/cm
2
g outdoor fan is
off, but if the discharge pressure has been below 20kg/cm
2
g, the outdoor fan is on.
1. Do not operate "cooling" and "heating" operation at the same time.
It may cause troubles.
2. If you operate only one or two indoor units among the three units in heating mode.
1) You mau slightly feel heating sense from the remaining (non-operated) unit(s).
(This product is designed to operate the solenoid valves of outdoor unit and to pass the refrigerant to the
indoor units even you use only one indoor unit out of three units in heating operation)
2) Fan operation of the remaining (non-operated) units is not to be made in case of the above condition. 
CAUTION